Document mq8Je4O7xqpyzqdpV1VOa46wZ
NON-POLLUTING TRANSFORMER FLUID
DOW-CORN'NG IS ASKING INDUSTRY HELP IN OBTAINING SILICONE CERTIFICATION
.Acloar silicono dielectric coolant liquid is being offered by
Dow-Corning, Midland, Mich., for u:,,- in small and medium
sized power transformers as a safe alternate to the chemical
.-j^skajetcoqtaining PCB, a substance that'is.now.be inn widely
condemmcd as dangerous when discharged into the environ
ment. ,
" -l
P*.,Extensive data from a series of tests by both Dow and some
transformer manufacturers indicate that silicone liquids
provide o high degree of safety when used as o subsitute for
eskorets in both indoor and outdoor transformers. It is with
tho Indoor applications that the problem arises sinco theso
transformers cannot (according to electrical codes) be
tnsu(otcd with oil, on environmentally sofo substonco, but with
lowflosh point. .
\
There Is o problem however in thot the slllcono material
docs not hevo Notionel Electrical Codo or OSHA recognition,
j and it docs not have third party certification by an organization
( j Vuch as Underwriters Laboratories.
" '
jt *,. P'( pow says that so far, three North American manufacturers I . . fcre using the silicone dielectric fill in some of tho transformers
they ship on request. These ere Wcstinghouso, RTE Corp.,
and Fcrranti-Peckard, Ltd., of Canada. . In these cases,
responsibility for proper clearance with insurance underwriters,
government regulating agencies end local code authorities
rests with the user or purchaser of the liquid in new or refilled
i transformers. Tho silicone fluid also costs about twice as
** fnuch as eskorcl at present. -
v'i . `In the next few years, ell existing eskercl transformers at j . Dow Coming will be retrofitted to eliminate any chance of
tt" J major PCB environmental contamination and to create a baso
t|i j for a service life data collection program. This test is hoped
a -Jo include up to 1,000 transformers.
j * While not quite as resistant to ignition as askcrels, end :
[`.C.. v differing in certain other performance characteristics, the
. - silicone fluid produced by Dow will not ignite before reaching
* a temperature of 750 F., but it is not classed as fire-resistant.
f ' N If the heat source is removed or fluid temperature drops below
:s ; 760 F., burning will stop and the fluid is therefore self
extinguishing. This is much better than oil but not as good as
the askarels with PCBs' which are considered dangerous to fish
end wild life and capable of causing sickness in humans. '
""''YVhat effects have the pressures to reduce energy hsd on spccificetion? , , A New Jersey design firm says, "Transformer vendors are tequired to submit loss figures with their quote so that we can make an economic study based on client payout period. A 5% to G% initial cost saving for a less efficient transformer can
Dow-Corntng is presently asking both manufacturers end
transformer users to participate in its testing program. Users
would participate under on agreement with Dow and their
local code authorities whereby- transformers would bo
refilled with silicone fluid.
. ..
7
rapidly be offset by a more efficient one." ______ --.
Another engineer wrote: "We require contractors to
reimburse the owner for substitutions of equipment with
higher operating costs."
Further comments noted specs for bettor power factor
correction, emphasis on life cycle costing and demand limiters
for industrial plants. Lower lighting levels, higher efficiency
light sources and flexible switching of lighting were also
mentioned.
..
,