Document mbb0JNnBZDjorxe9kwwv6VnwZ
Inter Office
Per*e*r*t and 0'oatr*' **r
Nov<*.nber 1c. :
Toi Mr. J. A. Hudson, Manager Dearborn Glass Plant
cc R. L. Kuhn M. S, Lechner, M.D. P. B. Paxton R. Smith
Subject: Industrial Hygiene Survey - Asbestos at the Glass Plant Storage
As requested by Mr. R. Smith, Labor Relations, ve analyzed three bulk samples of insulation collected October 12, 19S1 at your storage area in the AAD warehouse, for asbestos. Several pipes in the area have insulation exposed from wear and old age. Two samples were obtained from these pipes. A third sample was collected from a piece of insulation that had fallen to the floor.
The Industrial Hygiene Laboratory performed a screening test for asbestos. All three samples indicated "presumptive" positive results for asbestos. By "presumptive" we mean that this test is not specific for asbestos identi fication. Instead, this screening procedure tests qualitatively for magnesium which is liberated from chrysotile or iron which i6 released from amosite or crocidolite, common types of asbestos. In order to obtain conclusive results, a more exhaustive analysis, 6uch as x-ray diffraction, is required and would entail sending the samples to a consulting laboratory. If you require thi6 analysis, please contact this section. In the interim, the insulation should be treated as if it contains asbestos.
In it6 present form as an insulating cover for pipe, if left undisturbed the exposed insulation does not poBe a substantial risk to those working there. However, since there is a possibility of the insulation crumbling and becoming airborne, ve recommend, if work continues in this area, air monitoring to docu ment any possible contamination. Routinely, most excessive exposures occur during the removal or bagging of insulation where cutting and chipping results in the airborne release of fibers or fiber bundles. If any work is performed on this insulation, such as removal, adequate protection must be supplied including use of corporate-approved respirators and protective clothing and OSHA Regulation 29 CFR 1910.1001 followed. In any oase, our section should be advised.
Additionally, several barrels labeled aB containing PCB contaminated material were located close to column B-19* These barrels are presently unprotected from possible damage from lift truck activity. Dikes to contain any spill should be installed if the barrels are to 6tay for any length of tine. SSECO should be contacted for further information and assistance.
SCF-FORD-3168
8005 0624
DDr*r*TVTr t5V Crtnr,
J. A. Hudson Page Two ' November 18, 1981 If there are further questions, please contact the writer at 73955*
H&{lXcyr~
A. R. Amberg Industrial Hygienist Industrial Hygiene and Toxicology Department Employe Health Services st
8005 0625 PRODUCED BY FORD