634 CHAPTER 59 4. When electrical defrost is used, and several display cases ire being operated on the same electrical circuit it is advisable to stagger the defrost periods of the cases an hour or more apart to avoid overloading the electrical circuits, unless the wiring has been installed with the total defrost load in mind. Thermostatic expansion valves for liquid refrigerant con trol are most widely used in cases being made today. The size of valve to be used is determined by the refrigerant used, Btu per hour load, and operating refrigerant temperature. Most cases are supplied with expansion valves installed at the factory. On low temperature cases it may be necessary to use pressure limiting thermostatic expansion valves. Hie high pressure created by the heating of the coil for defrost can overload the condensing unit during the pull down period after defrost, where units selected for low temperature ap plication have been used. As an alternate, a crankcase pres sure limiting valve may be used. Some self-contained display case models are being equipped with capillary tubes for liquid refrigerant control. Condensing units are supplied by many manufacturers for their self-contained fixtures. Selection of the proper condens ing unit for remote installations is based on the display case manufacturer's load and other operating conditions. WALK-IN COOLERS Walk-in coolers are required for the storage of meat, pro duce, dairy products, frozen food and iee cream, etc. Their number and size depends on the size of the store. In medium andlargerstores, it isdesirableto have a separate produce cooler as well as a separate dairy cooler. Meat coolers are used in all food stores with storage conditions being 34 to 36 F. Moisture conditions must be confined to a rela tively narrow range, because if too high, bacterial growth, mold, and aliming will be encouraged. If too low, excessive do? hydration will 'occur. Air circulation must be maintained at all times to prevent stagnation, but not so rapid as to cause drying out or burning. Forced air blasts must not be permitted 1962 Guide And Data Book Table 2 .... Minimum Net Liquid Receiver Volume Wdghf--U, Vofuse Hp Co fab Refrigerant 12 22 X 150 6.8 6.2 X 225 10.3 9.3 l 300 13.7 12.4 IK 450 20.5 18.6 2 600 27.4 24.8 3 750 35 32 6 900 41 37 7K 1500 70 64 to strike products. For this reason gravity type coils may be preferred. All modern markets today require low temperature storage. Some prefer a low temperature walk-in, which is used for all low-temperature storage; others prefer batteries of low tem perature reach-ins, individually located, to store frozen foods, frozen meats, ice cream, etc. See Chapter 51, 1961 Gome Am> Data Book for design, construction and performance data. For the regular frozen food department, low tempera ture storage capacity equivalent to the cubic feet of low temperature display equipment in the store has been found to be satisfactory. Forced air typ& coils, are generally used for these coolers because humidity tolerance is not criticaL Off-cycle defrosts are normally used for produce and dairy coolers. Straight-time or time-initiated pressure terminated defrosts are generally used for meat coolers. For low-tempera ture coolers both electric heat defrosts and reverse cycle de frosts are being successfully used. MECHANICAL REFRIGERATION MACHINES Air-cooled, water-cooled, and evaporative condenser types of refrigeration machines are used for food store application. Due to the ever increasing water shortage, more and more air cooled condensers are being used. Usually a machine room or rooms (Fig. 2) are provided to contain condensing units, elec trical controls and sometimes the cooling tower. These rooms should be well ventilated for both water- and air-cooled units. It is suggested that 100 cfm per total horsepower of con densing units should be allowed for proper ventilation of a water-cooled unit machine room. Liquid Receivers Because of the long runs of refrigeration lines frequently found in food stores, and the larger than average refrigerant requirements of multiple display cases, it is necessary that the condensing units be equipped with adequately large liquid re ceivers. Net volumes for liquid receivers as shown in Table 2 have been found to be practical minimuma. Sizing of refrigeration lines, both liquid and suction, are more critical than in the average refrigeration installation because of the typically long horizontal runs and the fre quent use of vertical risers. Recommended refrigerant lion sizes to assure a full feed of liquid to the expansion valve, and proper suction line oil return to the compressor without excessive pressure drop, are shown in Table 3. Suction line* should be insulated for 50 ft from the display case, unles provision is made to run these lines in an area where sweating will not be objectionable. Water Cooling Towers Approximately 30 percent of the supermarkets being h*' stalled today are using water-cooled condensing units, *" Retail food Store Refrigeration 635 Table 3 .... Recommended Copper Refrigerant Une Sizes (inches) Refrigerant 12 Refrigerant 22 Normal Temp HP liquid Suction* Liquid Low Temp Section* low Temp Liquid Suction* Max MM Max MM Max Min Max Min Max MM Max MM K XX X K X HX X X X IK KKK X X K K IX K XKK XK lX X X IK X K K IX X K K X K X X IK IK X K IK IK K K ix X 3 X X IK 1M X K IK IX X X IK X X X IK IK X X IK ix X X IK IK 7X X X 2K IK X X IK ix X X IK IK Tog vertical name * wav -V-nM be provided at tbe bottom of U* riaer end TMiwiwnm line dee ---worry--wT.followed. Lons radios fitting* ebould be need eUjurer pcadbie to minimiai pressure drop. though the trend is toward air cooling. Nearly all of these water-cooled condensing units are installed with a water saving cooling tower due to the shortage or cost of water as writ inadequate sewage capacity. The application of water cooling towers in conjunction with air fj)nditinning is an entirely different engineering problem from applying towers in conjunction with food store refrigera tion, because: 1. Air conditioning is rarely used during the winter months, wbereas food store units are used the year around. The special problems of winter operation of food store refrigeration are to maintain discharge or onnrignging pressure high enough to fully feed the evaporators, and to prevent freezing ofthe cooling water. 2. In air conditioning applications, the units operate nearly constantly at nearly constant load. Refrigeration units applied to food stores, however, cycle frequently and operate under widely differing cooling water requirements from the beginning to the end of the running cycle. The water requirement just after starting is normally at least four times the requirement just before stopping. The problem of maintaining proper water flow for dmnging wmnnl and continually changing load conditions is far more Employ for food store refrigeration than for air conrtiBfining The basic purpose of tire cooling water is, of course, to con trol the condensing or head pressure of the refrigeration unit. In order to obtain lowest operation costs, it is desirable to operate at as low a head pressure as is possible. However, if tiie head pressure is maintained so low that the liquid refrig erant leaving the condenser is cooler than the temperature of the air surrounding the receiver tank or the liquid line, then te-evaporation or flash gas will occur. .When flash gas occurs, the refrigeration capacity begins to drop, the expansion valve capacity is vastly reduced, and its operation becomes erratic. Erratic valve operation resulting in starved evaporators causes the evaporatorto retain oiL Held experience has shown that this has caused many compressor failures. It is of vital importance that no matter what system of controlling condttwing water is used, some means roust be provided to pre vent the head pressure from falling below the refrigerant pressure corresponding to the maximum expected ambient temperature. Recommended practice is to provide year-around control of condensing pressure through the use of a thermostatic con trol of the cooling tower fan (the control being set to turn the Ian off when the water temperature drops to 70 F) and a prop- set condensing pressure-actuated water regulating valve. Valve Settings The water valves should be set to maintain the discharge pressures above the saturation pressure of the refrigerant corresponding to summer mru-hm* room temperatures. As an example, if the summer machine room temperature is 100 F, Refrigerant 12 units should have their water valves set for 117 psig or higher; Refrigerant 22 unite should have their valves set for 200 The use of properly water regulating valves will not cause excessive pressure drop and reduced water flow. Ex perience shows that the normal water valve pressure drop should be below 3 psL The water regulating valve will auto matically vary the amount of water required to provide the desired condensing pressure under all load and under all seasonal conditions, thereby giving maximum year-around economy of operation. Cooling water problems may be classified in the order of their severity as scaling, corrosion, cooling tower wood de terioration, and fouling by growths of algae and slimes. Numerous treatments have been devised, but often a treat ment for a specific condition may aggravate or even create another of the unfavorable conditions noted. For example, cooling water softened by cation exchange usually solves the scaling problem, but then gives rise to wood deterioration as a result of the highly aiim-lino water produced. On the other hand, if sulfuric acid is used to prevent scaling and to avoid high alkalinities, the corrosion problem may become severe. Proper bleed-off and regular water treatment is required to insure the satisfactory performance and full life of the cooling towers, condensers, water pumps and piping. Specialists in this field of water treatment should be consulted, because each locality has different water and atmospheric conditions. Air-Cooled Condensers Air-cooled condenser'type condensing unite are gaining popularity for food store refrigeration as well as for air con ditioning. Their relative freedom from continuous, regular maintenance is one factor in their increasing popularity. This type of unit is used in two major variations: 1. Remole air-cooledcondenser type. This type ol system usually has the air-cooled condensers outdoors, while the compressors and controls for the condensing units are located indoors in a machine room. 2. Complete air-cooled condensing units. This type of system