CHAPTER 20
1957 Guide
system. Variations in the steam pressure during the warming-up period, when the rate of air elimination, and condensation is high, are dearly indicated in these curves.
It is evident that the condensate flow during the initial warming-up period reaches a peak, which is greater than the constant condensing rate eventually reached when the pressure becomes uniform. Moreover, the peak condensing rate is obtained when the system steam pressure is Tower than that existing during a period of constant condensing rate. It will also be noted that the peak rate of air elimination does not coincide with the higher condensing rate.
Steam Flow
The rate of flow; of dry steam or steam with a small amount of water flowing in the same direction, is in-accordance with the general laws of gas flow, and is a function of the length and diameter of the pipe, the density of the steam, and the pressure drop through the pipe. This relationship
has been established "by Babcock in the formula given at the top of Table 2. In Columns 1, 2, 3, and 4 of this table, the numerical values of the factors for different pressure losses, pipe- diameters, steam densities and lengths of pipe have been worked out in convenient form so that the steam flowing in any pipe may be calculated by multiplying together the proper factors in each column, as shown in the example at the bottom of the table.
Pipe Sizes
The determination of pipe sizes for a given load in steam heating depends on the following principal factors:
1. The initial pressure and the total pressure drop which may be allowed between the source of supply and at the end of the return system.
2. The maximum velocity of steam allowable for quiet and dependable operation of the system, taking into consideration the direction of condensate Sow.
3. The equivalent length of the run from the boiler or source of steam supply to the farthest heating unit.
4. The direction of flow of the condensate, whether against or with the steam-
initial Pressure and Pressure Drop
Theoretically, there are several factors to be considered such as initial pressure and pressure required at the end of the line, but it is most impor-
Steam Heating Systems
519
Table 2. Flow of Steam in Pipes
P = loss in pressure in pounds per square inch. D = inside diameter of pipe in inches. L = length of pipe in feet. d = weight of 1 cu ft of steam. fV = pounds of steam per hour.
W
P = 0.0000000367 ( 1 +
W*L dD*
Cou 1
Pm Size
^a
Orocsa
Se<2M2A0yild~o- Nomina!
Actual Internal Diameter
Pm 6q Inches
Cau2 1
Steam Press.
nia
Cou 3
vi--
or Pm m
Fkst
Cou 4
0.25 65.28 i
1.049 0.864 0.536 -1.0* 0.187
20 2.240
0.50 92.28 m 1.380
1.496 1.178 -0.5* 0.190
40 1.580
1.00 130.5 m 1.610
2.036 1.828 0.0 0.193
60 1.290
2
184.6 2
2.067
3.356 3.710 0.3 0.195
80 1.120
3 226.0 2X 2.469 4.788 6.109 1.3 0.201 100 1.000
4 261.0 3 3.068 7.393 11.183 2.3 0.207 120 0.912
5 . 291.8 m 3.548
9.887 16.705 5.3 0.223 140 0.841
6 319.7 4 4.026 12.730 23.631 10.3 0.248 160 0.793 7 345.3 4H 4.506 15.947 32.134 15.3 0.270 180 0.741
8 369.1 5 5.047 20.006 43.719 20.3 0.290 200 0.710
10 412.7 6 6.065 28.886 71.762 30.3 0.326 250 0.632
12 452.0 7 7.023 38.743 106.278 40.3 0.358 300 0.578
14 488.3 8 7.981 50.027 149.382 50.3 0.388 350 0.538
16 522.0 9 8.941 62.786 201.833 60.3 0.415 400 0.500
20 583.6 10 10.020 78.854 272.592 75.3 0.452 450 0.477
24
639.3 12
12.000 113.098 437.503 100.3 0.507 500 0.447
28 690.5 14 13.250 137.880 566.693 125.3 0.557 600 0.407
32 738.2 16 15.250 182.655 816.872 150.3 0.603 700 0.378
40
825.4
Column 1 X 2 X 3 X.4 - lb of steam 175.3 0.645
800 0.354
48 904.1 pipe for a given condition.
200.3 0.685 900 0.333
80
1167.2
Example t: 1 oz drop -- 2 In. pipe
-- 1.3 lb press. -- 100 ft equivalent length:
1000 0,316
160 1650.7
130.5 X 3.710 X 0.201 X 1 - 97.2 lb per hour. 97.2 X 4b -- 388.8 sq ft equivalent radiation.
1200 0.289
320 480
2334.5 2859.1
Table 2.does not allow for entrained water in low-pressure smteearmda, lcpoinpdeeanssafotiuonndinincporvaecrteicde.pipe and roughness in com-
1500
2000
0.258 0.224
bfedEPer square inch gage *= 2.04 in. Vacuum, Mercury Column. ne factor 4 is (he approximate equivalent in square feet of steam radiation of 1 lb of steam per hour.