Document n90kLK2bwGB9NDRnK4ELRLgNz
FILE NAME DuPont DUP DATE 1966 Sept 1
DOC DUP108
DOCUMENT DESCRIPTION Meeting Minutes - Standards Section - Safety and Fire Protection Subcommittee - from Aug 30 Meeting
i
1029 >
QU POND am" sUsGnes Ont
E. I. DU PONT DE NEMOURS & CompaNY
.
WILMINGTON DELAWARE 19898
ENGINEERING DEPARTMENT
CC
Ferguson Items D. W.
HUID19
HUID19
.
12 - 23
C. E. Marsh Item 16
W. D. Webb ~ tem16
J.
J.
W. M.
Farrell
Jr.
Item
1
Item 22
16
)
H. A. Heidelberger Design -
Item 22
A. C. Elsasser Item 23
R. 32
September 1 1966
00449
PRESENT ABSENT
C. HOLDER JR - CHAIRMAN - EMP REL F. T. BODURTHA JR - ESD
W. A. BOWER - PLASTICS - WILM
WILM
.
G. W. CAWMAN - ORCHEM - CHAMBERS WORKS
C. R. GROVES FMP REL - WILM
K. E. KEUPER - CONSTRUCTION
H. LEWIS > EXPLO - CARNEY'S POINT - DEV LAB
.
D. M. HALL ALT FOR W. G. RIDLEY - TEX FIB - WAYNESBORO
E. A. ROBE - F & F - PHILADELPHIA
E. A. TSCHOPP - DESIGN
R.
SECTION
W. STANDARDS S. KISER - PIGMENTS - NEWPORT~
E. J.
WILFERT - GSD - WILM
STANDARDS SECTION - SAPETY AND FIRE PROTECTION SUBCOMMITTEE
MINUTES
THE MEETING
HELD TUESDAY AUGUST 30
1966
AT 9:00 A.M. IN ROOM 13418 NEMOURS BUILDING
APPROVAL OF MINUTES
:
The minutes of the last meeting were approved
NOTE Followin arge the dates agreed to for the next 3 meetings
September 27 Novemberl Novemberl November 29
No change Was October 25 Was November 22
1 1967 WORK FORECAST
The following item was added to the list prepared last month
Trailers used as temporary offices
new
This may be developed in conjunction with appropriate &
subcommittees
2 ELECTRIC FORK TRUCKS The Chairman reported that he had received a reply from Under-
writers Laboratories stating in effect that since our comments
applied to trucks which were several years old Underwriters'
Laboratories felt they could take no action ~ Holder agreed
to locate through Purchasing a recently purchased Type EE truck
fer
and have it checked against Underwriters Laboratories specification
BETTER THINGS FOR BETTER LIVING THROUGH CHEMISTRY
Safety and Fire Protection
Subcommittee Minutes
-2-
.
004500450 0
C. Holder also will reply to the letter from D. G. MacLean Chambers Works pointing out that this subcommittee agrees
with the use of the Type EE truck as permitted in Specification SV2A
S12G - LABORATORY DESIGN CRITERIA
It was reported that J. D. Wilson has promised a revised draft
by October 30
F20E - DEPTH OF COVER FOR OUTSIDE UNDERGROUND FIRE MAINS
This revised standard was approved for issue
Floc - FIRE HOSE COUPLING SPECIFICATION
It was agreed to omit Bellewood Cooper and Wyandotte Tulsa will be added
River
F & F Warehouses
This standard was approved for issue
F9G - SOLVENT DISPENSING ROOM Recommendations to change Par 6.1 and add a new Par 6.2
by submitted W. G. Ridley June 27 1966 were discussed at
length The subcommittee disagreed with these recommendations and concluded that no change should be made in the standard
S2H - RESPIRATORY PROTECTIVE EQUIPMENT F. T. Bodurtha is scheduled to report in September
S10P - METAL SCAFFOLDS
S7F - SCAFFOLD PLANK K. E. Keuper is scheduled to report in September
PROTECTION OF OPENINGS IN FIRE WALLS
Due from & in October
10
25B - BARRICADES FOR PROCESS EQUIPMENT
It was suggested
that some information be included on the use
of blasting mats such as were used at Louisville H. Lewis will contact F. A. Loving and F. M. Willis for their comments
and will reply to the comments received from R. P. Delano
Discussion will be continued
11 12
F6J - FLAMMABLE VAPOR AND GAS DETECTORS
Deferred due to the absence of W. S. Kiser
S1H - AIR DISTRIBUTION SYSTEMS FOR AIR MASKS
W. A. Bower reported
that
he will
have a revised draft before
the next meeting He plans to include information regarding
use of portable compressor filters etc. This should satisfy
the request made by the Protective Coatings Subcommittee for
information on air supplied to sand blasting hoods
13 14
S1E - SAPETY SHOWERS
C. R. Groves asked that this be deferred until next month
F7H a EMERGENCY SHUTOFF FOR GAS SUPPLY LINES
E. A. Tschopp asked that this be deferred until next month
.
arenes
am
"
Safety and Fire Protection
. Subcommittee Minutes
-3-
15 REAFFIRMATION
00451
16.
S1B S17B
S8G S9R
S4G F11G
Reaffirmed
Reaffirmed
"
Keuper will report next month Cawman will report next month Robb will report next month
S2P - PRESSURE TESTING |
The subcommittee reviewed recommendations in a
July 15 1966 from J. W. Farrell Jr. to K. E.
letter dated
Keuper
a Lubricating oils - the subcommittee objected to including this service due to the potential fire hazard should a leak occur
b Brine - Approved
17
18.
c Air increased limits of 150 220 - Approved
a Inert gas increased limits 150 150 - Approved
HEAT VENTS FOR FIRE
C. Holder had no report
F18B - FIRE DAMPERS FOR DUCTS E. A. Tschopp had no report
19.
20
F1D - FIRE PUMPS
E. A. Tschopp had no report
S2T - THRESHOLD LIMIT VALUES
.
F.
T. Bodurtha reviewed with subcommittee members the importance
of reporting TLV data which can be used by ACGIH as a basis for
establishing threshold limit values This is particularly
important in those cases where Du Pont feels that the TLV presently is too low
21
F4H - FLAMMABLE LIQUID STORAGE TANKS the
C. R. Groves submitted a revision clarifying the definition of
gravity flow This was approved for issue
22
B2W >> PIXED LADDERS
.
A. J. Schwertfeger Explosives Department brought to the sub-
committee's attention the fact that the standard B2W does not
limit the straight unbroken length of fixed ladders while ASA
standard A14.3 - 1956 - requires in Par 6.2 When ladders are
used to ascend to heights exceeding 20 feet except on chimneys
landing platforms should be provided for each 30 feet of height or fraction thereof Each ladder section should be offset
from adjacent sections
Although the subcommittee members do
not believe that
present practices constitute any particular hazard they question the legal implications particularly since many or state codes could probably incorporate ASA A14.3 a
our
did local copy of