F ig . 3. V o l u m e . o f Air t h r o u g h O r if ic e s u n d e r V a c u u m
%
Chapter XVIII--Pumps and Traps for Heating and Ventilating Equipment
The increase in pump capacity may be reduced if a static head above the pump suction is provided. When this static head is made equivalent to the absolute boiling pressure of the condensate (measured in feet of water) minus 12 ft., no increase in pump capacity is required. Such static
Table 6. Correction Factors for Standard Centrifugal Pumps for Tempera tures of Condensate above 180 Deg. Fahr. at Pump Suction
Deo. Fabr.
190
200
204
Factor
1.15 1.56
2.00
Note.--To use Table 6, multiply the quantity of condensate to be handled by the factor corresponding to the temperature of the condensate at the pump suction and select a pump suitable for the quantity thus found.
suction head requirements may also be reduced about 50 per cent when special large suction inlets or special impellers are provided.
Sufficient head in addition to the total head necessary to overcome static head, velocity head, pipe friction and- boiler pressure should be provided wherever condensate is to be returned direct to a boiler from the pump.
Table 7. Duplex Piston Type Return Pumps with Receivers Standard Pressure
Size of Pinup
3 X 2 X 3H 4MX2MX4 5MX3HX5 6X4X6 7KX5X6
Receiver Capacity
Gallons
12 20 40 . 60 100
Sq. Ft. Direct
Radiation
6000 10,500 19,500 30,000 45,000
Lb. Condensate
per Hour
2000 3500 6500 11,000 15,000
Minimum
Steam Pressure
50 40 35. 35 30
i}i X 2 X 4 5K X 2K X 5 6 X 2J4 X 6
6X3X6 6X3KX6
Low Pressure
12 6000 20 . 10,000. 40 120,000 40 180,000 60 290,000
2000 3500 4000
6000 9000
25
20 15 20
25
Table 8. Centrifugal Return Pumps with Receivers
Size of Pump Discharge
Inches
i
iH 2
Receiver Capacity Gallons
40 60 100
.Sq. Ft. Direct. Radiation
12,000 25,500 42,000
Lb. Condensate
per Hour
4000 8500 .14,000 ,
H. P. to
Drive
i
m 2
293
Total Head
Ft.
25 50 50