Document mmzwL4RarpoR5D7VbyLNMxQ4Q

OWENS/CORNING FlBERGLAS TDAIIFlCAflK PLAINTIFF'S EXHIBIT K-9 1 5 Mechanical insulation systems INSULATION selection guide PLUMBING PIPING & EQUIPMENT SYSTEMS system temp, range products PIPING Chilled Drinking Water Rainwater Leaders Drain Lines (Bent Soft Copper Connections) 35-50F 35-50F PIPE INSULATIONS Heavy Density One-Piece Fiberglas 25 C-P O-C Flexible Tubing page 4-9 10-14 15-17 36-37 Domestic Cold Water Boiler Makeup Water Domestic Hot Water Tempered Water Booster Heater Water 50-60F to 180F EQUIPMENT Hot Water Storage Tanks Heat Exchangers Hot Water Generators Booster Heaters 150-180F Heavy Density One-Piece Fiberglas 25 C-P 4-9 10-14 15-17 Heavy Density One-Piece Fiberglas 25 H-P EQUIPMENT INSULATIONS 700 Series Kaylo Block Fiberglas 25 H-E . 4-9 f flO-14 w "l8-20 27-29 34-35 25-26 Products shown in BOLD FACE type are recommended for use for the services shown based on performance and widespread acceptance. Other products are listed be cause of local conditions or produet preference. 2 MECHANICAL PIPING SYSTEMS system temp, range products page PIPING Refrigerent Suction Chilled Water (Primary and Secondary) Cooling Tower Water (IPS) Refrigerent Suction Chilled Water (Bent Soft Copper Connections) PIPE INSULATIONS -20 to 35F Heavy Density One-Piece Fiberglas 25 C-P 0 to 70F O-C Flexible Tubing 4-9 10-14 15-17 36-37 Dual--Temperature Make-Up Water Heating Hot Water Fuel Oil Piping High Temperature Hot Water Steam and Condensate 35 to 60F to1200F Heavy Density One-Piece Fiberglas 25 C-P Heavy Density (to 450F) One-Piece (to 400F) Kaylo (to 1200 F) Fiberglas 25 H-P (to 450F) 4-9 10-14 15-17 4-9 10-14 21-22 18-20 MECHANICAL EQUIPMENT temperature products Cold Equipment - 20F to 70F Hot Equipment 70F to 1200F Type 705 Fiberglas 25 C-E Type 704 (to 450F) Fiberglas 25 H-E (to 450F) l-S Board (to 850F) Thermal Insulating Wool (TIW) (to 1000F) Kaylo Block (to 1200F) page 27-29 23-24 27-29 25-26 30-31 32-33 34-35 3 Heavy Density Sectional Pipe Insulation A multi-purpose rigid pipe insulation for all types of piping systems operating at temperatures from -120 F to 450 F uses Fiberglas*Heavy Density Sectional Pipe Insulation has a broad range of uses for hot and cold piping. It is available with a variety of factory-applied jackets to provide for appearance, vapor barrier, fire safety or weatherproofing to permit selection of the correct in sulation for the service requirements from --120F to 450F. See page 2 for a complete selection guide. description Fiberglas Heavy Density Sectional Pipe Insulation is a precision molded pipe covering composed of Fiberglas wool resin-bonded and formed in two half cylinders up to 12" IPS. It is available in 3 ft. long sections to fit all sizes of pipe and tubing from y2" IPS to 33". benefits superior thermal efficiency --Fiberglas Sec tional. Pipe Insulation because of its low k factor provides high efficiency with resultant cost sav ings. The closely knit glass fibers form millions of air pockets to retard the flow of heat for great er fuel savings and more precise temperature control. resists compression --Heavy Density Fiberglas Pipe Insulation resists compression and mech anical damage because it is denser than other glass fiber pipe insulations. This means less chance of unsightly damage and puncture of the vapor barrier on cold lines. dimensionally stable--Fiberglas will not shrink or rot and will withstand thermal shock. easy to fabricate --Fiberglas Heavy Density Pipe Insulation is easy to cut and fit in the field with "Trademark Registered Owens-Corning Fiberglas Corporation an ordinary knife. No special tools are required and the firm clean-cut sections knit tightly to. gether forming an efficient thermal barrier at fittings and joints. The rigid, sectional form lends itself to accurate shop fabrication of valve and fitting covers. inorganic--The special compounded glass fibers are completely inert. They will not corrode steel, copper or aluminum pipe and will not cause stress corrosion in stainless steel. factory applied jackets--A wide variety of fac tory-applied jackets are available to provide va por barrier protection, weather resistance, fire safety or damage resistance. These jackets speed application in the field. The Self-Seal ing Lap jacket further simplifies installation and assures a moisture vapor barrier seal at the joints. 4 Performance characteristics moisture absorption: 0.2% by volume--96 hrs. at 120F and 95% RH capillarity: negligible (after 24 hours) alkalinity: ph 9 specific heat: 0.20 Btu/lb.F stress corrosion: will not cause stress corrosion, cracking of stainless steel thermal conductivity: Fire Retardant Jacket, left. Fiberglas 25 Concealed with Self Sealing Lap and end ioint sealing strip, right. mean temperature 75F 40F k 0.240 0.227 specification compliance: HH-I-558a Insulation. Blocks, Boards, Blankets, Felts, Sleeving (Pipe and Tube Covering) and Pipe Fitting Covering, Thermal (Mineral Fiber, Industrial Type), Farm O, Type III, Cleis 12. ASTM Specification C547-67 Standard Canvas Jacket, left. Pre-Sized Glass Cloth Cloth with end ioint closure strip, right. Glass Klad Metal Jacket, left to right: .016 Embossed Aluminum with snap-in locking joint; .010 Stainless Steel with snap-in locking joint; .010 Embossed Aluminum with overlapping jacket laps on end and longitudinal joints; End joint sealing butt strips for end joint closure. NEATER JOBS are possible with Fiberglas Heavy Density Pipe Insulation because of its inherent rigidity. It cuts cleaner with square neat edges. ABUSE RESISTANT--Heavier density means less chance of damage from ladders or other mechanical abuse during installation or in service. 5 PIPE INSULATION SELECTION CHART-PLUMBING & MECHANICAL SYSTEMS SERVICE REQUIREMENT HOT PIPING Plumbing Domestic Hot Water Tempered Water TEMPERATURE F JACKETS AVAILABLE (RECOMMENDED IN BOLD FACE TYPE) CONCEALED EXPOSED 110-180 110-130 Fiberglas 25 Concealed Jacket-completely lire safe FRJ jacket with Self Sealing Lap. End joint butt strips furnished. Standard Canvas Jacket-low cost--provides base for painting. Heavier 6 or 8 oz. weights available. Fiberglas 25 H-P- pre-sized surface ellml nates field priming. May be left as is or painted any color. Fiberglas 25 Concealed Jacket--completely fire safe FRJ jacket with Self Sealing Lap. End joint butt strips furnished. Mechanical Heating Hot Water Steam and Condensate Fuel Oil Piping High Temperature Hot Water COLD PIPING Plumbing Domestic Cold Water Chilled Drinking Water Rain Water Leaders Mechanical Chilled Water--Primary and Secondary Dual-Temp Refrigerant Suction 150-210 210-450 210-450 250-450 Canvas; 6 oz. or 8 oz.--normally sized and painted. FRJ with Self Sealing Lap--FRJ (Fire Re tardant Jacket) is a laminate of white kraft and foil, reinforced with strong glass yarns, laminated with flame snuffing adhesive. Meets requirements of GSA 301-1, Type A. Jacket can be used on heated, and dual-tem perature lines up to 450F. Butt joint strips to close end joints are furnished. Also avail able without the Self Sealing Lap feature. FRJ with Self Sealing Lap--no further finish required. Neat, white attractive finish. Or, may be painted with water based paint.'" *May be finished with field applied 6 oz. canvas, sizing & paint. 50-65 35-65 33-65 Fiberglas 25 Concealed Jacket-completely fire safe FRJ jacket with Self Sealing Lap. End joint butt strips furnished. Fiberglas 25 C-P--a completely U.L. rated cold pipe insulation system. U.L. rating includes jacket, insulation; fittings and ac cessories. 35-55 40-210 -60 to +35 FRJ with Self Sealing Lap--provides a posi tive vapor seal for all cold and chilled water lines. FRJ (Fire Retardant Jacket) is a lami nate of white kraft and foil reinforced with strong glass yarns. Meets requirements of GSA 301-1, Type A jackets. Laminated with flame snuffing adhesive. Excellent vapor barrier with low perm rating 0.02. Jacket can be used on heated, dual-temperature and refrigerant lines from --120F to 450F. Butt joint strips to close end joints are furnished. Also available without the Self Sealing Lap feature.* FRJ with Self Sealing Lap--no further finish required. White appearance presents neat finished job." *May be finished with field applied 6 oz. canvas, sizing & paint. FRJ WITH SELF-SEALING LAP--installed by this unique method eliminates the need for stapling, bands and lap adhesives. The contact type adhesive offers a positive vapor seal at all joints and speeds application. It's as easy as 1, 2, 3:(1) start to peel the release paper off the vapor barrier, (2) apply to pipe and peel off the balance, (3) press OUTDOORS Glai Klad--factory applied .016 embossed alumi num or .010 stainless steel. Complete with Integral longitudinal Pittsburgh seam and butt joint strips that lock out the weather. Butt joint strips are furnished, with weatherproof mastie protected with release paper. Also available with .010 embossed aluminum without Pittsburgh seam, having a twoinch overlap at the longitudinal seam and a 2" overlap on end joint. Glas Klad--factory applied .016 embossed alumi num or .010 stainless steel. Complete with integral longitudinal Pittsburgh seam and butt joint strips that lock out the weathar. Butt joint strips are fur nished with weatherproof mastie protected with release paper. Also available with .010 embossed aluminum without Pittsburgh seam, having a two-inch overlap at the longitudinal seam and a 2" overlap on end joint. Note: All cold lines running outdoors require a weather proofing jacket, in addition to the factory applied vapor barrier. DESIGN CONSIDERATIONS The wide temperature range of Fiberglas Heavy Density Pipe Insulation permits the specifier to select material from one manufacturer to answer all the mechanical and plumbing system insulation requirements, concealed, exposed, outdoors, hot or cold. A selection of jackets matched to end use and factory applied to the insulation assures maximum performance at the most economical cost. Self Sealing Lap on FRJ (Fire Retardant Jacket) assures a positive vapor seal and serves to hold the insulation on the pipe. This technological advance employs a unique chemical bonding agent that instantly seals and holds the joint lap tightly in place. The bond also becomes stronger with age. Butt joint strips of the same material are used on the end joints. The use of staples, bands and messy adhesives are eliminated and the attendant problems of fishmouths and other application defects. In addition FRJ with Self Sealing Lap is fire retardant, presents a neat white appearance and is glass fiber reinforced to resist damage. Fiberglas 25 Jacket factory-applied to Fiberglas Heavy Density Pipe Insulation is a completely fire-safe insulation for hot or cold lines. No lagging is required before painting. The jacket is tough, resists damage and will not mildew or rot. Available in C-P or H-P for exposed applications and Fiberglas 25 Concealed for concealed systems. Fittings for cold lines are insulated with mitered segments, or pre-molded Fiberglas fittings which is subsequently wrapped with glass fabric and coated with vapor barrier mastic. For hot lines the fitting is made smooth with insu lating cement, canvased and sized. Fiberglas will not burn, rot or shrink. With the addition of FRJ or Fiberglas 25 Jacket, the insulation is completely fire-safe. The exceptional low k factor means maximum economy and performance for all piping systems, concealed, ex posed or outdoors. Caution: Owens-Corning Fiberglas Insulations are to be applied only with approved adhesives, mbstics and mechanical fastening devices as published in Accessory Materials List, Pub. No. 4-IN-3430. Owens-Corning Fiberglas accepts no responsibility or liability for the performance of materials other than those listed in this list unless approved in writing by O-CF Testing Laboratories. 1' the lap in place at the center and, pressing hard, work out toward either end. Rub with the blunt edge of a knife. End joints are sealed with a 3* wide butt strip of the same Self-Sealing vapor barrier material. This feature also available on Fiberglas 25 C-P and Fiberglas 25 Concealed. 1 recommended thickness Selection of insulation thicknesses for any spe cific application should take into consideration the following important criteria. 1. Cost of in sulation applied. 2. Cost of heat energy. 3. Cost of capital. 4. Cost of depreciation-plant and in sulation. 5. Capital investment in heat produc tion equipment. 6. Temperature differential. 7. Size of the pipe or surface. 8. Conductivity of insulation. cold piping--Proper thickness (see overleaf for tables) is required for efficient operation and to prevent condensation on the insulation sur face. Specifically: 1. Designed thickness should be specified to result in a surface temperature above the Dew-Point temperature of the surround ing air. Generally this is equal to or greater than the "economical thickness" despite the relatively higher cost of cold Btu's. 2. Insulation thickness should be based on ambient air conditions and corresponding permissible temperature differences. Ambient Air Condition Permissible temp, drop (between ambient air and insulation surface) 90 Fat 90% R.H. 90 Fat 80% R.H. 3F 7F 3. Piping operating down to freezing tem peratures or at fluctuating hot and cold temperatures should be insulated for max imum performance during the coolest part of the cold cycle. recommened thickness heated piping to 450F (80F ambient air) Pipe Temp. 200 300 400 450 Temp. Dirf. 120 220 320 370 IPS RT HL ST RT HL ST RT HL ST RT HL ST % 1 13 91 1 24 101 iy2 32 100 iy2 39 105 % 1 15 94 1 29 106 iy2 42 104 1V2 45 120 1 1 16 92 1 30 102 iy2 42 104 iy2 49 108 1V4 1 20 95 1V2 27 95 1V2 45 104 2 51 104 1V2 1 21 93 IV2 31 96 IV2 50 107 2 57 107 2 1. 24 94 1 y2 36 97 IV2 58 107 2 60 103 2 y2 1 xh 24 91 2 36 95 2 60 104 2 72 108 3 IV2 25 90 2 39 94 2y2 56 97 2y2 69 98 3i/2 iy2 31 92 2 47 96 2y2 58 96 2y2 71 99 4 iy2 30 90 2 47 94 2y2 64 97 2y2 80 100 4>/2 iy2 34 92 2 58 97 2y2 58 96 2y2 84 102 5 iy2 38 91 2 58 95 2y2 80 100 3 70 98 6 iy2 29 88 2 56 94 2y2 95 101 3 95 99 7 iy2 44 91 2s 74 95 2yz 100 98 3 100 99 8 iy2 50 93 2 76 95 2y2 104 100 3 112 99 9 iy2 58 91 2 80 96 2y2 118 99 3 114 100 10 2 48 88 2y2 76 93 3 111 97 3 135 101 12 2 56 89 2y2 88 93 3 127 98 3y2 138 98 14 2 63 89 2y2 99 94 3 142 98 3 k 153 99 HL--heat loss ... Btu/hr/lineal foot ST--surface temperature (F) RT--recommended thickness HG-- heat gain 8 recommended thickness cold piping & dual-temperature (minus 60 to 200F) oof ambient air) pipe surface temperature .... pipe sizes K y 1 i'/ IK 2 2K 3 4 S 6 7 8 "9 - 10 11 12 14 16 18 20 24 30 33 copper tubing Vi H y. Vk IV4 *k m 3K 3% *% 5 Vi 6 90% relative humidity 40 F 35 F 0 F --30 F chilled water Ice wa er RT* HO RT* HO i'/i 3.8 IK 5 IK 4.3 IK 5 IK 4.7 IK 6 IK 5.3 2 6 IK 6.0 2 IK 5.8 2 7 7 2 7.2 2 8 2 7.5 2 9 2 9.1 2 10 2 10.6 2K 11 2 12.4 2K 12 2 13.8 2K 14 2 15 2 ~ 16 2K 15 2K 16 2 17 2K 16 2K 17 2K 19 2K 17 2K 19 2K 21 2K 23 2K 21 2K 24 2K 25 2K 28 2K 26 2K 30 2K 31 3 32 2K 37 2K 40 3 3 32 45 IK 3.5 IK 3.8 IK 3.2 IK 3.5 IK 3.5 IK 3.8 IK 3.9 IK 4.2 IK 4.5 IK 5.0 IK 4.9 IK 5.4 IK 5.6 IK 6.1 IK 6.0 2 5.8 2 6.3 2 6.8 2 6.6 2 7.6 2 7.8 2 8.5 2 7.9 2K 8.6 2 9.2 2K 9.6 2 12.7 2K 11.3 RT 2K 2K 2K 2K 3 3 3 3 3 3K 3K 3K 3K 4 4 4 4 4 4 4 4 4K 4K 4K special bri ne HO RT HG 63 63 7 7 63 73 8 9 8 3K 8 3K 8 10 10 3K 10 4 11 11 12 4 13 4 13 15 14 4K 15 4K 16 17 17 4K 17 4K 18 20 18 4K 22 20 4K 23 21 5 23 5 24 28 25 5 29 5 28 31 31 5 33 33 5K 37 40 5K 43 47 5K 51 --60 F refrigera its RT HG 3'/l 7 3K 8 3K 9 3K ! 1 3K 10 4 11 4 12 4K 13 4K 15 41/, 17 5 18 5 19 5 21 5K 22 5/, 24 5K 25 5K 26 6 27 6 29 6 32 6 35 6 41 4K 48 6K 54 80% relative humidity 40 F 35 F 0 F --30 F chiliad waiter RT HO V, 5.4 y* 6.2 V* 7.1 M 8.4 % 9.4 a 11.0 a 12.6 1 12 1 14 1 18 1 21 1 24 1 25 1 27 1 32 1 32 1 34 1 41 1 44 1 52 1 57 1 70 1 82 1 91 a 4.0 % 4.4 % 4.8 a 5.2 % 6.3 % 7.2 % 8.0 % 9.6 % 11.5 y. 13.3 1 12.8 1 11.7 1 13.9 1 i 16.1 ice waifar RT HO *6 n7 y. 6 19 19 1 10 1 12 1 14 1 16 1 20 1 24 1 28 1 29 IK 24 IK 26 IK 29 IK 32 IK 35 IK 39 IK 43 IK 48 IK 55 IK 70 l'K 77 % 4.3 a 4.9 % 5.3 % 5.8 % 6.9 a 7.8 % 8.8 1 0.0 1 11.1 1 10.6 1 14.0 1 10.9 1 15.2 1 17.6 RT 1 IK IK IK IK l'K IK IK IK IK 2 2 2 2 2 2 2 2 2 2 2 2 2 2 spacial briile HO RT HG 8 IK 9 8 IK 10 8 IK n 9 IK 12 10 2 12 2 12 13 15 2 16 2 16 17 18 2 23 2 20 24 21 2 23 2 27 30 26 2 27 2 33 35 30 2 31 2 39 41 36 2K 39 41 2K 44 45 2K 49 50 2K 54 55 2K 60 64 2K 70 79 2K 83 88 2K 92 --60 F refrfgerants RT HO IK 11 2 10 2 11 2 14 2 15 2 16 2K 17 2K 18 2K 21 2K 25 2K 28 2K 31 2K- 34 2K 37 2K 41 3 38 3 41 3 46 3 50 3 56 3 62 3 73 3 88 3 98 ^Minimum thickness available above 12" IPS is 1 ", above 24" IPS is 1 Mi". 9 One-Piece Pipe Insulations A versatile, efficient quick applying insulation for hot and cold piping from-- 30F to 450 F. uses Fiberglas One-Piece Pipe Insulation is adaptable to all types of piping systems operating at temperatures from --30F to 450F. It is available with a variety of factory-applied jackets for appearance, vapor barrier, fireproofing or waterproofing to permit selection of the right combination^ of insulation and jacket for the service condition requirement. description Fiberglas One-Piece Pipe Insulation is a resilient light weight pipe insulation molded from fine glass fibers in cylindrical form. A single longitudinal seam, which is opened to apply to the pipe, springs closed when in place. It is available with a variety of factory-applied jackets for appearance and function. benefits economical application--One-piece unit is applied quickly, easily, even in the larger sizes, easy fabrication--Only a knife is needed for fabrication of the'most intricate fittings. efficient--Because of its very low k factor, it is possible to reduce the thickness of insulation to provide thermal efficiency equivalent to other non-fibrous materials with savings in material costs. Conversely, the same thickness of Onepiece provides better thermal efficiency, which results in savings in operating expense due to reduction in heat loss. permanent -- Completely U.L. rated -- Inorganic Trademark Registered Owens-Coming Fiberglas Corporation glass fiber construction will not shrink, rot or cause metal corrosion. multi-purpose--The variety of applications means less inventory. A selection of factoryapplied jackets are available for surface finish, vapor barrier, weather protection, fire proofing or damage resistance. The Self-Sealing lap jacket speeds application in the field and assures a positive vapor barrier. damage resistant--The resilient glass fibers spring back when bumped, and One-Piece will not break if accidentally dropped during installation. 10 Performance characteristics moisture absorption: 0.2% by volume 96 hrs. at 120 F and 95% RH specific heat: 0.20 Btu/lb. F. shrinkage: None alkalinity: ph9 thermal conductivity: Unusually low thermal conductivity shown on chart 1. Standard Canvas. 130 noon mean temperature 75F 40F k 0.23 0.21 specification compliance: HH-l-558a Form D, Type III, Class 12 HH-l-562 Type II MIL-I-22344B (Ships) 2. FRJ. 3. FRJ with Self-Sealing Lap. 4. Fiberglas 25 Concealed Neat Finished Appearance on this well Insulated chilled water system is one of the reasons why One-Piece Pipe Insulation is used widely in equipment rooms. 11 Self Sealing Lag vapor barrier jacket combines a positive vapor seal, with an attractive fire safe finished appearance for cold water service and dual-temperature tines. PIPE INSULATION SELECTION CHART-PLUMBING & MECHANICAL SYSTEMS SERVICE REQUIREMENT HOT PIPING Plumbing Domestic Hot Water Tempered Water Mechanical Heating Hot Water Steam and Condensate Fuel Oil Piping High Temperature Hot Water COLD PIPING Plumbing Domestic Cold Water Chilled Drinking Water Rain Water Leaders Mechanical Chilled Water--Primary and Secondary Dual-Temp Refrigerant Suction TEMPERATURE F JACKETS AVAILABLE (RECOMMENDED IN BOLD FACE TYPE) CONCEALED EXPOSED 110-180 110-130 150-210 210-450 210-450 250-450 Fiberglas 25 Concealed Jacket--completely fire safe FRJ jacket with Self Sealing Lap. End joint butt strips furnished. Standard Canvas Jacket--low cost--provides base for painting. Heavier 6 or 8 oz. weights available. FRJ with Self Sealing Lap--FRJ (Fire Re tardant Jacket) is a laminate of white kraft and foil, reinforced with strong glass yarns, laminated with flame snuffing adhesive. Meets requirements of GSA 301-1, Type A. Jacket can be used on heated, and dual-tem perature lines up to 450F. Butt joint strips to close end joints are furnished. Also avail able without the Self Sealing Lap feature. Fiberglas 25 H-P--a completely U.L. rated hot pipe insulation system. U.L. rating in cludes jacket, insulation, fittings and ac cessories. Available on Fiberglas Heavy Density Pipe Insulation only. See data sheet 1-IN-3853. Fiberglas 25 Concealed Jacket--completely fire safe FRJ jacket with Self Sealing Lap. End joint butt strips furnished. 50-65 35-65 33-65 35-55 40-210 -30 to --35 Fiberglas 25 Concealed Jacket--completely fire safe FRJ jacket with Self Sealing Lap. End joint butt strips furnished. FRJ with Self Sealing Lap--provides a posi tive vapor seal for all cold and chilled water lines. FRJ (Fire Retardant Jacket) is a lami nate of white kraft and foil reinforced with strong glass yarns. Meets requirements of GSA 301-1, Type A jackets. Laminated with flame snuffing adhesive. Excellent vapor barrier with low perm rating 0.02. Jacket can be used on heated, dual-temperature and refrigerant lines from --30F to 450F. Butt joint strips to close end joints are furnished. Also available without the Seif Sealing Lap feature. Fiberglas 25 C-P--a completely U'.L. rated cold pipe insulation system. U.L. rating in cludes jacket, insulation, fittings and ac cessories. Available in Fiberglas Heavy Density Pipe Insulation only. See data sheet 1-IN-4376. FRJ WITH SELF-SEALING LAP--installed by this unique method eliminates the need for stapling, bands and lap adhesives. The contact type adhesive offers a positive vapor seal at all joints and speeds application. It's as easy asl, 2, 3: (1) start to peel the release paper off the vapor barrier, (2) apply to pipe and peel off the balance, (3) press the lap in 12 OUTDOORS A suitable weatherproof jacket applied over no wrap or factory jacket. DESIGN CONSIDERATIONS The wide temperature range of Fiberglas One-Piece Pipe Insulation permits the specifier to select material from one manufacturer to answer all the mechanical and plumbing system insulation requirements, concealed, exposed, outdoors, hot or cold. A selection of jackets matched to end use and factory applied to the insulation assures maximum performance at the most economical cost. Self Sealing Lap on FRJ (Fire Retardant Jacket) assures a positive vapor seal and serves to hold the insulation on the pipe. This technological advance employs a unique chemical bonding agent that instantly seals and holds the joint lap tightly in place. The bond also becomes stronger with age. Butt joint strips of the same material are used on the end joints. The use of staples, bands and messy adhesives are eliminated and the attendant problems of fishmouths and other application defects. In addition FRJ with Self Sealing Lap is fire retardant; presents a neat white appearance and is glass fiber reinforced to resist damage. Fiberglas 25 Jacket factory-applied to Fiberglas Heavy Density Pipe Insulation is a completely fire-safe insulation for hot or cold lines. No lagging is required before painting. The jacket is tough, resists damage and will not mildew or rot. Available in C-P or H-P for exposed applications and Fiberglas 25 Concealed for concealed systems. Fittings for cold lines are insulated with mitered segments, or pre-molded Fiberglas fittings which is subsequently wrapped with glass fabric and coated with vapor barrier mastic. For hot lines the fitting is made smooth with insu lating cement, canvased and sized. Fiberglas will not burn, rot or shrink. With the addition of FRJ or Fiberglas 25 Jacket, the insulation is completely fire-safe. The exceptional low k factor means maximum economy and performance for all piping systems, concealed, ex posed or outdoors. Caution: Owens-Corning Fiberglas Insulations are to be applied only with approved adhesives, mastics and mechanical fastening devices as published in Accessory Materials List, Pub. No. 4-IN-3430. Owens-Corning Fiberglas accepts no responsibility or liability for the performance of materials other than those listed in this list unless approved m writing by O-CF Testing Laboratories. edge of a knife. End joints are sealed with a 3" wide butt strip of the same Self-Sealing vapor barrier material. 13 economic thickness heated piping to 450F (80F ambient still air) pipe temp, temp. diff. IPS 200 120 ET HL ST 300 220 ET HL ST 400 320 ET HL ST y2 1 13 91 54 1 15 94 i 1 16 92 1V4 1 20 95 l'/z 1 21 93 2 1 24 94 2 Vi 3 3 Vi 4 4Vi 5 6 7" 8 9 10 12 14 lVi l`/2 1 Vi iy2 i`/2 v/2 iy2 -iy2 iy2 iy2 2 2 2 24 25 31 30 34 38 29 - 44 50 58 48 56 63 91 90 92 90 92 91 88 91 93 91 88 89 89 ET-economic thickness (inches) 1 24 101 iy2 32 100 1 29 106 iy2 42 104 1 30 102 iy2 42 104 iy2 27 95 iy2 45 104 i`/2 31 96 i`/2 50 107 ii/2 36 97 iy2 58 107 2 36 95 2 60 104 2 39 94 Specify Fiberglas Heavy 2 47 96 for thickness above 2". 2 47 94 2 58 97 2 58 95 2 56 94 2 74 95 2 76 95 2 80 96 HL-heat loss ... BTU/hr/lineal foot ST-surface temperature (F) cold and duai-temperature lines(90 Fat80% R.H.) pipe surface temperature 50 F or above 49 F to 35 F pipe size RT HG RT HG y2 y2 4 3/4 5 34 y2 5 34 6 i y2 6 34 7 1`4 Vi 7 34 8 l`/2 Vi 8 3/4 9 2 Vi 10 34 11 2y2 Vi 12 34 13 3 11 -34 15 3*4 3/4 12 1 12 4 3/4 13 1 14 4V4 3/4 14 1 15 5 3/4 15 1 19 6 3/4 17 1 22 7 1 18 1 25 8 1 20 1 27 9 1 22 1 29 10 1 25 ' 1 32 11 1 25 - 1 34 12 1 26 1 35 RT-recommended thickness (inches) 34 F to 0 F RT HG 1 1 iy2 iy2 i`/2 iy2 lVi lVi lVi lVi V/i lVi lVi lVi VA V/i V/z V/i V/z 8 9 8 9 10 12 15 16 18 18 22 23 25 28 31 34 36 39 43 HG-heat gain 0F to -30 F RT HG iy2 V/i V/z V/i iy2 iy2 2 2 2 2 2 2 2 2 2 2 2 2 2 8 10 11 12 13 15 15 17 19 20 23 23 26 29 32 35 38 41 44 14 Fiberglas 25 C-P Pipe Insulation System A U.L. rated noncombustible pipe insulation system for cold service piping operating at temperatures down to 35 F. uses Recommend for use on all cold or dual-service piping operating from 35F. to 450F. where rated non combustible fire safety is desired--such as, commer cial and institutional buildings, schools, hospitals, and places of public assembly. Also recommended for proc essing lines where fire safety is a paramount criterion. Fiberglas 25*C-P Pipe Insulation System is composed description of Fiberglas Heavy Density Sectional Pipe Insulation jacketed with a vapor barrier laminate of aluminum foil and pre-sized glass cloth. The jacket has a pres sure sealing lap adhesive (on sizes up to 12" IPSx2") to eliminate the use of staples, adhesives, or bands. The fittings are also non-combustible. benefits fire safety--a complete insulation system with a UL rating including pipe fittings, vapor barrier and mastic when installed in accordance with recom mended procedures. ready for painting--factory pre-sized glass cloth jacket and matching tape and mastic system do not require field sizing. If desired, painting may be omitted. If painting is required see "Applica tion recommendations." damage resistant--the extra heavy density pipe insulation and extra tough woven glass cloth jacket resists damage on exposed lines. Fiberglas (Reg. U.S. Pat. Off.) and "25" are trademarks of Owens-Corning Fiberglas Corporation. lower operating cost--the exceptional thermal effi ciency of Fiberglas Heavy Density pipe insulation contributes to lower operating cost of cooling equipment and piping. no condensation drippage--the foil vapor barrier and pressure sensitive lap when applied as per instruction, assure a positive vapor seal. Fittings also provide a vapor seal. installation savings--Fiberglas 25 C-P pipe insula tion system meets all existing standards for fire safety and its uses may result in lower insurance costs. 15 Performance characteristics Insulation moisture absorption: 0.2% by volume 96 hrs. at 120F and 95% RH specific heat: 0.20 Btu/lb. F shrinkage: none alkalinity: ph 9 capillarity: negligible after 24 hrs. dimensional stability -- will not warp, shrink, rot or decompose, vermin and rodent resistant--provides no sustenance. temperature limitation--recommended for chilled or dual-temperature piping from 35F. to 450F. Jacket vapor transmission rate: .05 perms burst strength: 300 psi 0 75 100 200 MEAN TEMP (F) 300 350 fire hazard classification Maximum Fire Hazard Classifications for building materials and insulations as noncombustible have been established as follows: Flame Spread Fuel Contributed Smoke Developed Acceptable 25 50 50 Fiberglas 25 C-P Pipe Insulation Systems, including fit tings, is considerably below the maximum allowable. This is your assurance that you can specify and use Fiberglas 25 C-P Pipe Insulation System without the danger of con tributing to the spread of fire or-that combustion will liber ate excessive smoke.The system has been designed to meet the stringent fire safety requirements of the GSA and Corps of Engineers. Underwriters Laboratories (Pipe & Equipment Coverings R5583 40 U 8.15) Flame Spread Fuel Contributed Smoke Developed ** Fiberglas 25 C-P Pipe Insulation System 20 5 40 **Note. This rating is for the pipe insulation plus an unlimited number of fittings in a piping system if materials and application con form to those recommended. application recommendations The self sealing lap feature on Fiberglas 25 C-P Pipe Insulation sections makes installation on straight runs of pipe a simple procedure. The only precaution needed is to keep all contact adhesive surfaces clean and to rub hard all longitudinal and circumferential seams. The end joints are sealed with a factory furnished joint sealing strip with pressure sealing adhesive. Fittings are fabricated from mitered segments of Fiberglas Heavy Density pipe insulation or commercially available molded insulation fitting covers. Fitting insulation is coated with a skim coat of insulat ing cement to smooth out the insulation. After cement is dry, O-C F Fitting Mastic, Type C, is then applied over Fiberglas Reinforcing Cloth and coated with another coating of O-C F Fitting Mastic, Type C. If painting is required, no sizing is necessary; but, to main tain the noncombustible rating of the system, only Glidden acrylic latex paint (No. 5370) is approved for use. specification compliance HH-l-558a, Form D, Type III, Class 12 Recommended Thickness Selection of insulation thicknesses for any specific application should take into consideration the fol lowing important criteria. 1. Cost of insulation ap plied. 2. Cost of heat energy. 3. Cost of capital. 4. Cost of depreciation-plant and insulation. 5. Capital investment in heat production equipment. 6. Temperature differential. 7. Size of the pipe or surface. 8. Conductivity of insulation. for cold piping, proper thickness is required for efficient operation and to prevent condensation on the insulation surface. Specifically: 1. Designed thickness should be specified to result in a surface temperature above the Dew-Point tem perature of the surrounding air. Generally this is equal to or greater than the "economical thickness" despite the relatively higher cost of cold Btu's. 2. Insulation thickness should be based on ambient air conditions and corresponding permissible tem perature differences. Ambient Air Condition 90 F at 90% R. H. 90 F at 80% R. H. Permissible temp, drop (between ambient air and insulation surface 3F 7F 3. Piping operating down to freezing temperature or cycling hot and cold temperatures should be in sulated for maximum performance during the cool est part of the cold cycle. Pipe Suface Temperature 35 F Condition Ice Water 90% RELATIVE HUMIDITY Recommended Thickness--Ambient Still Air At 90F PIPE SIZES copper tubing nominal sire Vi 1 V/i 2 Vi 4 V* m 2 3 5 6 ' 8 10 12 16 20 30 7 9 11 14 18 24 33 % %1 1 Vi 2V4 3'/2 5 Vi % 1</ 2 3 4 6 Recommended Thickness (in.) Heat Gain (Btu/lf/hr.) lVi m 2 m2 2 567 567 2 2 2Vi 21/2 2Vi 2Vi 2Vi 2 Vi 3 2 2 Vi 2Vi 2Vi 2Vi 2Vi 2Vi 3 3 8 10 12 15 17 21 25 31 32 9 11 14 16 19 23 28 32 45 1 Vi IVi iy2 1 Vi 2 IVi IVi 1 Vi 2 2 2 2Vi 21/2 2Vi 3.8 3.8 5.0 6.1 6.8 8.5 9.6 3.5 4.2 5.4 5.8 7.6 8.6 11.3 80% RELATIVE HUMIDITY Recommended Thickness (in.) Heat Gain (Btu/lf/hr.) % % 1 1 1 1 1 IVi iy2 IVi IVi IVi % % % % 1 1 1 % 1 1 1 1 1 IVi IV2 IVi IVi m IVi % % % 1 1 1 1 6 8 9 12 16 24 29 26 32 39 48 70 7- 9 I? 14 20 28 24 29 35 43 55 77 4.3 5.3 6.9 8.8 11.1 14.0 15.2 4.9 5.8 7.8 8.0 10.6 10.9 17.6 'Minimum thickness-available above 12" IPS is 1", above 24" IPS is 1 Wf Fiberglas 25 C-P Pipe Insulations installed by this unique method elimi nates the need for stapling, bands and lap adhesives. The contact type, adhesive offers a positive vapor seal at all joints and speeds applica tion. It's as easy as 1,2,3: (1) start to peel the release paper off the vapor barrier, (2) apply to pipe and peel off the balance. (3) place the lap in place at the center and, pressing hard, work out toward either end. Rub with the blunt edge of a knife. End joints are sealed with a 3" wide butt strip of the same Seif-Sealing vapor barried material. 17 Fiberglas 25 H-P Pipe Insulation System A noncombustible pipe insulation system for hot service piping operating at temperatures up to 450 F. uses Recommended for use on all heated piping operating at temperatures up to 450R where a complete noncombus tible insulation system is desired, for commercial and insti tutional buildings, schools, hospitals and places of public assembly. Also recommended for processing lines where fire safety is a paramount criterion. description Fiberglas 25* H-P Pipe Insulation System is composed of Fiberglas Heavy Density Sectional Pipe Insulation jack eted with a white pre-sized glass cloth jacket. Longitudinal jacket flaps are secured with flare-door staples. End joints are closed with a glass cloth tape stapled firmly in place. benefits fire safety--a complete insulation system with a UL rating including pipe fittings, and mastic when installed in accordance with recommended pro cedures. ready for painting--factory pre-sized glass cloth jacket and matching tape and mastic system do not require field sizing. If desired, painting may be omitted. "See Application Recommendations." damage resistant--the extra heavy density pipe insulation and extra tough woven glass cloth jacket resists damage on exposed lines. lower operating cost--the exceptional thermal effi ciency of Fiberglas Heavy Density pipe insulation contributes to lower operating cost of heating equipment and piping. 'Trademark Registered Owens-Corning Fiberglas Corporation 18 Performance characteristics Insulation dimensional stability: will not warp, shrink, rot or decompose specific heat: 0.20 Btu/lb F. vermin and rodent resistance: provides no sustenance temperature limitation: heated lines to 450F alkalinity: ph 9 stress corrossion: will not cause stress corrossion cracking of stainless steel Jacket permanence: mildew resistant. Will not rot or shrink. Vermin and rodent proof, burst strength: exceptional glass-cloth strength exceeds that of canvas Pre-sized Glass-Cloth 300 psi 8 oz Canvas 211 psi thermal conductivity 0 75 100 200 MEAN TEMP IFI 300 350 fire hazard classification Maximum Fire Hazard Classification for building materials and insulations as noncombustible has been established as follows: Flame Spread Fuel Contributed Smoke Developed Acceptable 25 50 50 Fiberglas 25 H-P Insulation System, including fittings, is below the maximum allowable. This is your assurance that you can specify and use Fiberglas 25 H-P Pipe Insulation System without the danger of contributing to the spread of fire or that combustion will liberate excessive smoke. The system has been designed to meet the stringent fire safety requirements of the GSA and Corps of Engineers. Underwriters Laboratories (Pipe & Equipment Coverings R5583 40 U 8.15) Flame Spread Fuel Contributed Smoke Developed Fiberglas 25 H-P Pipe Insulation System 20* 25 15 10 20 35 *Note: This rating is for the pipe insulation plus an unlimited number of fittings in a piping system when O-CF Fitting Mastic, Type H, is used. **Note: This rating is for the pipe insulation plus fittings when the sys tem is limited to 25% of fittings and BF 30*36 is used. finish The factory pre-sized white finish eliminates the necessity of sizing the jacket before painting and the neat white sur face may be left unpainted if desired. Fitting finish is also compatible with the insulation jacket. If painting is re quired, Glidden acrylic latex paint (No. 5370) is approved for use. application recommendations Fiberglas 25 H-P Insulation System is installed on the pipe by stapling the longitudinal jacket flap securely with flaredoor staples on 2" centers. End joints are closed by wrap ping with factory-furnished pre-sized glass cloth tape stapled in place. Fittings are insulated with Fiberglas molded or seg mental Insulation and wrapped with Fiberglas Rein forcing Cloth, Type H. The wrapping is subsequently coated with O-C-F Fitting Mastic, Type H or Benjamin Foster 30-36. federal specification compliance Fiberglas 25 H-P Pipe Insulation System meets the re quirements of Federal Specifications. HH-l-558a Form D; Type III, Class 12. ASTM C547-67 19 recommend thickness selection of an insulation thickness for any specific applica tion should take into consideration the following important criteria: l.Cost of insulation applied. 2. Cost of heat energy. 3. Cost of capital. 4. Cost of depreciation-plant and insula tion. 5. Capital investment in heat production equipment. 6. Temperature differential. 7. Size of the pipe surface. 8. Conductivity of insulation. The thicknesses shown in the table, below, are based on the optimum balance of these consideration for selecting an in sulation thickness for performance and economy. recommended thickness-heated piping to450F (80F Ambient still air.) Pipe Temp. 200 300 400 Temp. Diff. 120 220 320 IPS RT HL ST RT HL ST RT HL ST RT 14 % 1 IV* 1)4 2 2Vi 3 -3)4 4 4)4 5 6 7 8 9 10 11 12 14 16 18 20 24 30 14 19 14 22 Vi 25 1 20 1 21 1 24 1 28 1 - 32 1 30 1 39 1 38 1 50 1 57 1 62 1 68 1 80 114 59 1)4 64 114 80 1% 92 114 93 114 101 1% 110 1)4 131 2 132 105 Vi 34 107 1 29 107 1 30 95 1 37 93 1 39 94 1 45 94 1*4 50 94 114 50 95 IVi 56 95 1*4 57 95 114 72 95 114 70 97 114 85 96 114 90 96 114 100 97 114 110 91 114 110 91 114 120 96 114 149 92 114 171 92 2 133 92 2 148 92 2 162 93 2 194 92 2 257 125 1 39 106 1 46 102 1 48 108 1 62 106 1 63 106 1 73 101 114 74 101 114 76 103 114 94 101 114 94 104 114 118 100 114 114 101 114 128 100 1*4 142 101 2 125 101 2 138 101 2 146 101 2 168 107 2 171 110 2 190 97 214 181 97 214 204 97 214 222 98 214 266 98 214 323 115 1 122 1 117 1 125 1 121 114 122 114 113 114 110 114 111 114 112 114 115 114 115 114 115 2 110 2 107 2 106 2 106 2 106 2 106 2 108 214 103 214 103 214 103 2 >4 104 214 103 214 RT--recommended thickness HL--heat loss, Btu/hr/lineal foot ST--surface temperature (F) HG--heat gain 450 370 HL 47 56 60 75 62 70 88 93 114 114 148 140 125 136 154 174 180 194 209 199 223 248 271 320 361 ST 123 131 129 135 112 113 121 116 118 118 121 121 110 108 111 111 111 111 112 107 108 108 108 109 105 20 Kaylo 10 & Kaylo 20 Pipe Insulations Rigid hydrous calcium silicate pipe insulations for heated piping up to 1800 F. uses Kaylo 10 is recommended for use on heated piping operating up to 1200F and Kaylo 20 extends the tem perature range to 1800F. These thoroughly field-tested insulations have the physical properties most desirable for efficient, durable work for indoor and outdoor, power and process piping. A variety of jackets are available for surface finish and weatherproofing. benefits lower operating costs --Kaylo Insulations have ex ceptional thermal efficiency. The low k factor of .40 at 200 mean temperature means lower operating cost, better temperature control for process operations. rugged -- Kaylo Pipe Insulations are strong and rigid to resist mechanical abuse in shipping, handling and in service versatile -- Kaylo's extended temperature range cov ers a broad number of uses with one material. All heated piping requirements to 1800F and in sizes from W to 30" I PS can be met with Kaylo and Kaylo 20. will not cause stress corrosion cracking -- Kaylo 10 will not cause stress corrosion cracking of stainless steel because it contains an inhibitor, and has less than 75 ppm soluble chlorides. description Kaylo 10* & Kaylo 20* pipe insulations are rigid hydrous calcium silicate heat insulations for use on all heated piping up to 1800F--indoors and out. These products are precision molded in sections or segments from a chemically reacted material. A small amount of asbes tos fiber is added to improve mechanical strength. Kaylo 10 is white. Kaylo 20 has a slight pinkish color to distinguish it from Kaylo 10. unaffected by moisture -- Kaylo can be completely saturated in water without appreciable loss of strength and regains its strength and thermal value after dry ing out. clean, neat installation -- Kaylo cuts cleanly leaving a sharp square edge for neater appearance on fittings. Rigid manufacturing tolerances assure uniform, smooth, unbroken joints. variety of jackets --A variety of factory-applied jack ets allows a selection of product for indoor finished appearance or for weatherproofing insulation on out door lines. nesting sizes -- Kaylo Pipe Insulations are manu factured to Simplified Dimensional Standards to per mit nesting sizes for double layer applications. tKaylo is a registered trademark (Reg. U. S. Pat. Off.) of Owens-Corning Fiberglas Corp. 21 Performance characteristics Kaylo 10 Kaylo 20 density (approx.) modulus of rupture (ASTM C-446) compression strength (ASTM C-165) at 5% deformation resistance to abrasion (Conventional tumbling test-loss in weight before heating) (ASTM C-421) 11 lb. pcf. 12 lb. pcf. 75lbs./sq. in. 70lbs./sq.in. 115 psi 110 psi after 10 minutes, 20% max. after 20 minutes, 45% max. corrosion resistance dimensional stability linear shrinkage after heating for 24 hours in a muffle (ASTM C-356) does not cause or acceler ate corrosion of steel, alu minum, or stainless steel hardness (ASTM C-569) % length loss .75 1.4 (at 1200F) .70 2.0 (at 1800F) thermal conductivity sizes thickness -- Kaylo Pipe Insulation is available in single or double layer thicknesses from 1" to 3" depending upon pipe size. Kaylo Tube Insulation is available in single layer thick nesses of 1" and lVb". pipe sizes -- Kaylo Pipe Insulation is available to fit nominal pipe sizes from Vi" to 39" in diameter. Kaylo Tube Insulation will fit nominal copper tubing sizes from %" to 3" in diameter. forms -- Kaylo Pipe Insulation is available in sectional or multisegmental form depending upon pipe size. All insulation is furnished in 3 ft. sections. jackets canvas--Standard canvas & 8 oz. canvas jacket are available for all types, sizes and thicknesses of Kaylo Pipe and Tube Insulation at an additional charge. These jackets are factory applied on Sectional Pipe and Tube Insulation. On Multiseg mental forms, they are furnished but not adhered. Bands are available for use with this product at slight additional charge and will be furnished on request. Kaylo Klad -- Kaylo is also available with an embossed alu minum jacket .016" thick or .010" thick stainless steel jacket. These jackets provide greater resistance to mechanical dam age and present a neat finished appearance to pipe lines. The longitudinal seam has a self-locking joint. Butt sealing strips with integral mastic and protective asbestos cover are furnished for sealing end joints. specification compliance HH-l-523c--Insulation Block and Pipe Covering Thermal (Cal cium Silicate for Temperatures up to 1200F). Type II, Class A through F. MIL-1-278ID (Int. Amend. 1) -- Insulation Pipe Covering, Thermal: Grade I, Class b; Grade II, Class d; Grade III, Class e, Type I and II. MIL-l-24244 (Ships)* -- Insulation Materials, Thermal, with Special Corrosion and Chloride Requirements, Type 1A, 1C, ID, IE. ASTM C533-67 *KaylolOonly application recommendations outdoor lines -- Kaylo Pipe Insulations are mechanically fastened by wiring in place using 16 gauge wire on 9" centers and subsequently covered with a weatherproof jacket of metal or 45 lb. roofing felt. See Application Specifications for com plete details. indoor lines -- Kaylo for indoor piping work is furnished with a factory-applied canvas jacket and held in place with bands or wire. The jacket has overlapping joint flaps that are smoothly pasted in place. Canvas should be sized to provide a base for painting. fittings -- Fitting are insulated with mitered segments of Kaylo wired in place and finished with a Va," layer of insulating cement. Flanges and valves are insulated with oversized pipe insulation. They are finished off with canvas pasted in place for indoor lines or reinforced waterproof mastic for outdoor lines. For tables on economic thickness refer to Owens-Coming Fiberg/as Corporation Pub. No. I-IN-4350-B (page 5.3 in Mechanical Insulation Systems manual. Pub. No. 14-/N-2600-A) 22 Fiberglas 25 C-E Equipment Insulation System A noncombustible rigid board insulation and vapor barrier system for cold and dual-temperature service ducts and equipment operating at temperatures down to 35 F. uses Recommended for use on all cold or dual-temperature service rectangular ducts and cooling equipment where the ultimate in noncombustibility is desired. Boards are impaled over welded pins and held in place with white fastener caps vapor sealed with mastic. benefits fire safety--the only complete insulation system with UL rating on board, vapor barrier, joint tape, mastic and fastening device. ready for painting--the pre-sized glass cloth fac ing, matching tape and fastener caps, do not re quire field sizing. They may be left unpainted if desired. damage resistant--the tough finely woven glass cloth facing resists damage and the semi-rigid in- Fiberglas (Reg. U.S. Pat. Off.) and "25" are trademarks of Owens-Corning Fiberglas Corporation. description A Fiberglas 25* C-E Equipment Insulation System for cold temperature service consists of a rigid board of glass fibers faced with a noncombustible vapor barrier facing. The facing is a laminate of vapor tight alumi num foil and pre-sized glass cloth. Joints are sealed with a noncombustible vapor barrier pressure sensi tive adhesive tape to form a complete vapor tight system. sulation board is resilient thereby absorbing im pact and resisting damage. lower operating cost--the uniform, factory con trolled board thickness assures constant thermal efficiency performance. no condensation drippage--the factory-applied glass cloth and foil vapor barrier and the taping system make the system vapor tight to resist vapor penetration. 23 Performance characteristics dimensional stability: will not warp, shrink, rot or decompose vermin and rodent resistant: provides no sustenance flame hazard classification: Flame Spread Flame Contributed Smoke Developed 20 10 35 temperature limitations: recommended for heated surfaces when temperatures do not exceed 450F or fall below 35F vapor transmission rate: .05 perms thermal conductivity ___________________ 50 C c c1/1r 0 75 100 200 MEAN TEMP (F) 300 350 sizes Width 24", Length 48", Thickness 1", 1W\ 2". fire hazard classification Maximum Fire Hazard Classification for buidling materials and insulation as noncombustible has been established as follows: Flame Spread Fuel Contributed Smoke Developed Acceptable 25 50 50 Fiberglas 25 C-E Insulation System, including joint sealing treatment, is considerably below the maximum allowable. This is your assurance that you can specify and use this system without the danger of contributing to the spread of fire or that combustion will liberate excessive quantities of smoke. The system has been designed to meet the strin gent fire safety requirements of GSA and Corps of Engineers. Underwriters Laboratories (Pipe & Equipment Coverings R5583 40 U 8.15) *`Fiberglas 25 C-E Insulation Systems Flame Spread 20 Fuel Contributed 10 Smoke Developed 35 **NOTE:This rating is for the composite product and includes the use of 0-CF Type C Joint Sealing Tape for sealing joints. specification compliance Meets the stringent fire safety requirements of GSA and Corps of Engineers HH-l-558a, Form A, Class 1 & 2. Meets NFPA 90 A Fire Hazard Classification. application recommendations The Fiberglas 25 C-E Insulation System is installed by im paling the insulation boards on welded pins spaced 3" in from each corner of the board with intermediate pins of no greater than 21" centers. After boards are impaled, the welded pins are cut to extend W beyond the face of the board. A self-locking cap is pushed onto the pin after coating with OC Fitting Mastic (Type C) to provide a vapor seal. All insulation edges and butt joints are to be sealed with O-CF Type C Joint Sealing Tape.Tape is a pressure sealing type requiring no separate adhesive. Pressurize tape by rubbing hard with a nylon sealing tool. Ductwork els and other sharp radius bends require pre scoring of the insulation board to conform to the curved surface. If painting is required, no sizing is necessary; but, to main tain the noncombustibility of the system, only Glidden acrylic latex paint (No. 5370) is to be used. thickness to prevent condensation cold ducts and eauioment The following chart indicates the recommended thickness for installation on cold air ducts at various temperature differences (duct to air). Also shown are values for heat gain and approxi mate maximum relative humidity allowable. Temperature Differences 20 25 30 35 40 45 50 Recommended Thickness (inches) y,J/ 1 1 H* 1V4 2 Heat Gain Btu/ftz-hr 5.1 6.4 6.1 7.1 5.7 6.3 5.4 Permissible Relative Humidity 90% 87% 89% 88% 90% 89% 90% 24 Fiberglas 25 H-E Equipment Insulation System v: A non-combustible rigid board insulation system for hot service ducts and equipment operating at temperatures up to 450 F. uses Recommended for use on all hot mechanical equipment and ductwork operating up to 450 F, where the ultimate in noncombustibility is desired. description A Fiberglas 25* H-E Equipment Insulation System for heated surface service consists of a rigid insulation board of glass fibers faced with a noncombustible pre-sized Fiber glas cloth. Other components of the system include a non combustible pressure sealing joint tape and pre-finished metal fastener caps attached to welded pin anchors. benefits fire safety--a complete insulation system with UL rating on board, facing, joint tape, fastening de vice. ready for painting--the pre-sized white glass cloth facing, matching tape and fastener caps do not require field sizing prior to painting. If painting is required, use recommended paint. damage resistant--the tough finely woven glass cloth facing resists damage and the rigid insula tion board absorbs most impact blows without damage. lower operating cost--the uniform, factory con trolled board thickness assures constant thermal efficiency performance. Fiberglas (Reg. U.S. Pat. Off.) and ,-25" are trademarks of Owens-Corning Fiberglas Corporation. 25 Performance characteristics dimensional stability: will not warp, shrink, rot or decompose vermin and rodent resistant: provides no sustenance flame hazard classification: Flame Spread Flame Contributed Smoke Developed 25 10 50 temperature limitations: recommended for heated surfaces when temperatures do not exceed 450 F jacket burst strength: 300 psi thermal conductivity: 75 100 200 MEAN TEMP (F) 300 350 sizes Width-24", Length 48", Thickness 1", IV2", 2". fire hazard classification Maximum Fire Hazard classification for building materials and insulation as noncombustible has been established as follows: Flame Spread Fuel Contributed Smoke Developed Acceptable 25 50 50 Fiberglas 25 H-E Insulation System, including fittings, per forms below the maximum allowable. This is your assur ance that you can specify and use this system without the danger of contributing to the spread of fire or that com bustion will liberate excessive smoke. The system has been designed to meet the stringent fire safety requirements of GSA and Corps of Engineers. Underwriters Laboratories (Pipe & Equipment Coverings R5583 40 U 8.15) Flame Spread Fuel Contributed Smoke Developed ~ Fiberglas 25 H-E Insulation System 25 10 50 *Note: This rating is for the composite product and includes the use of O-CF Type H Joint Sealing Tape if materials and application conform to those recommended. specification compliance meets the stringent fire safety requirements of GSA and Corps of Engineers HH-l-558a, Form A, Class 1 & 2. ASTM C392-63 Meets NFPA 90A fire hazard requirements. application recommendations Fiberglas 25 H-E Equipment Insulation System is. in stalled by impaling the insulation boards on welded pins spaced 3" in from each corner of the board with inter mediate pins on no greater than 21" centers. After boards are impaled, the welded pins are cut to extend W beyond the face of the board and a self-locking cap is pushed onto the pin. All insulation raw edges and butt joints are to be sealed with O-CF Joint Sealing Tape, Type H. Tape is a pressure sealing type requiring no separate adhesive. Pressurize tape by rubbing hard with a plastic sealing tool. Ductwork els and other sharp radius bends require pre scoring of the insulation board to conform to the curved surface. If painting is required, no sizing is necessary; but to main tain the noncombustibility of the system, only Glidden acrylic latex paint (No. 5370) is approved for use. recommended thickness--heated equipment (80F ambient still air) Operating temp. RT HL ST 150F 1 15 89 250F l`/2 29 98 350F 2 39 104 450F 2 61 117 RT-- recommended economic thickness, inches. HL -- heat loss (Btu/ft2-hr.). ST -- surface temperature (F). 26 Industrial Insulation 700 Series A highly versatile group of Fiberglas insulating boards designed to insulate ductwork and equipment operating at temperatures up to 450F. uses The 700 Series boards have been designed primarily to insulate heating and air conditioning ducts, ovens, tanks, boilers, hot water generators and other hot equipment. type 700 --a low cost flexible material suitable for insulating factory-fabricated metal panels and for packing into irregular spaces type 701 --A lightweight resilient insulation, in board form, used on vessels having irregular surfaces where the exterior finish is supported by welded studs, pins or other mechanical attachments type 702 -- More rigid than 701 and is recommended for use on equipment and cTuctwork subject to minmum maintenance and construction abuse type 703 -- A semi-rigid board recommended for use on equipment, vessels and air conditioning ductwork. description Fiberglas * 700 Series Industrial Insulations are made of inorganic glass fibers pre-formed into semi-rigid to rigid rectangular boards of varying densities. The series consists of Type 700, 701, 702, 703, 704 and 705. Each type has specific thermal and physical characteristics which makes it suitable for the uses described. Type 703, 704 and 705 are available with a variety of factoryapplied vapor-barrier facings to prevent condensation on cold'surfaces and to provide a neat finished appearance. Fire Retardant Facings are available. type 704 --A rigid board recommended for use on heating and air conditioning ductwork in exposed areas where sharp, true corners and smooth surfaces are desired. type 705 --A rigid board with very high strength char acteristics for use on chillers, hot and cold equipment, heating and air conditioning ductwork where greater abuse resistance and good appearance is required. benefits lower operating costs --the exceptional thermal efficiency of Fiberglas 700 Series Insulations lowers operating costs. end-use tailored -- a variety of densities and facings offers a selection of products to meet specific per formance and economic requirements. continuous in-place performance -- 700 Series resists `Trademark Registered Owens-Corning Fiberglas Corporation damage, maintains structural integrity and efficiency. Thickness stays uniform. neat, finished appearance -- the boardlike character istics of the heavier density 703, 704 and 705 products provide neat square corners. The factory-applied facings present an attractive finished appearance. fire safe -- Fiberglas is inherently fire safe. The un faced boards and the Aluminum Foil Faced 703, 704 and 705 have UL Flame Spread ratings of less than 25. 27 Performance characteristics sound absorption coefficients (2" thick #6 mounting) TYPE 125 250 500 1000 2000 701 .34 .70 .96 .97 .86 702 .28 .77 .96 .98 .87 703 .32 .74 .97 .98 .87 704 .27 .79 .98 .99 .88 705 .48 .82 .97 .99 .90 4000 .83 .87 .85 .86 .86 NRC '.87 .89 .89 .91 .92 size and density Density Thiekness Compressive Strength Standard Type (pef) (in Vi" increments) (psf at 10% deformation) Size Therm. Corn). @ 75F Mean Temp. 700 1.08 701 1.58 702 2.25 703 3.00 704 4.20 705 6.00 1_4" 1 "--4" 1"--3" 1"--2" 1 "--2" 1"--2" 3f 4.5t 9.5f 100 200 350 24" x 48"* 0.260 0.242 0.235 0.230 0.230 0.220 For special applications, boards up to 48* x 96* are available. fAfter compression packaged. thermal conductivity 0 75 100 200 MEAN TEMP (F) 300 350 moisture absorption......................................................................................................... less than 0.2% by volume bacteria and fungus resistance............................................................................. does not breed nor promote odor..................................................................................................................................................................... ...........odorless humidity and temperature effect...................cycling conditions will not cause spalling or crumbling corrosion........................................................ does not accelerate corrosion of copper, steel or aluminum. 28 facings Type 703, 704 and 705 are also available with the following factory applied vapor barrier facings: FF -- .0025 aluminum foil (UL Rated) FRK -- Foil-reinforced kraft SF -- Duplex Laminated kraft COATED -- either clear or black fire hazard classification unfaced foil-faced (700, 701, 702) (703, 704, 705) (703, 704, 705) flame spread 10-20 15 fuel contributed 10-15 15 smoke developed 0-20 0 (compared to untreated Red Oak as 100) 15-20 20-35 0 application recommendations Type 700, 701, 702 -- Lightweight unfaced flexible insulations jn board form for use on vessels having irregular surfaces where the exterior is supported by welded studs or stiffeners and not by the insulation itself. The products are self-sup porting but are generally secured with mechanical fasteners and protected by sheet metal. Type 703, 704, 705 --These board insulations are normally impaled on welded pins on flat surfaces. They are cut in segments and banded in place on irregular surfaces. Unfaced boards are normally finished with reinforced insulating cement or weatherproof mastic. Faced boards, with joints taped to provide a continuous vapor barrier, may be left unfinished or may be canvas jacketed. recommended thickness -- heated equipment (80F ambient air) Surface Type 701 Temp. RT HL ST 150 1*4 11 87 250 2 24 95 350 3 29 98 450 3*4 40 105 Type 703 RT HL ST 1*4 10 86 2 21 93 2*4 31 99 3 40 105 Type 704 RT HL ST 1*4 10 86 2 20 92 2*4 30 98 3 39 104 RT -- recommended economic thickness, inches. HL -- heat loss (Btu /ft2-hr.). ST -- surface temperature (F). thickness to prevent condensation cold ducts and equipment The following chart indicates the recommended thickness of Type 703, 704, 705 Faced Duct Insulation for installation on cold air ducts at various temperature differences (duct to air). Also shown are values for heat gain and approximate maximum relative humidity allowable. Temperature Difference* 20 25 30 35 40 45 50 Recommended Thicknest (inchM) /a y 1 1 1*4 1*4 2 Heat Gain Btu/ftz-hr 5.1 6.4 6.) 7.1 5.7 6.3 5.4 Permliclble Relative Humidity 90% 87% 89% 88% 90% 89% 90% specification compliance HH-l-542, Type I HH-l-542, Type II 700 701, 702, 703 HH-l-558a, Form A, Class 1. HH-l-558a, Form A, .Class 2. HH-l-558a, Form 8, Type 1, Class 7. 702, 703**, 704, 705 703**, 704, 705 700, 701, 702 HH-l-562, Type I, Class 2. HH-l-563, Type II, Class D. (5Q0F***) HH-l-564, Form I & II, Class A. Navy Bureau of Yards and Docks, 16Yf Corps of Engineers, C.E.--301.08, .11 thru .17 703**, 704, 705 701, 702, 703 703**, 704, 705 703**, 704, 705 703**, 704, 705 Type 703 Q is specially produced for contracts where certification of compliance to the above federal Specification is required. Available plain or faced for use on hot or cold equipment and for air conditioning ductwork. Waiver required on upper temperature limit limitations Industrial insulation 700 series, plain, should not be used on surfaces operating at temperatures above 450F. Types 703, 704, 705 faced products should not be used on surfaces op erating at temperatures greater than 250F except that FF may be used at a maximum thickness of 2*4 inches up to 450F. caution Owens-Corning Fiberglas Insulations are to be applied only with approved adhesives, mastics and mechanical fasten ing devices as published in Accessory Materials List, Pub. No. 4-IN-3430. Owens-Corning Fiberglas accepts no respon sibility or liability for the performance of materials other than those listed unless approved in writing by O-CF Test ing Laboratories. 29 Intermediate Service Board A lightweight, highly efficient, semi-rigid insulation for service temperatures up to 850F uses Fiberglas* l-S Board Insulation is designed for use on boilers, breechings, ducts, chimney liners and other heated equipment operating at temperatures up to 850 F. It is designed for use in applications where an outside facing of steel sheet or metal mesh (with or without finishing cement) is provided. description Intermediate Service Insulation (l-S) is a lightweight insulation composed of Fiberglas fibers bonded together in semi-rigid, boardlike form with a special high tem perature binder. benefits Lowers operating costs--Fiberglas Intermediate Service Board is an extremely efficient thermal insulation. A low k factor of .30 at 200 F mean temperature means lower fuel costs due to less heat loss--more comfortable working conditions in equipment rooms. This superior thermal efficiency is attained because of finer fiber construction and the complete absence of shot or unfiberized material. Heat flow tests on a 600 F power plant duct insulated partially with l-S insulation and with a 8 pcf mineral wool insulation showed that l-S board had superior heat flow characteristics over an 18-month period of continuous service. Lower cost installation--the lightweight feature of l-S Board Insulation means easier handling; and the larger `Trademark Registered Owens-Corning Fiberglas-Corporation size pieces, up to 4' x 4', speed installation and reduce the number of joints to leak heat. Larger sizes are possible because of unusual structural integrity. The insulation will not crumble or break; cuts cleanly for good tight joints; conforms readily to irregularities and curved surfaces and returns to full thickness if compressed. Continuous in-place performance--Fiberglas Intermediate Service Board will not slump or deteriorate in severe service conditions. The insulation easily passed the rugged Navy Test MH-I-15475C (Ships), Paragraph 4.5.3 which requires vibration at 12 cps through an arc of .015" for 100 hours at 750F, without setting. 30 Performance characteristics $ sizes: 2' x 2'; 2' x 4'; 4' x 4' thicknesses: 1 to 4" in W increments, moisture absorption: less than 0.2% by weight specific heat: 0.20 Btu/lb., F 0 100 200 300 400 500 Mean Temperature. F. heat transfer data operating temperature (ambient still air 80 F) thickness in inches 450 F 500 F 550 F 600 F 65 D F 70 0 F 751 F 80 ] F 85( F heat surf heat surf heat surf heat surf heat surf heat surf heat surf heat surf heat surf loss temp loss temp loss temp loss temp loss temp loss temp loss temp loss temp loss temp 2.0 61 117 73 125 88 133 103 143 121 154 140 2.5 49 110 59 116 71 123 84 131 98 140 113 149 131 160 149 3.0 41 105 50 110 59 116 70 123 82 130 95 138 110 147 125 156 143 3.5 36 102 43 106 51 111 60 117 71 123 82 130 94 138 108 146 123 155 4.0 31 99 38 103 45 107 53 112 62 .118 72 124 83 130 95 138 108 146 4.5 28 97 34 101 40 104 47 109 55 114 64 119 74 125 84 131 96 138 5.0 25 95 30 99 36 102 43 106 50 110 58 115 66 121 76 126 85 133 5.5 23 94 28 97 33 100 39 104 45 108 53 .112 61 117 69 122 79 128 6.0 21 93 25 96 30 98 36 102 42 105 48 109 56 114 63 119 72 124 I limitations l-S Board must be applied flush against the hot surface with an exterior finish of sheet metal mesh (with or without a cement coating) whenever it is exposed to temperatures in excess of 350 F. There will be no rapid decomposition of the product after inserting a 1300F probe into the insulation for 20 minutes with the hot surface at 850F when the product is applied as noted above. application recommendations Fiberglas Intermediate Service Insulation is installed on flat and curved surfaces by attaching with welded pins or studs and finishing with sheet metal; or metal mesh and insulating cement, canvassed and painted. Pins with speed washers, or studs and nuts are installed on a maximum spacing of 18"and not farther than 6" from the edge of the insulation. The insula tion is normally impaled over the pins or studs and the enclos ing sheet metal or metal mesh is secured to the same fasteners. Joints of the sheet metal finish are offset from the joints of the insulation. Double-layer application is recommended for tem perature over 600 F. federal specification compliance MlL-l-i 5475C (Ships) (except for fusing temperature) HH-l-558a Insulation, Blocks, Boards, Blankets, Felts, Sleeving (Pipe and Tube Covering) and Pipe Fitting Covering, Thermal (Mineral Fiber, Industrial Type), Form A, Class 3 (waiver needed on compression strength). 31 Thermal Insulating Wool (TIW) Types I & II Resilient, lightweight, inorganic insulation for applications up to 1000 F. ^ uses TIW, Type I is used in applications requiring a lightweight insulation such as in panel systems, flexible wrap, industrial ovens, or surfaces having irregularities. It's low compressive strength does not make it suitable for use as a base wool for metal mesh blankets. TIW, Type II is especially suitable for use in metal mesh blankets, and for use on boilers, vessels and many other types of industrial equipment operating at temperatures up to 1000 F. It may also be used in panel systems for. precipitators ducts and breechings where more compressive strength than Type I is needed. description TIW, Type I and II are off-white to light tan, non-combustible wool with long, resilient, inorganic glass fibers bonded with a thermosetting resin. TIW, Type I is available in batts or rolls, while TIW, Type II comes in batts only. t benefits Lowers Operating Costs -- the low K factor of Fiberglas* Thermal Insulating Wool can substantially lower fuel costs by reducing heat loss, and helps develop more comfortable working conditions in equipment rooms. Lowers Installation Costs -- larger blankets cover greater areas reducing installation cost. No tedious block-by-block hand lay-up. No drilling for studs. Type II blankets are easily impaled over welded studs or pins with speed washers or may be held in place with wire ties, metal lath or lagging. Dimensionally Stable -- will not shrink, rot or slump. Non-Corrosive -- inorganic fibers of Fiberglas TIW Type I and II, will not cause or accelerate corrosion of any metal. It cannot cause stress corrosion cracking of stainless steel. Moisture Resistance -- Fiberglas TIW Type I and II do not absorb moisture. If the insulation becomes wet, it dries out rapidly when exposed to dry air, and without any residual loss of integrity or thermal efficiency. Fire safe -- glass fibers will not burn or support combustion. `Trademark Registered Owens-Corning Fiberglas Corporation 32 5 Performance characteristics Moisture absorption % by volume Temperature limit Bacteria and fungus resistance Odor Specification compliance: Type I 0.1 % or less 1000 F Type II 0.2% or less 1000 F Does not breed or promote Essentially odorless Tiw, Type I -- HH-1-558a Form B -- Blankets and Felts, Flexible Type I, Class 8 TIW, Type II -- HH-l-558a Form B -- Blankets and Felts, Flexible Type I, Class 8 Mil-1-2818 B -- Insulation Blanket, Thermal Fibrous Material (Requires waiver on ignition loss) Thermal Conductivity 0 100 200 300 400 500 MEAN TEMP. Sizes TIW, Type I Standard Roll Sizes Width -- 24" or 36" Thickness 1" 2" 3" 4" Lengths 76' 76' 52' 38' Note: MTO thicknesses are available in 'A" increments MTO widths are available 12", 18", 24" and 72 TIW, Type II Standard Batt Size 24" x 48" 24" x 96" Made-to-Order Width -- 10" (min) to 38" Length -- 10" (min) to 117" Thickness -- 1 "-3" (V2" increments) Recommended Thicknesses Recommended thickness, heat loss, efficiency and surface temperature data are provided for the various Commercial, Power and Process Industries so that the design engineer can better select the thickness required for his specific job conditions. On outdoor work increase recommended thickness at least V2 inch to compensate for wind conditions. TIW, Type 1 Operating Temperature (Ambient Air 80F) RT HL 500 600 700 800 900 1000 4 55 5 64 6 75 7 90 8 106 8.5 131 RT -- recommended thickness (inches) HL -- heat loss (Btu/hr/sq. ft.) ST -- surface temperature (degrees F) ST 114 119 126 135 145 160 TIW, Type II Operating Temperature 200 300 400 500 600 700 800 900 1000 (Ambient Air 80F) COMMERCIAL POWER PROCESS RT HL ST .75 35 102 1.5 38 103 2.5 38 103 RT HL ST 1.5 21 91 2.0 30 95 2.5 39 100 3.0 47 104 3.5 56 108 4.0 64 112 5.0 74 117 5.5 83 122 6.0 94 127 RT HL ST 1.0 26 93 1.5 37 99 2.0 47 104 2.5 58 109 3.0 68 114 3.5 79 120 4.0 90 125 4.5 101 131 5.0 114 137 33 Kaylo 10 & Kaylo 20 Block Insulation rigid calcium silicate insulations for all types of heated equipment operating at temperatures up to 1800F. uses Kaylo 10* Block is for use on indoor or outdoor equipment operating at temperatures up to 1200F. Kaylo block is ideally suited for use on stainless steel vessels and equipment as it helps inhibit stress corrosion cracking. Typical applications are for boilers, breeching, tanks, vessels. Kaylo 10 Block is white in color. Kaylo 20* with its high temperature limit of 1800F extends its use to include refractory wall backing for furnaces and boilers and fireproofing of equipment and vessel skirts. description Kaylo 10 and Kaylo 20 Block Insulations are rigid hydrous calcium silicate heat insulations reinforced with asbestos fibers. They are strong, efficient and are highly resistant to abrasion and moisture damage. Kaylo 20 has a slightly pink color to distinguish it from Kaylo 10. benefits high thermal efficiency--both Kaylo 10 and Kaylo 20 offer excellent thermal efficiency coupled with high strength. A low k of .40 for Kaylo 10 and .52 for Kaylo 20 at 200F mean temperature proves that Kaylo will provide significant savings in operating costs over the life of the equipment. resistant to abuse--resists mechanical damage because of hard, tough, reinforced structure. strong--less breakage in shipment and handling. High temperatures have little effect on strength characteristics. will not cause stress corrosion cracking--Kaylo 10 will not cause stress corrosion cracking of stainless steel because Kaylo 10 contains less than 75 ppm soluble chlorides as well as an inhibitor which prevents trace quantities of chlorides from the atmosphere or other ^Trademark Registered Owens-Corning Fiberglas Corporation sources from causing cracking and possible failure of piping and equipment. resistant to moisture damage--unlike many other insulations, Kaylo is not affected appreciably from moisture damage. It regains thermal efficiency and strength after drying out. Outdoor installations must be weatherproofed, however, for long continuous service. dimensionally stable--Kaylo does not shrink appreciably in service, even at elevated temperatures. This means less heat leakage at the joints. And Kaylo will not warp or crack in service. fabricates easily--ordinary insulators tools are all that is required to fabricate Kaylo. It cuts with a clean true edge for tighter fit at the joints. Fittings are neater, faster. 34 Performance characteristics density: flexural strength: (ASTM C-203) compressive strength: (ASTM C-165) at 5% deformation KAYLO 10 11 pcf approx. 60 psi average 115 psi KAYLO 20 12 pcf. approx. 65 Ib./sq. in. 110 psi thermal conductivity resistance to abrasion: (ASTM C-421) dimensional stability: (ASTM C-356) hardness: (ASTM C-569 after 10 minutes, 20% max. after 20 minutes, 45% max. linear shrinkage after heating for 24 hours in muffle at 1200F.--1.4% (Kaylo 10) for 24 hours in muffle at 1800F.--2.0% (Kaylo 20) .60 .70 economic thickness* Selection of insulation thicknesses for any specific applica tion should take into consideration the following important criteria. 1. Cost of insulation applied. 2. Cost of heat energy. 3. Cost of capital. 4. Cost of depreciation --plant and insu lation. 5. Capital investment in heat production equipment. 6. Temperature differential. 7. Size of the pipe or surface. 8. Conductivity of insulation. From "How to Determine Economic Thickness of Insulation"-- National Insulation Manufacturers Association. economic thickness--Kaylo 10 block to 1200 F-- ambient still air 80 F ET--economic thickness HL--heat loss ST--surface temperature Btu/hr/lin/foot THICK 200 F 300 F 400 F 500 F 600 F 700 F 800 F 900 F 1000 F 1100 F 1200 F HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. HEAT SURF. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. LOSS TEMP. 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 38 103 72 124 109 147 27 96 51 111 78 127 107 145 21 93 40 104 60 117 83 130 107 145 17 90 33 100 49 110 68 121 87 133 109 146 14 89 28 97 42 105 57 115 74 125 92 136 112 148 13 88 24 95 36 102 49 110 64 119 80 129 97 139 116 150 11 87 21 93 32 99 44 107 56 114 70 123 85 132 102 142 120 153 10 86 19 91 28 97 39 104 50 111 63 118 76 127 91 136 107 145 125 156 9 85 17 90 26 96 35 101 46 108 57 115 69 122 82 130 97 139 113 149 130 159 8 85 16 89 23 94 32 100 42 105 52 112 63 118 75 126 88 134 103 143 118 152 7 85 14 89 22 93 30 98 38 103 48 109 58 115 69 122 81 130 94 138 109 146 'calculated Kaylo 20 Block to 1800 F--ambient still air 80 F Operating Temp. F 1300 1400 1500 1600 1700 1800 Power ET HL ST 7 *A 111 136 8 117 139 8 123 142 8 Vi 129 145 9 135 148 9 Vi 141 151 Process ET HL 6 135 6V4 143 7 151 7 158 7 Vi 165 1'h 172 ST 148 152 155 159 163 166 specification compliance HH-l-523c Insulation Block, Pipe Covering, Thermal, (Cal cium Silicate for temperatures up to 1200F). Type 1. MIL-1-2819E Insulation Block, Thermal. Class 1, 2, and 3. ASTM C533-67. MIL-1-24244 (ships) Insulating Materials, Thermal, with Special Corrosion and Chloride Requirements (Kaylo 10 only). Type 3A, 3B. sizes thickness--1", 1W, 2", 2W\ 3", 3Vz" and 4" width--3", 6", 12" and 18" length--18" to 36" form --Block beveled lags For pipe sizes greater than those for which Kaylo 10 and Kaylo 20 Pipe Insulation sizes are available, Kaylo 10 and Kaylo 20 beveled lags may be used to insulate piping. Lags beveled to fit pipes from 18" to 72" in diameter are available in thickness of IV2," 2", 2Yz" , 3". Lags are 36" long and 3" wide. application recommendations Kaylo 10 & 20 Block Insulations are held in place by mechanically fastening with bands, welded rods or studs. The insulation may be finished with a trowel coat of insulating cement, canvassed and painted. Out door installations require weatherproofing with mastic or metal jacketing. 35 0-C Flexible Tubing and Sheet Insulation "Standard" A flexible foamed plastic insulation for hot or cold copper tubing and iron pipe operating at temperatures from -50 to 220 F. uses 0-C Flexible Tubing is recommended for use on cooling and heating water lines, chilled drinking water and refrigerent suction lines. The flexible feature of this resilient insulation allows it to conform to gradual bends. Available unslit to slide over tubing or pipes before they are installed, or, slit to apply over piping already in place. description 0-C Flexible Tubing Insulation is made from an expanded elastomeric plastic blend. Millions of tiny cells, each filled with an inert gas, make this product an extremely efficient insulator. It is resilient and soft, returning to full thickness after being compressed. The inside surface is powdered to make it easy to slip over the pipe or tubing. benefits Efficient--a low thermal conductivity of 0.26 at 70 mean temperature assures minimum heat loss or gain--maximum performance of equip ment. Built-In Vapor Barrier--the closed cell struc ture eliminates the need for a separate vapor barrier and protects against moisture conden sation on cold lines. Uniform Thickness--strict quality control as sures constant diameters and thicknesses, pro viding a snug fit on the pipe, and smooth butt joints. Fast Application--available in two forms, slit and unslit. Means faster application. No band ing required. The unslit material slips over gradual bends with ease. Broad Uses--temperature range from --50 to 220F makes possible insulation of most lines commonly used in commercial heating and air conditioning. Flexible and Resilient--designed for excep tional ease of handling. It is so flexible it can be tied in knots--so resilient it springs back to original shape when untied. Resists mechan ical abuse. Softer for winter flexibility and ease of application. 36 Performance characteristics density, Ibs./cu.ft. (avg.)................................ 6.0 thermal conductivity (Btu-in/sq.ft.-hrF) 70F mean temperature..................... 0.27 90F mean temperature.....................0.28 water absorption, % by volume (ASTM D1056).................................................0.5 water vapor transmission, perm-in......................................... less than 0.05 maximum temperature limit continuous use F...........................--50 to 220 fire rating per ASTM D-635.. .Self extinguishing ozone resistance......................................... Good odor...................................... Extremely low level Recommended Thicknesses -- MILO NORMAL SEVERE DESIGN CONDITIONS* PIPE SIZE (Prevention of condensation on indoor piping under a maximum severity of 90 F and 50% R.H. Typical of these conditions: most air conditioned spoces and arid climates.) V" thru 2" IPS Over 2" IPS thru 4." IPS (Prevention of condensation on indoor piping under a maximum severity of 85 F and 70% R.H. Research and field experience suggest indoor conditions anywhere in the U.S. seldom exceed this degree of severity.) V." ID thru 2" IPS Over 2" IPS thru 4" IPS (Prevention of condensation on indoor piping under a maximum severity of 90 F and 80% R.H. Typical of these conditions: indoor areas where excessive moisture is introduced, or poorly ventilated confined areas where the temperature may be depressed below ambient.) %" ID thru 4" IPS O-C flexible Tubing Thickness for Line Temperature 50 F Norn. Nom. Vs" 32 P Nom. 3/#" Nom. Vj" OP Nom. Yj" Nom. Yi" Norn. 3/#" Nom. i/j" Nom. Y," Nom. V," Nom. 3/4" Nom. 34" Nom. %" Nom. 34" Available on Request * Consideration for condemofi'on only. Heat gain of coolant not considered because O-C Flexible Tubing Insulation is used primarily on short run-outs. flexible tubing sizes Iron pipe sizes (IPS) %" to 6" copper tubing (CT) 3/8" O.D.--4Vs" O.D. Wall thickness--inches (nominal) yU", 3/a", Vi", Va" Inside Diameters--inches 3/8" to 6" Length of Sections Standard Carton 6 Feet Made to order 100' to 700' depending on size flexible sheet sizes Standard size--24" x 72" and 30" x 72" (depending on thickness) Sheet thickness--Vfeyi6", ", 3/8", Vi", 1/a", 1" continuous rolls--1/8" x 30" x 150', 3/8" x 30" x 74' Me" x 30" x 150', " x 30" x 54' l/" x 30" x 120', l/2" x 24" x 55' Vi" x 24" x 40' specification compliance HH-l-573b MIL-P-15280-E (GSA-F55) application Insulation can be slipped over pipe or tubing before installation or snapped over piping already connected. All joints are sealed with 0-C 500 adhesive. Paint both edges of slit as porous surfaces of tubing require it for firm bond. This tenacious adhesive forms a strong resilient bond which grows stronger with age. It is water and oil resistant. Flexible tubing insulation can be slipped right over copper tube fittings. Cast bronze fittings or fittings on iron pipe can be "sleeved" with a larger diameter of insulation nested over the covering on the pipe and adhered with 0-C 500 adhesive. 0-C Flexible Tubing In sulation should be protected from the weather on lines running out doors with: Benjamin Foster's BF 57-68; Insul-coustic VIAC 550 or Aklyd-Chlorinated Rubber Paint or Inmont 762 protective coating. 37 Offices of Owens-Corning Fiberglas Corporation Akron, Ohio Albany, New York Albuquerque, N. M. Anchorage, Alaska Atlanta, Georgia 216-867-5770 518-869-0221 505-268-2596 907-272-6425 404-355-6821 Baltimore, Md. Bethlehem, Pa. Billings, Montana Birmingham, Alabama Boise, Idaho Boston, Massachusetts Buffalo, New York 301-727-0234 215-865-0427 406-252-8496 205-871-7369 208-342-9311 617-235-7540 716-832-1410 Charleston, W. Va. Charlotte, N. C. Chicago, Illinois Cincinnati, Ohio Cleveland, Ohio Columbia, S. C. Columbus, Ohio 304-343-7094 704-372-7065 312-583-0100 513-281-1173 216-884-9440 803-252-1384 614-451-6420 Dallas, Texas Dayton, Ohio Denver, Colorado Des Moines, Iowa Detroit, Michigan 214-521-7751 513-293-7922 303-777-6694 515-288-4273 313-547-8000 East Hartford, Conn. El Paso, Texas Evansville, Indiana 203-289-6411 915--533-8208 812-425-5124 Flint, Michigan Fort Wayne, Indiana Fresno, California 313-787-6573 219-483-9552 209-266-4193 Grand Rapids, Michigan 616--452-8788 Greensboro, N. C. 919--273-0528 Greenville, S. C. 803-239-4279 Harrisburg, Pa. 717-761-0430 Honolulu, Hawaii Houston, Texas 808--537-3832 713--869-3351 Indianapolis, Indiana 317--898-1140 Jackson, Mississippi Jacksonville, Florida 601--982-4337 904--786-2838 Kansas City, Missouri Knoxville, Tennessee 816--753-7725 615--584-3421 Lansing, Michigan Little Rock, Arkansas Los Angeles, California Louisville, Kentucky 517-372-4930 501-664-2133 213-685-4381 502-897-3276 Memphis, Tennessee Miami, Florida Milwaukee, Wisconsin Minneapolis, Minnesota Mobile, Alabama 901-362-2010 305-624-2669 414-344-3811 612-545-3791 205-471-5465 Nashville, Tennessee Newark, New Jersey New Orleans, Louisiana New York, New York Norfolk, Virginia 615-298-3646 201-484-2800 504-837-2902 212-759-3810 703-853-9162 Oklahoma City, Okla. Omaha, Nebraska Orlando, Florida 405-528-4468 402--339-2626 305--425-3481 Peoria, Illinois Philadelphia, Pa. Phoenix, Arizona Pittsburgh, Pa. Portland, Oregon Providence, R. I. 309-682-9622 215-688-8650 602-277-6217 412-563-7766 503-292-0781 401-434-7435 Raleigh, N. C. Richmond, Virginia Roanoke, Virginia Rochester, New York Rock Island, Illinois 919-833-7716 703-355-5703 703-362-1177 716-381-0340 309-788-1190 Sacramento, Calif. St. Louis, Missouri Salt Lake City, Utah San Antonio, Texas San Bernardino, Calif. San Diego, California San Francisco, Calif. San Jose, California Savannah, Georgia Scarsdale, New York Seattle, Washington Shreveport, La. Sioux Falls, S. D. Spokane, Washington Syracuse, New York 916-927-1341 314-991-2640 801--487-1361 512--342-9531 714-888-0141 714-276-7711 415-873-7950 408-297-9520 912-233-5980 914-472-3400 206-762-4250 318-865-7511 605-334-3821 509-924-6532 315-455-5601 Tampa, Florida Toledo, Ohio Tulsa, Oklahoma 813-877-7516 419-259-3030 918-627-1220 Washington, D.C. (Gov't.) 202-296-3296 Washington, D.C. (Sales) 301--434-6100 Wichita, Kansas 316--265-2522 Windsor, Conn. 203--524-5987 INTERNATIONAL GENERAL OFFICE: New York, New York 212--759-3810 EXPORT SALES OFFICES: Miami, Florida 305--374-3255 San Francisco, Calif. 415-873-7950 EUROPEAN SALES OFFICES: Brussels, Belgium Milan, Italy Paris, France 02/72.23.26 690.959 265-3301 Wiesbaden, Germany 01-127--84004 OWENS/CORNING FIBERGLAS OWENS-CORNING FIBERGLAS CORP. Industrial and Commercial Construction Materials Division Fiberglas Tower, Toledo, Ohio 43601 Pub. No. 1 .IN-4623-A lifho in U S.A. Augusf, 1970