Document n9wxoOXpzqBvbbbmw0dBmJdEX
32786 . '
Efk 560/6-764W5
PCBs IN THE UNITED STATES INDUSTRIAL USE AND ENVIRONMENTAL DISTRIBUTION
TASK I
- AA '
`
. <*$
.**
&
*^
V
FEBRUARY 25, 1978 FINAL REPORT
U.S. ENVIRONMENTAL PROTECTION AGENCY OFFICE OF TOXIC SUBSTANCES WASHINGTON, D.C. 20440
PLAINTIFFS |EXHIBIT NO.-TM
hD f(-ri~/t
DGFEXP0011653
HARTOLDMONOOOQ494
GEHRV 32903
itecfe' r
Voltages listed cover the majority of askarel distribution trans formers, Product scope includes up to 34,500 primary volts and virtually any secondary voltage, 34,500 and below.
Quantities of askarel used in this class of transformers are in the range of 500 to 5,000 lbs. iii each unit depending on the rating and the size of the transformer.
A great majority of distribution type transformers have pro vision for venting. Many of these units are equipped with spring loaded venting devices which vent upon a pressure excursion, and diaphragm rupture discs are offered as a customer option,
B, Askarel Fewer Transformers
1. Secondary substation
(a) load center units
{b) Secondary substation generation units
(c) switchboard units (d) Internal units (e) JYbtor control units These 5 comprise the largest group of askarelinsulated transformers and they find widespread, application in the automobile, paper, chenical, textile, steel, nonferrous metal, conent, mining and petroleum industries. They are used in com mercial and public buildings, such as schools and hospitals; In defense and nuclear energy installations; and by private and public utilities.
2. Master unit substation 3. Primary unit substation 4. Limited ampere substation 5. industrial furnace
-85-
DEFEXP0011770
HARTOLDMONOOOQ495
Furnace transformers used in the hot, dirty atmosphere in proximity to glass melting and induction furnaces, which require high current, low voltage power supplies (receive up to 15,000 volts and contain 2000 to 4000 lbs. of askarel each), Existing technology does not permit construction of sealed dry-type transformers for these power ratings.
6. Rectifier
Rectifier transformers used for large rolling mills and DC industrial power supplies (receive up to 15,000 volts AC and deliver low voltage high amperage DC. tech unit contains about 19,000 lbs. of askarel). These units are covered by the same canments given for industrial furnace transformers.
7. Transportation
Railroad transformers used on-board in electric locorotives
or multiple unit electric railroad cars (receive up to 25,000 volts and contain
700 to 2400 lbs. of askarel in each unit depending on the rating and size of the
transformers).
.
(a) Third rail
These transformers are 'used for rapid transit systems, and. are basically serving a rectifier _ function
(b) Loccrootive
Erica: to 1932, all on-board transformers were open
dry type. Because of problems with then, railroads
went to askarel-insulated -transformers. The changes
in locomotive design since the 1930's would not now
accomodate open dry-type' transformers as replacsnents
for askarel units, A recent trend has been to replace
askarel by oil units, and this will continue unless
new Department of Transportation regulations require
nonflammability.
.
-86-
DEFEXP0Q11771
HARTOLDMONOOOQ496
GEHRV 32905
i
However, since a tunnel fire in 1340 caused by an oil filled locomotive transformer, Penn Central will not allow any oil containing transformer equipped locatiotive into New York City.
(c) .Multiple-unit car (MU)
These transformers are mounted under the flat-bed of passenger cars. They ride along am this location, ' about 8 inches above the rail, at speeds up to 150 inch. The transformer irrust be ruggedly built to with stand the impact of flying debris and constant vibra tion. Power to the cars is brought in through an overhead catenary and is fed to the underside of the car where the transformer, controls, and propulsion equipment are located.
' Space and weight are critical in this application. There are only about 33 inches above the rail. The width of the transformer is limited by the width of tile car.
Only oil- or askarel-insulated units would provide the required performance levels in the space avail able. As with ioccsiDtive applications, present Department of - Transportation regulations do not restrict the use of flamnable' liquids, and the use of askarel units has been dictated largely by the economic considerations of fire insurance rates, and by Penn-Central safety regulations.
8, Reactors
These units provide reactance (receive up to 15,000 volts
under nornral operating conditions. During normal operating conditions, they
deliver volts and current as received. During power surges they choke the voltage
and deliver the normal output) .
.
9, Grounding,transformers (receive up to 15,000 volts).
-87-
DEFEXP0011772
HARTOLDMONOOOQ497
Railroad locomotives which, operate on high voltage AC power from overhead catenaries are used in the U.S. Northeast Corridor, Askarel-filled transformers are mounted in the engines or under the self-powered passenger cars, and reduce the catenary voltage to that required by the traction motors, these electric locomotives are mostly limited to passenger service on the Northeast AMERKK routes and on the commuter lines around Philadelphia and New York. Large askarel-filled transformers are used in the old GG-I loccnotives, under the Rtetroliner cars, in various comiter cars, and in the new E-60 Icconotives. (Twenty-sir E-60 Icccmotives are currently being delivered-to AMTRM by General Electric; each loccsrotive contains 710 gallons of askarel) . Penn-Central Railroad operating rules require the use of askarels in all locomotives using the tunnels and stations in New York, lids rule has been in force as a fire safety measure ever since an early GG-I locomotive con taining a mineral oil-filled transformer was involved in a fire inside a tunnel early in the 1940's.
3.5 Present Alternates to the Use of PCBs in Transformers Askarel-filled transformers are only used where considerations of
fire safety, reliability, availability, and cost make such a unit preferable to an oil-filled transformer or to a dry type transformer. These alterna-tive types of transformers are currently used in 95 percent of all applications, and could, with proper engineering design, be used to replace most of the remaining askarel-filled units. Consideration would have to be given to the specific limitations of these designs that presently make askarel-filled transformers preferable for certain applications.
3.5.1 Mineral Oil-Filled Transformers If safety were not a consideration, there is no reason why
oil-filled transfomers could not he used in all applications. .Askarel-filled transformers cost about 1.3 times as much as oil filled units of the same capacity, and thus most users prefer the oil-type where possible. The oilfilled transformers are the same size as the askarel units, and are considerably lighter in weight. In addition, mineral oil has somewhat better heat transfer characteristics than does askarel, and an electrical arc in -mineral oil results in breakdown products that are nan-corrosive.
-254-
DEFEXP0011939
HARTOLDMONOOOQ498