Document n8eLwd7QYdp5r5n8xVZ58vkw
American Society of Heating and Ventilating Engineers Guide, 1937'"
7. Size of furnace necessary to supply the warm air required to overcome the hea
loss from the building. This size should include square inches of leader pipe area whi k
the furnace must supply. It is also desirable to call for a minimum bottom fire-on!
diameter in inches, which is the nominal grate diameter.
1)01
8. Area and dimensions in inches of chimney and smoke pipe. If an unlined chimnpv
is to be used, that fact should be made clear.
*7
The heat loss calculations should be made in-accordance with the procedure outlined in Chapter 7, taking into consideration the trans. mission losses as well as the infiltration losses.
LEADER PIPE SIZES
In a gravity circulating warm-air furnace system the size of the leader
to a given room depends upon the temperature of the warm air entering
the room at the register. A reasonable air temperature at the registers
must, therefore, be chosen before the system can be designed. The
National Warm ^4iV Heating and Air Conditioning Association has ap
proved an air temperature of 175 F at the registers as satisfactory for
design purposes. At this temperature, the heat-carrying capacity (heat
available above 70 F) per square inch of leader pipe per hour for first
second or third floors is shown by Fig. 1 at 175 F to be 105, 170 and 208
Btu, respectively. For average calculations, the values 111, 166 and 200
will simplify the work and may be satisfactorily substituted for these
heat-carrying capacities. If H represents the total heat to be supplied any
room, the resulting equations are:
ZJ
Leader areas for first floor, square inches =
approximately 0.009/7 (1)
Leader areas for second floor, square uincuhieas --= --1jgH6g-6 = approximately 0.006//
Leader areas for third floor, square inches = 200 -- approximately 0.005//
In designing for a lower warm-air register temperature, say 160 F, the
factors 111, 166 and 200 become 80, 140 and 166 (Fig. 1 at 160 F), and
the resulting equations are:
f Z7
Leader areas for first floor, square inches = -orjUr- = approximately 0.012H
(4)
Leader areas for second floor, square inches =
= approximately 0.007// (5)
Leader areas for third floor, square inches =
= approximately 0.006// (6)
These equations are applicable to straight leaders from 6 to 8 ft in length. Longer leaders must be thoroughly covered or the vertical stacks must be increased in area as discussed under wall stacks. If some pro vision is not made for these longer leaders, the air temperature may be much lower than anticipated and the room will not be properly heated.
The values shown in Fig. 1 apply only to the case where the straight, leader pipe is 8 ft in length and is connected to stacks whose crosssectional area is approximately 75 per cent of that of the leader pipe.
412
Chapter 23--Gravity Warm Air Furnace Systems 4 v deviation from these conditions requires a modification of the con tacts used in Equations 1, 2, and 3. The temperature drop in leaders of 5 nous lengths at three different register temperatures is shown in Fig. 2,
. sjjould be used to obtain new register temperatures, lower than 175 F, 311 which to base selections from the curves of Fig. 1, and thereby new constants for Equations 1, 2 and 3.
Leader sizes should in general be not less than those obtained by Eauations 1 to 3 nor should leaders less than 8 in: in diameter be used. It is not considered good commercial practice to specify diameters except
in whole inches. The tops of all leaders should be at the same elevation as they leave the furnace bonnet, and from this point there should be a uniform up-grade of 1 in. per foot of run in all cases. Leaders over 12 ft in length should be avoided if possible. In cases/where such leaders are required, the use of a.larger size pipe, than is required by the application of the equations, smooth transition fittings, and duct insulation are recommended.
413