Heating Ventilating Air Conditioning Guide 1939
3. The estimated heat emission in Btu per hour of the piping connecting the radiati
and other apparatus to the boiler.
0,1
Estimated Maximum Load: Construed to mean the load stated ;n Btu per hour or the equivalent direct radiation that has been estimated bv the purchaser to be the greatest or maximum load that the boiler will be called upon to carry. (A.S.H.V.E. Standard Code for Rating Steam Heating Solid Fuel Hand-Fired Boilers--:Edition of April, 1932.)
The estimated maximum load is given by8:
4. The estimated increase in the normal load in Btu per hour due to starting up radiation. This percentage of increase is to be based on the sum of Items 1, 2 and 3 and the heating-up factors given in Table 3.
Table 3. Warming-up Allowances-for Low Pressure Steam and Hot Water Heating Boilers*1. b.c
Design Load (Representing Summation op Items 1, 2, and 3,d
Btu per Hour
Equivalent Square Feet of Radiation^
Percentage Capacitt to Add fob Warming Up
Up to 100,000
100,000 to 200,000 200,000 to 600,000 600,000 to 1,200,000
1,200,000 to i,800,000 Above 1,800,000
Up to 420 .. . 420 to 840 . 840 to 2500
2500 to 5000 5000 to 7500
Above 7500
65 60
. 55 50 45 40
.
"This table is taken from the A.S.H.V.E. Code of Minimum Requirements for the Heating and Venti lation of Buildings, except that the second column has been added for convenience in interpreting the design load in terms of equivalent square feet of radiation.
*>See also Time Analysis in Starting Heating Apparatus, by Ralph C. Taggert (A.S.H.V.E1 Transac tions, Vol. 19,-1913, p. 292); Report of A.S.H.V.E. Continuing Committee on Codes for Testing and Rating Steam Heating Solid Fuel Boilers (A.S.H.V.E. Transactions, Vol. 36, 1930, p. 35); Selecting the,Right Size Heating Boiler; by Sabin Crocker {Heating, Piping and Air Conditioning, March, 1932).
oThis table refers to hand-fired, solid fuel boilers. A factor of 20 per cent over design load is adequate when automatically-fired'fuels are used (see Fig. 3).
<1240 Btu per square foot.
Other things to be considered are:
5. Efficiency with hard or soft coal, gas, or oil firing, as the case may be.
.6. Grate area with hand-fired coal, or fuel burning rate with stokers, oil, or gas.
7 Combustion space in the furnace.
8. Type of heat liberation, whether continuous or intermittent, or a combination of
both.
`<
9. Miscellaneous items consisting of draft available, character of attendance,- pos
sibility of future extension, possibility of breakdown and headroom in the boiler room.
Radiation Load
The connected radiation (Item 1) is determined by calculating the heat losses in accordance with data given in Chapters 5, 6 and 7, and dividing by 240 to change to square feet of equivalent radiation as explained in Chapter 14. For hot water, the emission commonly used is 150 Btu per square foot, but the actual emission depends on the temperature of the medium in the heating units and of the surrounding air. , (See Chapter 14.)
Although it is customary to use the actual connected load in equivalent square feet of radiation for selecting the size of boiler, this connected load usually represents a reserve in heating capacity to provide for infiltration in the various spaces of the building to be heated, which reserve, however,
*Loc. Cit. Note 7.
258
Chapter 13. Heating Boilers
use at all places at the same time, or in any one place at all times. Fo"a further discussion of this subject see Chapter 6.
g0t Water Supply Load
When the hot water supply (Item 2) is heated by the building heating
Wnei
__ ,
intrt rnnciHpratinn in sizinff flip hnilpr. The
f5000 . 500
BOILER DATA --
ORATE AREA,SO FT- IB.O
HEATING SURFACE,SQ.FT. 254
WEIGHT, LB.
9160
FUEL CAPACITY. LB.
651
FUEL AVAILABLE, LB. - 414
FUEL OCPTH.IM
10
FUEL--BITUMINOUS 3/4* LUMP ANALYSIS-- VOLATILE MATTER 34.ee/,
FIXED CARBON . ASH
55-44 9.67
SULPHUR MOISTURE BTU PER LB.
2.66 . 3*00
13,655
Fig. 2. Typical Performance Curves for a 36tIn: Cast-Iron Sectional Steam Heating Boiler, Based on the A.S.H.V.E. Code for Rating Steam Heating Solid Fuel Hand-Fired Boilers
allowance to be made will depend on the amount of water heated and its temperature rise. A good approximation is to add 4 sq ft of equivalent radiation for each gallon of water heated per hour through a temperature range of 100 F. For more specific information, see Chapter 43.
Kping Tax (Item 3)
It is common practice to add a flat percentage allowance to the equivalent connected radiation to provide for the heat loss from bare andcovered pipe in the supply and return lines. The use of a flat allowance of 25 per, cent for steam systems and 35 per cent for hot water systems is preferable to ignoring entirely the load due to heat loss from the supply
259