CHAPTER 21
i; 1958 Guide
through a particular heating unit is equal to the capacity of that unit divided by the capacity of the total radiation circuit multiplied by the total temperature drop of the circuit.
4. Since the temperature of the water supplied to heating units in the series-loop system cannot be regulated, it is advisable to provide dampers in the cabinets con taining finned pipe or baseboard radiation to permit adjustment of the heat delivery by each unit. Valves or adjusting fittings, if used in the water circuit, would affect the performance of the entire loop and would not be a satisfactory means of con trolling the heat output of the units.
Certain disadvantages of the series loop-system are:
1. The difficulty of making suitable provision for adjustment and balancing of the system.
2. The total circulating head required may be excessive. 3. The design of the system may be more difficult than for one-pipe or two-pipe main systems.
Example S: A series loop system is to be designed for the residence used in Exam ples 1 and 2 for two-pipe and one-pipe design. No heat will be supplied to the base ment. The total heat loss equals 45,500 Btu. Baseboard type radiation having a rating of 0.5 Mbh per linear foot at an average temperature of 190 F, is selected as the radiation used. The radiation is constructed with %-in. pipe. A 20 deg design temperature drop will be used. .
Solution: For a 45.5 Mbh load 4.55 gpm must be circulated for a 20 deg tempera ture drop. For a single looped main the measured length equals 140 ft. The ap proximate equivalent length equals 140 X 1.5 or 210 ft. If the 1J- in. pump, Fig. 9, were initially selected, it would develop a 6 ft head at 4.55 gpm delivery. For an available head of 6 ft and an equivalent length of 218 ft (nearest to 210 ft) Table 1 shows that only 3 gpm will circulate through the %-in. main. A larger, and more costly pump may be tried. The 3-in. pump Fig. 9 has 12.7 ft available bead at 4.55 gpm delivery. Using 12 ft available head and 250 ft equivalent length as the nearest available values Table 1 indicates that a flow of 4.3 gpm at a velocity of 2.6 fps will be established through %-in. main. However, because of cost, appearance and temperature drop considerations, this may not be desirable.
If the system is divided into two loops, as shown in Fig. 11, a smaller pump may be used and the system temperature drop decreased.
The 134- in. pump at 6 ft head for 4.55 gpm is again selected for preliminary sizing of piping.
The measured supply main length plus the length of the longest loop circuit is 106 ft. The equivalent length equals 106 X 1.5 or 159 ft. For 6 ft available head and 160 ft equivalent length, Table l indicates that the friction loss would be 3% ft per 100 ft or 450 mi per ft. At this friction loss the supply main would be of 1-in. size for a flow of 7 gpm (which is more than the required 4.5) and the %-in. looped main would deliver 3.7 gpm (more than the required 2.25 gpm). Because the flows are more than required, the system temperature drop would be less than 20 deg. A smaller pump could therefore be used if desired.
The pipe sizes should be recalculated at the design flow rates as follows:
Section
AB BCA
Heat Design Load Flow
Pipe Size
Friction Pipe
Loss
Length
mbh
gpm
in. pt/100 ST
pt
Fittings No. and Type
Equiv. PT
Total Equiv.
ST
m45.5 4.55 i
36 2 elbows
5.0 . 101
2 gate valves 2.5
1 flow valve 50.
1 boiler
7.5
m22.5 2.25 %
70 8 elbows
13.6 99
1 cock
1.7
2 tees @ 50% 13.6
Pbess Drop
ft
1.77
1.5
Total.................................................................................. ............................ 3.27
Hot Water Heating Systems
573
The total system head loss equals 3.27 ft for flow of 4.55 gpm anu-the lyi-ia.
pump is a satisfactory selection..
.... ....
If desired, the actual design temperature drop can be determined. , Because the pump head at 4.55 gpm is greater than 3.27 ft, the flow in the system will increase until pump head and flow equal system pressure drop and flow. Construction of a system curve, as described under centrifugal pumps, shows that for the system'with the pipe size selected and with the lj^-in. pump, equilibrium! will be reached at 6 ft head and 6.2 gpm flow. The actual temperature drop for. design conditions would
then be
X 20 or 14.5 deg, approximately.
..
Combination Systems
Three types of systems have been illustrated namely; one-pipe, two-pipe reversed-retum, and series-loop. Actually the design for a particular buildT ing may be a composite of two or even all three of these types of systems. For example, a two-pipe reversed-retum system of distribution may be used with a number of one-pipe loops in a single building such as an apart ment house, or a two-pipe reversed-retum system may be used with a main riser at each end of a building with a series-loop system used to serve the space on each floor of the building. In any case, it is well to bear in mind the principles of design involved in each particular type of system for that portion of the installation where it is used.
Adjustment of Flow and Capacity
Where the heating elements and piping are properly sized and arranged a hot water system is, to a large extent, self-adjusting. This is so because the mean temperature of the water flowing inside the heating unit is the most important factor in determining its output. If the flow of water is within 5 to 15 percent of the correct value for a given heating unit, the difference in mean temperature will not exceed one or two degrees and, con sequently, the effect on heat output will be negligible. However, the limi tations of commercial pipe sizes and pipe arrangement sometimes result in flow rates considerably different than those required to develop the proper output of the heating units. A means of adjusting the heat output of heat ing elements and branch circuits must be provided in the system to correct these effects.
Adjusting means may be necessary due to the type of system, for example, the two-pipe system using direct return mains. In this system the water flow circuits are hydraulically unbalanced, because the water for the first heating load taken off the main is the first to be returned. As a result, the first heating unit will receive a much' greater flow than is required to de velop its rated output. The flow through the last heating unit can be so low that practically no heat is delivered. The poor distribution of flow in the direct return system can be corrected by the installation of orifices or of adjusting fittings or valves, by means of which the system is balanced after Jt is placed in operation. In some cases, proper flow distribution can also be established by careful pipe size selection. That is, the piping can be sized so that the pressure drop through each piping circuit is the same at the design flow rate.
These.troubles are minimized by the reversed-return system, Fig. 8. In ms system the water for the first heating load taken off the main is the last h H r^urnedj and all circuits are of approximately equal length. - Proper self air C ^ance is therefore easily obtained and the system is inherently in While the reversed-retum piping circuit is much preferred,
some large installations a saving in pipe can be effected by use of a di rect-return system.