Document mpG07Ror0rxe9xXQxZmpwzBaB

BFGoodrich The BFGoodrich Company Chemical Group 6100 Oak Troe Boulevard Cleveland. Ohio 44131 216 447-6256 April 22, 1981 Mr. Herb Olson P.0. Box 341 Baton Rouge, LA 70821 Dear Herb: At our 1980 Vinyl Chloride Safety Association Meeting, I presented a paper comparing the "PVC relief area size" from a survey of the member ship. Since the meeting, more data has been received (especially from the foreign producers). The attached table includes the new information. Please note this information is based on the total area available for relief. It does not make any correction for the reduction of area when a relief valve is included. I did not receive enough information from the members to make a comparison including the relief valves. I will look forward to seeing you at our 1981 meeting in Hilton Head. Sincerely, BFGoodrich Chemical Group GDS/glg Attachments OCC 3979 * i--1 i--1 o c c 3980 Canpany and Location 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. POLY SIZE GAL 1,100 2,500 3,300 4,300 16,500 2,000 4,000 4,000 6,000 2,400 3,500 4,000 6,000 24,000 24,000 20,000 35,000 PVC POLY SIZE RELIEF AREA COMPARISION RATING PSIG RELIEF NOZZLE SIZE NUMBER 200 200-400 250 300 240-300 180 180 200 200 200 185-200 200 220 200 180 2" 4" 4" 4" 10" 3" 3" 4" 4" 4" 4" 4" 418" 16" 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 260 16" 172 8" 1 2 TOTAL AREA AVAILABLE 3.14 12.56 12.56 12.56 78.5 7.07 7.07 12.56 12.56 12.56 12.56 12.56 12.56 254.34 200.96 200.96 100.48 RELIEF AREA PER 1000 GAL 2.85 5.02 3.81 2.9 4.75 3.53 1.77 3.64 2.09 5.2 3.5 3.14 2.09 10.59 8.37 10.05 2.87 OCC 3981 FVC POLY SIZE RELIEF AREA OCMPARISION Canpany and Location POLY SIZE GAL EATING PSIG RELIEF NOZZLE SIZE NUMBER 12. 35,000 185 8" 2 6" 2 13. 2,200 200 4" 1 5,000 225 6" 1 7,000 200 6" 1 20,000 225 8" 2 14. 3,500 300 6" 1 7,400 250 6" 1 15. 4,200 200 4" 1 5,700 200 4" 1 4,500 200 3" 1 16. 52,800 260 10.0" 3 10,500 2609 10.0" 1 17. 8,000 128 3" 2 18. 4,000 240 3" 2 19. 20,000 220 6" 2 8" 1 3,700 2,200 2,200 220 200 200 6" 3" 3" 1 1 2 20. 16,500 300 12" 1 6,600 350 4" 3 4,200 350 3" 3 21. 20,500 270 8" 1 Note: Total relief area is based on full nozzle size for comparison and does not include the reduction of area if a relief valve is used. 2376E/wp/2 TOTAL AREA AVAILABLE 157 12.56 28.26 28.26 100.48 28.26 28.26 12.56 12.56 7.07 235.62 78.54 14.14 14.14 56.55 50.27 107.12 28.27 7.07 14.14 113.09 37.7 21.21 50.26 RELIEF AREA PER 1000 GAL 4.49 5.71 5.65 4.04 5.02 4.07 3.82 2.99 2.20 1.57 4.44 7.5 1.77 3.54 5.36 7.64 3.21 6.43 6.85 5.71 5.05 2.45 Tenneco Chemicals A Tenneco Company P.O. Box 849 Pasadena. Texas 77501 (713)479-3411 July 31, 1981 Mr. Herb Olson Ethyl Corporation P. 0. Box 341 Baton Rouge, La. 70821 Dear Herb, The program Agenda for the 1981 Vinyl Chloride Safety Association Meeting is enclosed. It is my understanding that you will mail this to all permanent members. In your cover letter, would you please mention a pre-registration time available on the evening before the meeting from 6 to 7 PM, September 23, 1981. Please let me know if you have any questions about the Agenda. Sincerely, Tom Moore TIM: ml cc: Glen Schaaf B. F. Goodrich Co. 6100 Oak Tree Boulevard Cleveland, Ohio 44131 OCC 3982 VINYL CHLORIDE SAFETY ASSOCIATION MEETING SEPTEMBER 24 AND 25, 1981 HILTON HEAD, SOUTH CAROLINA SEPTEMBER 24 8:00 - 8:30 8:30 - 9:00 AGENDA Registration and Coffee Social Chairman's Welcome and Business Agenda VCSA History/Status Review Preview Business Agenda Program Preview 9:00 - 9:15 9:15 - 9:30 9:30 - 9:45 9:45 - 10:00 10:00 - 10:15 10:15 - 10:30 10:30 - 11:00 11:00 - 12:00 12:00 - 1:45 2:00 - 2:30 2:30 - 2:45 I. True Confessions/Major Incidents Furan Process Sewer Explosion Control Room/Laboratory Explosion Nitrogen Inhalation Incident VCM Column Explosion Coffee Break Reactor Lockout Device Report Polypropylene Plant Fire Small Reactor Safety Survey Report Lunch Lunch Speaker: Gary Baise Law Firm of Beveridge & Diamond SUBJECT: VCM Regulatory Status II. OSHA/EPA Topics Regulatory Update Regulatory Incidents Hazardous Materials Notification 2:45 - 3:00 OSHA Inspection - Respiratory Protection 3:00- 3:15 Coffee Break Glen Schaaf B. F. Goodrich. Doug Frey Diamond Shamrock Tom Moore Tenneco Herm Waltemate B.F. Goodrich Darwin Rhoads Tenneco Jerry Brumbaugh General Tire John Barr Air Products Harold Dubec Hooker Dave Lull Diamond Shamrock OCC 3983 SEPTEMBER 2 A 3:15 - A: 00 III. Operator Training Operator Training Survey Report A:00 - A: 30 A:30 - 5:00 Implementing an Effective Plant Safety Program Video Tape Demonstration OSHA VCM Standard SEPTEMBER 25 8:30 - 9:00 9:00 - 9:30 Business Meeting Election of Officers/1982 Meeting Location IV. Safety Systems Reports Computer Safety Survey Report 9:30 - 10:00 VCM Safety Condensation System 10:00 - 10:15 10:15 - 10: A5 Break Compound Ignition Hazards 10:A5 - 11:15 VCM Tank Car Wreck 11:15 - 12:00 Wrap Up/Survey Questionnaire Completion Doug Frey Diamond Shamrock Stephen Brouillard Diamond Shamrock John Barr Air Products Glen Schaaf/ Doug Frey Jim Gabbett Georgia Pacific B, Terwiesch Chemische Werke Huls John McCully Conoco Everson Weekly Pantasote Tom Moore Tenneco OCC 3984