American Society of Heating and Ventilating Engineers Guide, 1929
in length or for leaders which are not straight, the ratio of stack area to leader area should be greater than 70 per cent in order to offset the
Chapter VIII--Gravity Warm-Air Furnace Heating.
binations with the nearest comparable case as shown in these figures. Any second floor stack supplying heat to a room whose heat loss is 9000
greater temperature losses (Fig. 2) in the longer leader. In gravity circulating systems, this stack to leader area ratio is a very important consideration. Specific data for a great variety of cases are presented in Figs. 4 and 5 and the designer should check his stack to leader corn-
172
B.t.u or above (see Figs. 4 and 5 which show that high temperatures are necessary if rooms of more than 9000 B.t.u. requirement are heated by stacks'in 4-in., studding), should be run within 6-in. studded walls or should have multiple stacks. Stack sections, wherever possible, should
173