TESTING and CLEANING
aroclor
New or overhauled systems must be TESTED FOR LEAKS and THOROUGHLY CLEANED OUT. This can be done in one operation as follows:
( ill the empty ?\ stcm with cleaning solution (5 lbs. caustic soda and 5 lbs. of soda ash in each 1000 lbs. or 120 gal. of water).
I 'lonm^ltly vent the system to insure complete filling, ( 'o>e the vents and start the circulation pump.
>i :rt (lie burner at !-i ere. heat liquid to )80eF. Circulate solu tion at least 24 hours.
During this time, periodically chain ml from a low spot some of the solution and replace this volume with clear water. Do this until the fluid in the system is clear. This takes about 24 hours.
When clear, raise the exit llni.l temperature to 215-225F., then turn (he burner and pomp
Next dram the entire y cem and i>pe:t ill \ enty Residual heat will dry out the moisture. When inspection shows the system is thoroughly dry, ilm-e all drain*. and u.nt*>.
Now till ihe U'ti'tn oitli Nlojisant'^Vn'.OprJ.idL^ until the expan sion tank gauge reads 1/4 full.
start ihe umij.it iry.y pump and turn .d'':Jmraemm_at !<m I'y.u. Heat the fluid to 250 F. (return temp.) over a two-hour period. During this time, sent ihe ones cyerj UMo nmuites to allow any residual water vapor and air to escape. Reinspect the entire system for leaks while fluid circulates. Again inspect the expansion tank
to make sure it is 1/4 full.
Finally, set_the_ burner !<>r iujl bran Bring system up to normal operating temperature, \djust nil <<*ntnls for full modulation, Fvnminc aJJ pipelines for expansion, adequate bracing and leaks. Proceed with normal operations,
2.3d 1-0456*4
(over) '
0360997
TOWOLDMON0030600 WATER_PCB-00015069
Card Mo. 2 of 3 on operation of Arodor 1243 heat transfer systems,
GENERAL RECOMMENDATIONS FOR OPERATION and MAINTENANCE
imWl248
HEAT TRANSFER SYSTEMS
The following instructions apply to all Aroclor heating systems and are supplemental to manufacturers' recommendations for the equipment proper.
| (follow those instructions any time a system has been shut d< vn long enough for the Aroclor to cool below 180 F.
Ustart circulation mimn and check c\i>.m-,ion : 11k (should 1)0
i/4TuID" "...... " '
................. .....
.Start burner on lowest t_e;U and maintain Sul! j-hxul.itiun until return n~uid~fcmpcrature readies !_mjj_F.
QSct burner for bill he.it. Resume normal operation when fluid reaches proper temperature.
Shut-down Procedure | (follow these instructions to present localized over-heating when system is being shut down).
in Shut burner off but mainuim :uj[ circulation for at least 1/2 hour to dissipate high residuaFTicat in combustion chamber.
J?Jlf air temperature is under 50F., keep fluid circulating
constantly at 20(TF.
'
Precautions in Case of Power Failure
Power failure automatically interrupts the burner operation. When power resumes, start flie_eircul.il ion jmi.ip to get rid of any vapor pockets that may have formed in the heater tubes. If fluid is still hot (above 180"F.), lull heat may be resumed when pipe knocking (if any) has stopped.
If returning fluid has cooled below 180F. during power failure and initial circulation, follow Start-up 1'nwefl.ne abuse.
For more details, consult Monsanto's booklet on "Aroclor 1248 Heat Transfer Data", or contact