Document mpwNma69ORqZm88zRBjrXXn20
366
CHAPTER 26
1959 Guide
in feet. The length of run is not usually known at the out set; hence, it may be necessary to assume some pipe size at the start. Such an assumption frequently is considerably in error, and a more common and practical method is to assume the length of run and to check this assumption after the pipes are sized. For this purpose the length of run usu ally is taken as double the actual length of pipe.
BASIC CHART FOR STEAM PIPE SIZING
Fig. 22 is the basic chart for determining the weight-flow rate and velocity of steam in Schedule 40 pipe for various values of pressure drop per 100 ft, based on zero psig saturated steam. By use of the multiplier charts it may be used at all saturation pressures between 0 and 200 psig.
TABLES FOR PIPE SIZING FOR LOW-PRESSURE
The basic chart, Fig. 22, can be used for sizing pipe on low-pressure systems. The values in Table 5 which are taken from the basic chart provide a more rapid nwmw of selecting pipe sizes for the various pressure drops listed and for systems operated at 3.5 and 12 psig. The weight-flow rates shown for 3.5 psig can be used for saturated pressures from 1 to 6 psig, and those shown for 12 png can be used for saturated pressures from 8 to 16 psig with an error not exceeding 8 percent.
Both Fig. 22 and Table 5 are for use where the flow of
Table 6.... Steam Pipe Capacities for Low-Pressure Systems
(For Use on One-Pipe System* or Two-Pipe Systems fa which Condensate Flows Agomst the Steam Flow)
This table b based on data developed through research investigafioas of the American Society of Heating and Air-Conditioning Engineers
Capacity m Pounds per Hour
Hoeunat Pipe Sc*o, taebo*
Two-Pip* System*
Condense !e flowing egoins 1 steam
Vertical Horizontal
On*-Pip Systems
Supply risers
upfeed
Radiator valves and
connections
Radiator and riser runouts
A
H
m m 2
2H 3 3M 4 5
6 8 10 12 16
flm C*
0*
8 14 31 48 97
159 283 387 511 1,050
1,800 3,750 7,000 11,500 22,000
_ 9
19 27 49
99 175 288 425 788
1,400 3,000 6,700 9,500 19,000
6 11 20 38 72
116 200 286 ' 380 --
__ --__
--
_
7 16 23 42
____
--
__ _
--
F*
7 7 16 16 23
42 65 119 186 278
5___45
--
NtU: Stenm et an average premuxe of 1 peig it used as t bask of
* Do not me Column B far pressure drops of less than Ms pri per 100 ft of equivalent run. Use Fig. S3 or Table 6 instead.
b Do not use Column D for pressure drops of less than H* Pfi per 100 ft of equivalent run except on sixes l in. and over. Use Tig. S3 or Table S instead.
* Pitch of borisootal runouts to risen and radiators should be not less than H in. per ft. Where this pitch cannot be obtained. ruzxmU over 8 ft in length should be one pipe tise larger than called for in this table.
condensate does not inhibit the flow of steam. Columns B
and C of Table 6 are for cases where steam and condensate flow in opposite directions as in risers or runouts that are
not dripped. Columns D, E, and F are for one-pipe systems
and include risers, radiator valves and vertical connections,
and radiator and riser runout sizes, all of which are based on the critical velocities of the steam to permit the counterflow
of condensate without noise. Return piping may be sized with the aid of Table 7, where
pipe capacities for wet, dry, and vacuum return lines are shown for several values of pressure drop per 100 ft of
equivalent length. It is-customary to use the same -pressure drop on both the steam and return sides of a system.
Example t: What pressure drop should be used for the steam piping of a system if the measured length of the longest run is 500 ft, and the initial pressure is not to be over 2 psig?
Solution: It will be asumed, if the measured length of the longest run is 500 ft, that when the allowance for fittings is added, the equivalent length of run will not exceed. 1000 ft. Then, with the pressure drop not over one-half of-the initial pressure, the drop could be 1 psi or les. With a pressure drop of 1 psi and a length of run of 1000 ft, the drop, per 100 ft would be 0.1 psi, while if the total drop were 05 psi, the chop per 100 ft would be 005 psi. In both cases the pipe could be sized for a desired capacity according to the 0.1 and 005 pres sure drop lines in Fig. 22. On completion of the sizing, 'the drop could be checked by taking the longest line and actually calculating the equivalent length of run from the pipe sizes de termined. If the calculated drop is less than that assumed, the pipe size is all right; if it is more, it is probable that there are an unusual number of fittings involved, and either the lines must be straightened or the column for the next lower drop must be used, and the lines resized. Ordinarily, resizing will be un necessary.
CHARTS FOR SIZING PIPE FOR HIGH-PRESSURE
Many installations of heating systems for large industrial-
type buildings have been designed for the use of high-pres sure steam, that is, without the use of pressure-reducing valves. Such systems usually involve the use of unit heaters
or large built-up fan units with blast heating coils. Pressures
on these systems vary from 30 to 150 psi. Temperatures are controlled by a modulating- or throttling-type thermostatic
valve controlled by the air temperature in the room, fan inlet, or fan outlet.
Figs. 23, 24, 25, and 26 provide charts for sizing steam
piping for systems of 30, 50, 100, and 150 psig at various pressure drops. These charts are based on the Moody Fric
tion Factor, which takes into account the Reynolds number and the roughness of the internal pipe surfaces, and contain
the same information as the basic chart of Fig. 22 but in a more convenient form.
Return pipe capacities given in Tables 8 and 9 are based
on the following assumed pressures in the return piping:
Pressure Drop lb/100 Ft
H y* H H
1 2
Pressure m Ketom line (Psig)
30 psi System
H l
2
3 4
150 psi System
IK
2X 5
7H
10 20
The pressure loss and lice loss as given were substituted in the Babcock steam flow formula, and the resulting capac ity was multiplied by 12 for 30-psig systems and by 16 for
Steam Heating Systems
367
Table 7.... Return Main and Riser Capacities for Low-Pressure Systems--Pounds per Hour
(Reference to (his tabte w2f bo made by column falter G through Y) This table b based on pipe lize data dovolopod tbroegh the research envestigation* of The American Society of Heating and Air-Conditioning Engineer!
Hi Psi or K O* Pipe Size Drop per 100 Ft
H* P*I or % Oz Drop per 100 Ft
H Priori Ox Drop per 100 Ft
H Pri or 2 Ox Drop per 100 Ft
H Psi or 4 Oz Drop per 100 Ft
M P or 8 Ox Drop per 100 Ft
Wet Dry Vac. Wet Dry
Voc Wet Dry Vac. Wet Dry
Vac.
Wet
Dry Voc. Wet Dry 'Vat
G H1
K 1 MNO P O R 5
r
U
V
WX
Y
H 125 62
1H 213 130
206
c2
o
5
2K 3
3H
5 6
700 1,180 1,880 2,750 3,880
470 760 1,460 1,970 2,930
42 100 142
200
145 71 143 175 80 175 250 103 249 350 115 350
248 149 244 300 168 300 425 217 426 600 241 600
333 236 388 475 265 475 675 340 674 950 378 950
810 1,580 2,130 3,300 4,580
535 868 1,560 2,200 3,350
815 1,360 2,180 3,250 4,500 7,880 12,600
1,000 1,680 2,680 4,000 5,500
575 950 1,750 2,500 3,750
1,000 1,680 2,680 4,000 5,500 9,680 15,500
1,400 2,350 3,750 5,500 7,750
740 1,230 2,250 3,230 4,830
1,420 2,380 3,800 5,680 7,810 13,700 22,000
2,000 3,350 5,350 8,000 11,000
825 1,360 2,500 3.580 5,380
2,000
5,350 8,000 11,000 19,400 31,000
2,830
11,300 27,300 43,800
x
IK
* 2 o
2H 3 3M 4 5
48 113 248 375 750
48 143 113 244 248 388 375 815 750 1,360
2,180 3,250 4,480 7,880 12,600
48 113 248 375 750
175 300 475 1,000 1,680
2,680 4,000 5,500 9,680 15,500
48 113 248 375 750
249 426 674 1,420
2,380
3,800 5,680 7,810 13,700 22,000
48 113 248 950 375
5,350 8,000
31,000
43^800
Table 8....Return Pipe Capacities for 30' Psig Steam Systems*
Capacity Expressed fa Poond* per Hear
Pipe Size
Drop is Pressure--Founds per 100 Ft fa leaglh
HHMH
1
K 115 170 245 308 365
1 230 340 490 615 730
iK
485
710 1,025 1,290 1,530
m 790 1,160 1,670 2,100 2,500
2 1,580 2,360 3,400 4,300 5,050 2K 2,650 3,900 5,600 7,100 8,400 3 4,850 7,100 10,300 12,900 15,300
7,200 10,600 15,300 19,200 22,800
4 10,200 15,000 21,600 27,000 32,300 5 19,000 27,800 40,300 55,500 60,000 6 31,000 45,500 65,500 83,000 98,000
* NoU: The above table ia baaed an stasia et pressure* of 0
150-pdg systems to obtain the values given in Tables 8 and 9. The return-line pressures used were found by observation of operating systems. The Babcock formula was used in this case since information on condensate flow in return lines based on the Moody Friction Factor is not readily available.
SIZING PIPING FOR ONE-PIPE GRAVITY SYSTEMS
Gravity one-pipe air-vent systems, in which the equivalent length of run does not exceed 200 ft, should be sized by means of Tables 5,6, and 7 and Tig. 22 as follows:
1. For the steam main and dripped runouts to risers where the
Table 9.... Return Pipe Capacities for 150 Psig Steam Systems*
Capacity Expressed fa Pound* per Hour
Drop fa Pressure--Pc per 100 Ft In leagfh
HKXH
2
H
IK
2 2H 3 3K
4 5 6
156 313 650 1,070
232 462 960 1,580
360 690 1,500 2,460
465 910 1,950 3,160
560 1,120 2,330 3,800
890 1,780 3,700 6,100
2,160 3,600 6,500 9,600
3,300 5,350 9,600 14,400
4,950 8,200 15,000 22,300
6,400 10,700 19,500 28,700
7,700 12,800 23,300 34,500
12,300 20,400 37,200 55,000
13,700 25,600 42,000
20,500 38,100 62,500
31,600 40,500 49,200 58,500 76,000 91,500 96,000 125,000 150,000
78,500 146,000 238,000
Nett: The above table is based on iteam at pressure* of 1 to 30 peig.
steam and condensate flow in the same direction, use He ps> drop (Table 5 or Fig. 22).
2. Where the riser runouts are not dripped,and the steam and condensate flow in opposite directions, and also for the radiator runouts where the same condition occurs, use Table 6, Column F.
3. For up-feed steam risers carrying condensate back from the radiators, use Table 6, Column D.
4. For doom-feed systems, the main risers of which do not carry any radiator condensate, use Table 6, Column B.
5. For the radiator valve size and the stub connection, use Table 6, Column E.
6. For the dry-return main, use Table 7, Column O.'
7. For the tvet-return main, use Table 7, Column ff.