Document nNyD9xvOeLjL9amBQ2Q5o64wG
610
CHAPTER 23
1957 GuidS?/
joist spaces and an uninsulated.attic space with a combined U value of 0.05 from room ^ ^ C to outdoor air.
Step t . Heat Loss
Calculate the heat loss of each room by methods outlined in Chapter 12 Heating Load, but do not include any heat loss through the area covered by the panel.
Room dimensions and calculated heat losses are as follows:
Room
Room A Room B Room C
Dimensions Feet*
11x12x8 11 x 12 x 8 15 x 21 x 8
Heat Loss Btu per hour
6300 2500 8000
Step 2. Required Panel Output
Divide the heat loss of each room by the maximum ceiling area in the room which can be used as a heating panel. The result is.the minimum heat output per square foot of panel that will satisfy the requirements of the room. Thepanel that requires the highest output per square foot will generally control the design, because the temperature of the fluid in the system must be high enough to produce the required output from that panel. The required panel output is given in the following table.
Available Panel Area Sq Ft
Room A 132 sq ft
Room B 127 sq ft
Room C 306 sq ft
Required Panel Output, qa Btu/(hr) (sq ft)
6300 ,,,,,, --- = 47.7 132 2500 ----- = 19.7 127 8000 ,,,, , ------ = 26.1 306
Step 8. Panel Surface Temperature
From Fig. 15 find the panel surface temperature needed to yield the required heat output to each room, using the output determined in Step 2 and the design room air temperature. This use of Fig. 15 for Room A is illustrated in Fig. 15A.
Fig. 15A. Determination of Panel Surface Temperature for Room A from Fig. 15
The values of tp determined for Rooms A, B and C are as follows:
Room A tp = 114 F Room B Zp = 92 F ' . Room C . fp = 97 F
Panel Heating
611
PANEL SURFACE TEMPERATURE MINUS AIR TEMPERATURE ABOVE PANEL
Fig. 18. Upward Heat Flow from Plaster Ceiling Panel
DEG.
Step 4- Upward Heat Flow
Determine the upward heat flow from each panel using Fig. 18. The upward heat, flow must be aeternuned in order to obtain the downward panel resistance
to select the proper size of boiler. The use of Fig. 18 is illustrated for Room A in Fig. 18A. Note that the U values shown on Fig. 18 are those for the entire struc-
Fig. 18A. Determination of Upward Heat Flow for Room A from Fig. 18
ture of which the panel is a part and are taken from room air (temperature, Za) to
air above the panel (temperature, Zb) and for that reason qn ^ U(Zp -- Zb)-. .U values
ay be obtained from Chapter 9 Heat Transmission Coefficients of Building Ma
terials.
.
..
The values of gQ for Rooms A, B and C as determined from Fig. 18 are aa follows:
Room
A B
_C
U
0.25 0.25 0.05
fp - fb F Deg
42 20 97
Btu/(hr) (sq ft)
12.5 6 5
5. Downward Panel Resistance
tu ^8s^me tentative pipe or tube spacings for the panel construction to be used from 086 listed in Table 1, choosing the closer spacings when higher outputs are re-