Document mbB93r9mjQ5w3ZkM9m17Yq0vO

^1 bulletin 749D (revised november, 1962) 28712 Modern concept based on experienced engineering--conservative design and top-quality construction-assu'e you of highest efficiency, faithful performance, long dependable set vice These qualities have been proved in thousands of installations , . Kewanee has been the recognized leader in steel boilers for neatly a century. Ratings aie conservative--five square feet of heating surface per horsepower-providing adequate reserve capacity. Firing rates aie carefully matched to heating surface, name size and shape are matched to furnace dimensions. Furnace voiume is de iarge furnace tube Provides abundant volume for complete combustion and greater proportion of primary heating surface. Hot flanged furnace tube openings assure maximum permanent strength at junction of furnace tube and tube sheets. Location of tube near bottom of boiler affords maximum protection against low water. 1 f I i signed foi efficient combustion, a no direct heat absorbing sui faces are ample Construction meets 01 exceeds A.S.M E. Boiler Code requirements. These combined features assum operating efficiency of 80%. forced draft operation fJ i^ C All fire tubes in high and low pressure units are set into tube sheets by roller expander ... No tubes welded to tube sheets. Spinner blades in all tubes swirl hot gases against tube surfaces for longer gas travel and maximum heat transfer. Assures ample combustion air for stub stack applications. twe pass design Special blower assemblies available for high altitude. Eliminates refractory baffles that can burn out and short circuit hot gases to stack... Kewanee design avoids wasted fuel, costly shutdown and expensive repairs. I Copyright 1962 by American Radiator and Standard Sanitary Corporation 28713 O T" T" dv TO !arge steam space 0 Combined with abundant, unbroken disengaging area and unusually large water content assures steady water line, dry i- bearn skids steam and ample reserves. Rugged with extra heavy reinforced saddles. They support the unit, distribute weight evenly and facilitate handling. welded shel! Flange quality plate... All materials meet or exceed ASME code insulated steel jacket requirements for strength and durability ... All welded con Factory installed heavy gauge steel jacket of drawband con struction .... High pressure shells are X-rayed and stress relieved. struction with 2" glass or mineral fiber insulation and reinforced cast irar. flue doors catwalk area. t An exclusive Kewanee feature-heavily insulated-precision fit and gasketed for gas tight seal. Hinged to provide quick water heating ccrls Standard Kewanee "Kl" (instantaneous) and "KT" 'tanki coils access to tubes without interference with firing equipment. can be provided for all low pressure units. 28714 3 Three-way air adjustment with inlet louver, discharge damper and primary-secondary pro portioning shutter results in maximum burning efficiency for either fuel under all operating conditions. I Kewanee Scottie Junior Package Units are avail able for light oil, gas, or combination gas-light oil firing. Three sizes of Kewanee Forced DraftBurners are tailored to cover the entire range of boiler capacities. Each Kewanee Forced Draft Burner is custom engineered for the boiler it fires. Together they make an unbeatable team with carefully matched capacity and characteristics. Light oil (No. 2 CS12-48) and either high or low pressure gas may be fired efficiently. Kewanee burners offer long, economical service with minimum maintenance. Forced draft eliminates need for conventional stacks. oil burners Oil burners are of the mechanical pressure atomizing type com plete with motor, fan, oil pump, nozzles, electric ignition, oil filter, combustion controls and relays necessary for automatic operation. Oil piping is ready for field connection to oil supply. gas burners Gas burners are of the multiple-jet flame retention type com plete with motor, fan, gas-electric ignition, automatic and manual gas valves, gas pressure regulators, combustion controls and relays necessary for automatic operation. Gas piping is ready for field connection to gas supply. gas-oil burners Gas-oil combination burners include the features of both the gas burners and oil burners in a single unit. No burner modifi cations to change fuels--just a flip of a switch. 4 28715 PRIMARY SECONDARY PROPORTIONING SHUTTER approvals Units 20,30,40 and 50 feature on-off operation. Combustion air is regulated by a fixed position air inlet damper in addition to an adjustable primary air shutter. An electronic combustion safe guard and a programming timer assure safe operation with pre-purge and post-purge. Units 60, 70 and 85 feature on-off operation with controlled low fire start. Fuel supply and combustion air are regulated at both low fire and high fire to provide smooth starting and top operating efficiency. An electronic combustion safeguard and a program ming timer assure safe operation with pre-purge and post-purge. Units 100, 125 and 150 feature full modulating operation with proved low fire start. Fuel supply and combustion air are regu lated throughout the firing range by a modulating motor con trolled by a boiler-mounted pressure or temperature modulating potentiometer. Enforced low fire start is provided by an interlock on the modulating motor. Combination electronic combustion safeguard and programmer assures safe operation with pre purge, post-purge and proved ignition for both fuels. Entire unit listed by the Underwriters Laboratory iUL). Fuel burning equipment listed by Canadian Standards Association (CSAi; Fire Marshal, State of Massachusetts; City of New York Board of Standards and Appeals; and others maximum safety Dual automatic main gas valves provide added protection against valve leakage. Boiler passages are purged of possible accumu lation of combustible gases both before and after each firing cycle. An electronic flame safeguard continuously monitors combustion. burner firing head Exclusive design of burner firing head provides quiet, stable combustion of gas or oil at all inputs. The recessed ring of gas burner ports permits partial premixing of gas and air at each individual port. Swirling high velocity main air supply assures intimate mixing of fuel and air for clean efficient firing. A separate manual adjustment of primary air permits stable operation under wide variations of gas pressure and other con ditions without objectionable noise or pulsation. control cabinet Master programming and flame safeguard relays, switching relays, necessary motor magnetic starters, numbered terminal strips, indicating lights for major operations and fuel selector switch--all are mounted and wired in a heavy gauge steel, dustproof, control cabinet. Wiring is ready for connection to source of power. 28716 scottie junior high pressure units UNIT NUMBER HX-20 HX-30 HX-40 HX-50 HX-60 HX-70 HX-85 H-100 H-125 H-150 Rating--horse power. -- MBh --steam per hour. 212F --steam radiation Firing rate--oil. 140,000 Btu -- gas Heating surface' Net furnace volume Safety valve capacity--steam per hour Outside surface to cover--uniacketed Approximate dry weight --125 lb. W.P. -- 150 1b. W.P. Vent diameter 20 672 lb. 690 sq. ft. 2800 gph. 6.0 . MBh 840 sq. ft. 99 cu. ft. 16.9 lb. 800 sq. ft. 63 lb. 4100 lb. 4200 in. 10 30 1008 1030 4200 9.0 1260 158 21.4 1200 90 5100 5200 10 40 1344 1380 5600 12.0 1680 215 29.6 1600 107 6300 6400 12 50 1680 1720 7000 15.0 2100 250 32.0 2000 121 7100 7100 12 60 2016 2070 8400 18.0 2520 322 47.9 2400 145 9300 9400 14 70 2352 2410 9800 21.0 2940 358 50.8 2864 158 9800 10000 14 85 2856 2932 11900 25.5 3570 429 62.5 3400 178 12100 13000 16 100 3360 3450 14000 30.0 4200 500 67.7 4000 197 12800 13400 16 125 4200 4310 17500 37.5 5250 625 85.4 5000 222 15800 16100 18 150 5040 5170 21000 45.0 6300 750 94.7 6000 252 18100 18400 18 dimensions, inches A--length overall B--width overall C --boiler--width D-- --length E-- --inside diameter 102 >/2 54 48'/2 85 42 1321/2 54 48'/, 115 42 137 60 541/2 121 48 150 60 541/2 134 48 161 66 60`A 143/2 54 174 66 60`A 154/2 54 158 73 65 139 60 172`A 73 65 153/2 60 177 79 71 158 66 198/2 79 71 179/2 66 F--steam supply height G--smoke outlet height H--water line height J--safety valve height K -- steam supply L--safety valve M --feed water . . N --blow-off 591/2 591/2 651/2 651/2 72`A 72/2 84 84 90/2 90/2 66 66 71`A 711/2 77i/2 77`/2 851/2 85`/2 91 91 51 51 55 55 60/2 60/2 67/2 67`A 71 71 651/2 651/2 74 74 81 81 89/2 89>/2 93/2 94/2 27 33 35 35 36 42 37 43 44 50 20 20 20 20 42 42 51 52 53 60 55 79 83 96 83 88 78 86 88 98 32*/, 321/2 36i/2 36% 40/2 401/2 48 48 51 51 Q--smoke outlet location R--smoke outlet diameter S--steam supply size1 T--feed size ... U--blow-off size. 3`/2 3`/. 4'A 41/2 4`A 4/2 4/2 4`A 5 5 10 10 12 12 14 14 16 16 IS 18 222 2 3 3 4 4 6 6 % % % % % % l'/4 l'/4 1V2 l'/2 1 1 1 1 1 Vi l`/4 2 2 2 2 W--furnace--height X-- --inside diameter Y-- --rearchamber Z--rear door clearance ... .. 291/2 291/2 31 31 34 34 38 38 39 39 18 18 20 20 24 24 26/4 26% 29% 29% 18 18 21 21 24 24 31 31 26 26 39 39 44 44 49 49 AA--base--width BB-- --floor to boiler CC-- --length DD-- --height... EE-- --location. FF--tube replacement space --front GG-- --rear HH --burner front to boiler KK--width--water column to CL of unit 36 36 42 42 48 48 60 60 66 66 16 16 16 16 16 16 18 18 18 18 91/2 1211/2 116 A 135 141 152 150 137 153 173 666 6 6 6 6 6 8 8 11 11 15 15 18 18 18 18 191/2 19/2 41 71 69 82 6 97 83 97 98 119 32 62 59 72 74 85 - 171/2 17`A 16 16 171/2 19 V? 19 19 19 19 311/2 31 A? 34/2 341/2 371/2 37/2 41 41 441/2 44/2 1 2" and 3" threaded outlets. 4" and 6" 300 tb. American Standard flanges. Waterside heating surface on X models. Fireside heating surface on others Manhole on 60 to 150 units. 6 28717 scottie junior low pressure units ..... A Rear EnJ 60150 H P UNIT NUMBER LX-20 LX-30 LX-40 LX-50 LX-60 LX-70 Rating--horsepower -- MBh . . --steam per hr, 212F -- steam radiation --water radiation --net steam radiation Firing rate--oil, 140.000 Btu --gas Heating surface* Net furnace volume Safety valve capacity--steam per hour Outside surface to cover--un/acketed Approximate dry weight Vent diameter dimensions, inches A--length overall B--width overatl C--boiler--width D-- --length .................... E-- --inside diameter F--steam supply height . . . G--smoke outlet height H--water line height J --safety valve height K--steam supply L--safety valve M--feed water each side .... N--return--4 openings--all sizes P--drain. Q--smoke outlet location R--smoke outlet diameter S--steam supply size1 T--feed size .. U--drain size . . . V--heater opening size. W--furnace--height . X-- --inside diameter Y-- --rear chamber Z--rear door clearance AA--base--width BB-- CC-- --floor to boiler --length DO-- --height EE-- --location . FF--tube replacement space --front GG-- --rear HH -- burner front to boiler JJ--burner front to base KK--width--water column to CL of unit . . 20 672 lb. 690 sq. ft. 2800 .sq. ft. 4480 sq. ft. 2300 - gph. 6.0 .. . MBh 840 sq. ft. 99 cu. ft. 16.5 . lb. 672 sq. ft. 61 lb. 3400 in. 10 98 56 48% 83 42 59% 65y2 49`/2 63 27 20 42% 321% 3% 10 4 -- i% 1% 29% 18 18 39 36 16 86% 6 7 39 22 15 4 \h 33% 30 1008 1030 4200 6720 3450 9.0 1260 158 21.7 1008 88 4000 10 128 56 48% 1121/2 42 59% 65% 49% 63 33 20 44% 32% 3% 10 4 1% 1% 29% 18 18 39 36 16 118 6 7 69 44% 15% 3 33% 40 1344 1380 5600 8960 4600 12.0 1680 215 29.9 1344 105 5400 12 132 62 54% 118% 48 70 71% 54 70% 35 20 51% 36% 4% 12 6 1% 1% 30% 20 21 44 42 16 115 6 11 67 48 13% 6 36% 50 1680 1720 7000 11200 5750 15.0 2100 250 32.7 1680 119 6200 12 145 62 54% 131% 48 70 71% 54 70% 35 20 51% 36% 4% 12 6 1% 1% 30% 20 21 44 42 16 130 6 13 80 70 13% 2 36% 60 2016 2070 8400 13440 6900 18.0 2520 322 49.8 2016 163 7500 14 149 69 57 131% 54 79 79% 63 77 36 64 25 42 yp 35% 4% 14 6 l`/4 1% 2 37 26% 24 54 19 137 6 8% 78 17% 3 V? 40% 70 2352 2410 9800 15680 8050 21.0 2940 358 53.3 2352 177 8200 14 162 69 57 142% 54 79 79% 63 77 42 69 33 39% 35% 4% 14 6 1% 1% 2 37 26% 24 54 19 150 6 8% 89 - 19% 3% 40% 1 4" threaded outlets 6" and 8" 150 lb. American Standard flanges. Manhole on No. 60 to 150 units. Waterside heating surface on X models. Fireside heating surface on others. LX-85 85 2856 2932 11900 19040 9800 25.5 3570 429 62.5 2856 186 8800 16 152% 75 64 134 60 84 85% 66 y2 87% 37 62 26 43 39 4% 16 8 1`A 2 2 37% 29% 24 60 18 137 6 11 78 18% 4y. 42 L-100 100 3360 3450 14000 22400 11500 30.0 4200 500 69.1 3360 208 10000 16 169 75 64 150% 60 84 85% 66!/2 87% 43 70 33% 45 41 4% 16 8 1% 2 2 37% 29% 24 60 18 150 6 13% 94 18% 5% 42 L-125 125 4200 4310 17500 28000 14400 37.5 5250 625 83.5 4200 233 12000 18 170 82 69 148 66 90 91 70% 91 44 69 31 47 41 5 18 8 1% 2 2 39 32% 24 -- 66 18 153 8 9% 94 _19 47% L-150 150 5040 5170 21000 33600 17250 45.0 6300 750 93 3 5040 263 13300 18 190% 82 69 168% 66 90 91 70% 93% 50 84 41 47% 41% 5 18 8 1% 2 2 39 32% 24 66 18 173 8 10 114 19 47% 28718 t \ I KEWANEE standard equipment ALL UNITS 1. Boiler Mounted on Steel Skids 2. Gas Tight Front Steel Smokebox with Gasketed Cast Iron Doors 3. Pyrex Observation Port 4. 3" Firetubes with Spinner Blades (Units 20 thru 85) 5. 2V>" Firetubes with Spinner Blades (Units 100 thru 150) 6. Round Smoke Outlet with Quadrant Lock Damper 7. Explosion Relief Door(s) 8. Operating Limit Control 9. Safety High Limit Control 10. Flue Cleaner with Handle 11. Insulated Steel Jacket with Reintorcea Catwalk Area 12. Manhole (Units 60 thru 150) 13. Lifting Loops 14. Listed Standard and Selected Optional Equipment Mounted. Piped, Wired. Ready for Field Connection to Fuel, Water, Steam, and Electricity 15. Factory Firetest 16. Starting Service 1. Safety Valve(s) 2. Steam Gauge and Cock 3. Hand Operated Water Column Trim ALL STEANi UNITS optional equipment 1. Flue Gas Temperature Gauge 2. One Year Service Period 1. Cham Operated Water Column Trim m Lieu of Hand Operated ALL LOW PRESSURE UNP'S 1. Hinged Rear Combustion Chamber Door with Rear Combustion Chamber Refractory (Units 20 thru 50) 2. Wet Back Type Construction (Units 60 thru 150) 3. 16" Dia. Rear Access Opening (Units 60 thru 150) lGW pressure steam units 1. No. 64K Combination Water Column and Low Water Cut-off (Units 20 thru 70) 2. No. 157A or 157D Combination Water Column, Pump Control and Low Water Cut-off (Units 85 thru 150) 3. Angle Drain Valve 1. No. 42K Combination Water Column, Pump Control and Low Water Cut-off (Units 20 thru 70) 2. Kewanee Water Column; Combination Water Feeder, Low Water Cut off and Alarm Switch 3. Second Low Water Cut-off 4. Instantaneous or Tank-Type Hot Water Coils 1. Water Relief Valve(s) 2. Pressure Gauge and Thermometer 3. Low Water Cut-off 4. Angle Drain Valve HOT WATER UNITS 1. Higher than Standard 30 lbs. Water Working Pressure 2. Baffled Return Opening (Kewanee Design) 3. Dip Tube in Supply Opening 4. Instantaneous or Tank-Type Hot Water Coils HIGH PRESSURE STEAM UNITS 1. No. 157A or No. 157D Combination Water Column, Pump Control and Low Water Cut-off 2. Blow-off Valves 3. Injector (Units 125 thru 150) 4. Globe and Check Valves for Boiler Feed Line 5. Rear Combustion Chamber Refractory 6. Hinged Rear Combustion Chamber Door (Units 20 thru 70) 7. Rear Cover Plate (Units 85 thru 150) 8. 16" Dia. Rear Access Opening (Units 85 thru 150) 1. Second Low Water Cut-off 2. Higher than 150 lb. Steam Working Pressure OIL UNITS 20, -30, 40, 50 1. Forced Draft Mechanical Pressure Atomizing Oil Burner 2. 115V, 60Cy., lph. Motor and Controls 3. Two-Stage Oil Pump Direct-Coupled to Burner Fan Motor 4. Dual Oil Nozzles 5. Oil Solenoid Valve (Dual on Units 40, 50) 6. 10,000 V Ignition Transformer for Electric Ignition 7. Photocell Flame Detector 8. "On-Off" Firing Sequence (with Low Fire Start on Units 40, 50) 9. Control Cabinet Mounted on Burner Including: RA890 Protectorelay; T-l Timer for Pre-Purge and Post-Purge Timing; Burner "On-Off" Switch. Indicating Lights (2); Necessary Relays; Numbered Terminal Strip; Engraved Name Plates < 1 . Other than Standard Voltages 2 . High-Low Firing Sequence (Units 40, 50) ` 3 . Fireye Flame Safeguard 4 . Oil Controls for FM * 5 . Oil Controls for FIA " 6 . Alarm Bell G!L UNITS 60, 70, 85 1. Forced Draft Mechanical Pressure Atomizing Oil Burner 2. 230V, 60Cy., lph. Motor (Units 60, 70) 230V, 60Cy., 3ph. Motor (Unit 85) 3. 115V. 60Cy., lph. Control Circuit 4. Two-Stage Oil Pump Assembly with Filter, Gauge. Relief Valve 5. Variable Capacity Oil Nozzle 6. Oil Solenoid Valves 7. 12,000V Ignition Transformer for Electric Ignition 8. Photocell Flame Detector 9. "On-Off Firing Sequence with Low Fire Start 1. Other than Standard Voltages 2. Modulated Firing Sequence 3. High-Low Firing Sequence 4. Ftreye Flame Safeguard 5. Oil Controls for FM 6. Oil Controls for FIA 7. Circuit Breakers 8. Draft Gauge Requires Special Control Cabinet 8 28719 % st andard =quipment ptional equipment C-L JHiTS 60, 70, 85--Continued 10. Two-Position Air Inlet Damper Control 11. Control Cabinet Mounted on Burner Including, RA890 Protectorelny. Control Circuit Transformer; Control Circuit Fuses; T-l Timer for Pre-Purge and Post-Purge Timing; Burner "On-Off" Switch, Air-Flow Safety Switch, Indicating Lights (2), Necessary Relays. Numbered Terminal Strip: Engraved Name Plates 9. Sequencing Draft Controls in Alarm RpII or. ICO, 125, 150 1. Forced Draft Mechanical Pressure Atomizing Oil Burner Z. 230V, 60 Cy , 3ph. Motor 3. 115V, 60 Cy., Iph. Control Circuit 4. Two-Stage Oil Pump Assembly with Filter, Gauge, Relief Valve 5. Variable Capacity Oil Nozzle 6. Oil Solenoid Valve 7. Oil Metering Valve 8. 12,000 V Ignition Transformer for Electric Ignition 9. Lead Sulphide Flame Detector 10. Modulated Firing Sequence with Low Fire Start 11. Modulating Motor to Control Fuel-Air Supply 12. Low Fire Interlock 13. Modulating Potentiometer (Boiler Mounted) 14. Control Cabinet Mounted on Boiler Skid Including: Fireye FJ-2 Flame Safe guard and Programming Relay; Control Circuit Transformer; Control Circuit Fuses; Burner "On-Off" Switch; Air-Flow Safety Switch; Indicating Lights (4), Necessary Relays; Numbered Terminal Strips; Manual Po tentiometer with Manual-Automatic Switch; Engraved Name Plates 1. Other than Standard Voltages 2. Oil Controls for FM 3. Oil Controls for FIA 4. DC Voltmeter 5. Circuit Breakers 6. Draft Gauge 7. Sequencing Draft Controls 8. Alarm Bell GAS UNITS 20, 30, 40, 50 1. Forced Draft Multiple-Jet Flame Retention Type Gas Burner 2. 115V, 60Cy , Iph. Motor and Controls 3. UL Gas Control Group Including: Automatic Diaphragm Gas Valve, Auto matic Solenoid Gas Valve, Gas Pressure Regulator and Gas Cock 4. Gas-Electric Ignition Assembly Including: 6000V Ignition Transformer, Gas Valve, Gas Pressure Regulator and Gas Cock 5. Flame Rod Flame Detector 6. "On-Off" Firing Sequence 7. Control Cabinet Mounted on Burner Including: RA890 Protectorelay; T-l Timer for Pre-Purge and Post-Purge Timing, Air-Flow Safety Switch, Burner "On-Off'1 Switch, Indicating Lights (2); Necessary Relays. Num bered Terminal Strip, Engraved Name Plates 1. Other than Standard Voltages 2. Modulated Firing Sequence (Units 40, 50) 3. High-Low Firing Sequence (Units 40, 50) 4. Fireye Flame Safeguard 5. Gas Controls for Other than Standard Pressures 6. Gas Controls for FM 7. Gas Controls for FIA 8. Gas Controls for Local Utility Requirements 9. Alarm Bell GAS UNITS 60, 70, 35 1. Forced Draft Multiple-Jet Flame Retention Type Gas Burner 2. 230V, 60Cy., Iph. Motor (Units 60, 70), 230V, 60Cy., 3ph. Motor (Unit 85) 3. 115V, 60Cy., Iph. Control Circuit 4. UL Gas Control Group Including: Automatic Motorized Gas Valve, Auto matic Solenoid Gas Valve, Gas Gauge, Gas Pressure Regulator and Gas Cock 1. Other than Standard Voltages 2. Modulated Firing Sequence 3. High-Low Firing Sequence 4. Fireye Flame Safeguard 5. Gas-Electric Ignition Assembly Including: 6000V Ignition Transformer, Gas Valve. Gas Pressure Regulator and Gas Cock 6. Flame Rod Flame Detector 7. "On-Off" Firing Sequence with Low Fire Start 8. Two-Position Air Inlet Damper Control 9. Control Cabinet Mounted on Burner Including: RA890 Protectorelay, T-l Timer for Pre-Purge and Post-Purge Timing: Air-Flow Safety Switch, Burner "On-Off" Switch; Control Circuit Transformer, Control Circuit Fuses; Indicating Lights (2); Necessary Relays. Numbered Terminal Strip; Engraved Name Plates 5. Gas Controls for Other than Standard Pressures 6. Gas Controls for FM 7. Gas Controls for FIA 8. Gas Controls for Local Utility Requirements 9. Circuit Breakers Draft Gauge Sequencing Draft Controls 12. Alarm Bell GAS UNITS 100, 125, 1. Forced Draft Multiple-Jet Flame Retention Type Gas Burner 2. 230V, BOCy., 3ph. Motor 3. 115V, 60Cy., Iph. Control Circuit 4. UL Gas Control Group Including: Automatic Motorized Gas Valve. Automatic Solenoid Gas Valve, Gas Volume Control Valve, Gas Gauge, Gas Pressure Regulator and Gas Cock 5. Gas-Electric Ignition Assembly Including: 6000V Ignition Transformer, Gas Valve, Gas Pressure Regulator and Gas Cock 6. Lead Sulphide Flame Detector 7. Modulated Firing Sequence with Low Fire Start e. Modulating Motor to Control Air-Fuel Supply 9. Low Fire Interlock 10. Modulating Potentiometer (Boiler-Mounted) 11. Control Cabinet Mounted on Boiler Skid Including- Fireye FJ-2 Flame Safeguard and Programming Relay, Air-Flow Safety Switch, Burner "On-Off" Switch, Control Circuit Transformer; Control Circuit Fuses; Indicating Lights (4); Manual Potentiometer with Manual-Automatic Switch; Neces sary Relays, Numbered Terminal Strips: Engraved Name Plates 150 1. 2. 3. 4. 5. 6. 7. 3. ' 9* 10. Other than Standard Voltages Gas Controls for Other than Standard Pressures Gas Controls for FM Gas Controls for FIA Gas Controls for Local Utility Requirements DC Voltmeter Circuit Breakers Draft Gauge Sequencing Draft Controls Alarm Bell COMBINATION GAS-OIL UNITS--ALL SIZES 1. Manual Fuel Changeover Switch '-1. Automatic Fuel Changeover Control 2. Changeover Without Mechanical Adjustments or Changes - Requires Special Control Cabinet On Special Application Only 28720 9 scottie junior package units h.igh. pressure The contractor shall furnish and install ......... Number Kewanee Forced Draft Scottie Junior Package Unit(s) for (oil) (gas) (gas-oil combination) firing. The unites) shall have a rating of . H.P. and shall contain not less than five sq. ft. of heating surface per H.P. and a minimum fur nace volume of................. cu. ft. The heat release shall not exceed 67,500 BTU per cubic foot of combustion space. The fur nace diameter shall be no less than ....... in., the diameter of the vent in. The shell shall be of the scotch type, two pass, horizontal firetube design, ASME Code construction for (125) (150) PSIG Steam. The boiler shall be mounted on steel I-beam skid base with in tegral forced draft burner and burner controls. Unittsi shall be provided with factory installed aluminum finished jacket of 22 ga. steel securely fastened with drawbands. Jacket shall have a 2" thick insulation of lightweight mineral or glass wool material of 3 lbs. density per cu. ft. attached with adhesive. A similar material of 8 lb. density, 2" thick, shall be applied at selected locations for reinforcement including the top splice where it will form a 12" catwalk along the entire length of the boiler. Cover rings shall be provided at all openings. Lifting loops shall be provided so that unit may be handled without damage to the jacket. Fuel burning equipment as follows shall be provided: Note: Select applicable paragraphs {payee 11 thru 13) according to fuel and unit size. All tubes shall be set with a roller expander and beaded at each end. Welded tube ends will not be permitted. The front smoke box shall be of heavy gauge steel welded to the boiler to secure a gas tight fit. The flue doors shall be of cast iron and gasketed to secure a gas tight fit with a minimum number of clamps and shall be lined with insulating refractory securely keyed in place and capable of withstanding a temperature of 1500F. A round flue outlet shall be furnished with a bearing damper with locking quadrant. The rear flue gas chamber shall be of pressure tight construction, lined with insulating castable refractory and provided with an access opening. Boiler trimmings shall consist of the following, mountedand piped: Safety valve(s); steam gauge with siphon and cock; No. 157A or 157D combination water column, pump control and low water cut-off; hand operated water gauge and try cocks assembly; blow-off valves; globe and check valves for boiler feed line. Boiler shall be inspected during construction by an authorized inspector and after completion shall be subjected to a hydrostatic test one and one-half times the working pressure and stamped with all identifying markings and symbols as required by the latest edition of the ASME Boiler Construction Code. low pressure The contractor shall furnish and install . Number Kewanee Forced Draft Scottie Junior Package Unit(s) for (oil) (gas) (gas-oil combination) firing. The unit(s) shall have a rating of H.P. and shall contain not less than five sq. ft. of heating surface per H.P. and a minimum furnace volume of cu. ft. The heat release shall not exceed 67,500 BTU per cubic foot of combustion space. The furnace diameter shall be no less than in., the diameter of the vent in. The shell shall be of the scotch type, two pass, horizontal firetube design, ASME Code construction for (15 PSIG steam) (30 PSIG water). The boiler shall be mounted on steel I-beam skid base with integral forced draft burner and burner controls. An access opening shall be provided to permit entry into the rear combus tion chamber. All tubes shall be set with a roller expander and flared at each end. Welded tube ends will not be permitted. The front smokebox shall be of heavy gauge steel welded to the boiler to secure a gas tight fit. The flue doors shall be of cast iron and gasketed to secure a gas tight fit with a minimum number of clamps. They shall be lined with insulating refractory securely keyed in place and capable of withstanding a temperature of 1500F. A round flue outlet shall be furnished with a bearing damper with locking quadrant. 28721 Boiler trimmings shall consist of the followi ng, mounted and piped: for No. 2 oil with a two-stage oil pump direct connected to the For Steam-Safety vaiveisi: steam gauge with siphon and cock; combination water column and low water cut-off i units 20 thru 70); combination water column, pump control and low water cut-off (units 85 thru 150'; and angle drain valve. blower motor. Burner shall include dual oil atomizing nozzles; oil solenoid valve; 10,000 volt ignition transformer; photocell flame detector; two indicating lights on burner-mounted control cabinet; and all necessary controls for "on-off" type of opera tion. Air control shall be by fixed position air inlet damper and For Hot Water--Relief valves, pressure gauge, thermometer, adjustable primary air shutter. low water cut-off, angle drain valve. Boiler shall be inspected during construction by an authorized inspector and after completion shall be subjected to a 60 lb. hydrostatic test and stamped with all identifying markings and symbols as required by the latest edition of the ASME Boiler Construction Code. UnitCsi shall be provided with factory installed aluminum finished jacket of 22 ga. steel securely fastened with drawbands. Jacket shall have 2" thick insulation of lightweight mineral or glass wool material of 3 lbs. density per cu. ft. attached with adhesive. A similar material of 8 lb. density, 2" thick, shall be applied at FOR 0!! UNITS GO. 70, 35 Oil burner shall be of the mechanical pressure atomizing type for No. 2 oil with a two-stage oil pump assembly with filter, gauge and relief valve. Burner shall include variable-flow oil atomizing nozzle; dual oil solenoid valves; 12,000 volt ignition transformer; photocell flame detector; air-flow safety switch; two indicating lights on burner-mounted control cabinet; and all necessary controls and linkage for "on-off" type of operation with low fire start. Air control shall include two-position regula tion of the air inlet damper. selected locations for reinforcement including the top splice where it will form a 12" catwalk along the entire length of the boiler. Cover rings shall be provided at all openings. Lifting loops shall be FOR OIL UNITS 100, 125, 15C provided so that unit may be handled without damage to the jacket. Oil burner shall be of the mechanical pressure atomizing type Fuel burning equipment as follows shall be provided: Note: Select applicable paragraphs (pages 11 thru 13) according to fuel and unit size. for No. 2 oil with a two-stage oil pump assembly with filter, gauge and relief valve. Burner shall include variable-flow oil atomizing nozzle; oil solenoid valve; oil metering valve; 12,000 volt ignition transformer for electric ignition; lead sulphide flame burner specifications detector; modulating motor with low fire interlock; skid-mounted control cabinet with combination electronic flame safeguard FOR ALL UNITS and programming control, four indicating lights and manual Fuel burning equipment shall be of the forced draft type; factory assembled, wired, mounted, and firetested. Shall bear the Under writers Laboratory label and shall be ready for field connection to power and fuel supply. Equipment to include windbox with refractory ring; forced draft fan with inlet air damper; high limit potentiometer with manual-automatic switch; and all necessary controls and linkage for modulated firing with proved low fire start. Air-fuel ratio shall be regulated through the entire firing range by a modulating motor controlled by a boiler-mounted modulating potentiometer. control; operating control; flame sensing device; and control cabinet containing electronic combustion safeguard, program ming timer for pre-purge and post-purge, burner on-off switch, FOR GAS UNITS 20, SO, .;0, 5C & necessary switching relays, indicating lights for major operations, numbered terminal strips, color-coded wiring, and engraved name plates. Note: The following equipment conforms to JJL requirements. Specify additional controls if FM or FIA insured or subject to special local utility requirements. Gas burner shall be of the multiple-jet flame retention type including a main gas control group consisting of an automatic diaphragm gas valve, automatic solenoid safety gas valve, gas pressure regulator and gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer, automatic gas FOR OIL UNITS 20, 30, 40, 50 valve, gas pressure regulator and gas cock; air-flow safety switch; flame rod flame detector; two indicating lights on Oil burner shall be of the mechanical pressure atomizing type burner-mounted control cabinet; and all necessary controls for 28722 "on-off" type of operation. Air control shall be by a fixed position air inlet damper and adjustable primary air shutter. FOR GAS UNITS SO, 70, 85 Gas burner shall be of the multiple-jet flame retention type including a main gas control group consisting of an automatic slow-opening motorized type gas valve, automatic solenoid safety gas valve, gas pressure regulator, gas gauge and gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock; air-flow safety switch; flame rod flame detector; two indicating lights on burner-mounted control cabinet; and all necessary controls and linkages for "on-off" type of operation with low fire start. Air control shall include two-position regu lation of the air inlet damper. FOR GAS UNITS 100, 125, 150 Gas burner shall be of the multiple-jet flame retention type including a main gas control group consisting of an automatic motorized gas valve, an automatic solenoid safety gas valve, gas volume control valve, gas pressure regulator, gas gauge and gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock; air-flow safety switch; lead sulphide flame de tector; modulating motor with low fire interlock; skid-mounted control cabinet with combination electronic flame safeguard and programming control, four indicating lights and manual potenti ometer with manual-automatic switch; and all necessary controls and linkage for modulated firing with proved low fire start. Airfuel ratio shall be regulated through the entire firing range by a modulating motor controlled by a boiler-mounted modulating potentiometer. FOR COMBINATION GAS-OIL UNITS 20, 30, 40, 50 Gas-oil burner shall consist of a combination multiple-jet flame retention type gas burner and mechanical pressure atomizing oil burner for No. 2 oil including all necessary controls for "onoff" type of operation. Gas controls shall include a main gas control group consisting of an automatic diaphragm type gas valve, automatic solenoid safety gas valve, gas pressure regu lator and gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock; air-flow safety switch; and flame rod flame detector. Oil controls shall include a two-stage oil pump direct connected to the blower motor; dual oil atomizing nozzles; oil solenoid valve; 10,000 volt ignition transformer; and photocell flame detector. An control shall be by a fixed position air inlet damper and adjustable primary air shutter. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector switch in the burner-mounted control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned. FOP, COMBINATION G/-.S-C1L UNITS 63, 70, 25 Gas-oil burner shall consist of a combination multiple-jet flame retention type gas burner and mechanical pressure atomizing oil burner for No. 2 oil including all necessary controls and linkages for "on-off" type of operation with low fire start. Gas controls shall include a main gas control group consisting of an automatic slow-opening motorized type gas valve, an automatic solenoid safety gas valve, gas pressure regulator, gas gauge and gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock; air-flow safety switch; and flame rod flame detector. Oil controls shall include a two-stage oil pump assembly with filter, gauge and relief valve; variable-flow oil atomizing nozzle; dual oil solenoid valves; 12,000 volt ignition transformer; and photo cell flame detector. Air control shall include two-position regula tion of the air inlet damper. Changeover from one fuel to the other shail be accomplished by means of a manual fuel selector switch in the burner-mounted control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned. FOR COMBINATION GAS-OIL UNITS 100, 125, 150 Gas-oil burner shall consist of a combination multiple-jet flame retention type gas burner and mechanical pressure atomizing oil burner for No. 2 oil including all necessary controls and link ages for modulated firing on both fuels with proved low fire start. Gas controls shall include a main gas control group con sisting of an automatic motorized gas valve, an automatic solenoid safety gas valve, gas volume control valve, gas pressure regulator, gas gauge and gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer, gas valve, regula tor and cock. Oil controls shall include a two-stage oil pump assembly with filter, gauge and relief valve; a variable-flow oil atomizing nozzle, oil solenoid valve, and oil metering valve; 12,000 volt ignition transformer. ||l _ 12 28723 Controls for both fuels shall include a lead sulphide flame detec tor; air-flow safety switch; modulating motor with low fire inter lock; skid-mounted control cabinet with combination electronic flame safeguard and programming control, fuel selector switch, four indicating lights and manual potentiometer with manualautomatic switch; and all necessary controls and linkage for mod ulated firing with proved low fire start. Air-fuel ratio shall be regulated through the entire firing range by a modulating motor controlled by a boiler-mounted modulating potentiometer. Change-over from one fuel to the other shall be accomplished by means of a manual fuel selector switch without changing linkage, burner position or mechanical adjustment. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned. All motors shall be for. volts, ... cycle, . . . phase operation. Controls shall be 115 volt, 60 cycle, single phase. Magnetic motoi starters with thermal overload protection and a step-down control circuit transformer shall be provided in the control cabinet when other than 115 volt motors are specified. Fuel burning equipment shall be set and adjusted by a factory authorized representative to burn G.P.H. of No. 2 oil (and) <or) .C.F.H. of BTU cu. ft. inatural> manufactured/-.L.P.; gas having a . .sp.gr. with . . inches W.C. pressure at inlet of burner manual gas cock. Unit efficiency, based on flue gas analysis, shall be not less than 80%. Xote: Speei/y /oi> alidade d over ft. ahnir -vr/ lerel. Owner's representative shall be present to receive instructions in the care and maintenance of the boiler unit at the time the boiler unit is started up by the service.representative. ;Yole: Specify a free service period of not less than ltd days after slnrl-up. KEWANEE t>nmer data a iiVf Unit* Input H Gas Oil L Mbtuh** Gph*** Fuel Control Gas Oil Air Control Programming and Flame Safeguard Control Gas Controlst Standard --U.L. 1000 btu/cf--.6 s.g. Required Inlet Pressure Group Size Motors HP Burner Oil Pump Standard Electrical Characteristics du cycie Voltage Phase Controls Voltage Single Phase 20 840 6 On-Off On-Off Fixed T-l Timer & RA890 6.5" w.c. l'A" 'h i 115 115 30 1260 9 On-Off On-Off Fixed T-l Timer & RA890 6.5" w.c. V/2" i/2 j 115 115 40 1680 12 On-Off Low Fire Start Fixed T-l Timer & RA890 6.5" w.c. V// y2 * 115 1 115 50 2100 15 On-Off Low Fire Start Fixed T-l Timer & RA890 6.5" w.c. 2" `/2 ; 115 1 115 60 2520 18 Low Fire Low Fire Two- Start Start Position T-l Timer & RA890 6.5" w.c. 2" % 14 230 115 70 2940 21 Low Fire Low Fire Two- Start Start Position T-l Timer & RA890 6.5" w.c 2!/z" 74 V4 230 115 85 3570 25.5 Low Fire Low Fire Two- Start Start Position T-l Timer & RA890 6.5" w.c. 21// 1 '/a 230 3 115 100 4200 30 Modu Modu Modu lating lating lating FJ-2 7.0" w.c. 2V2" 1 Vi 230 3 115 125 5250 37.5 Modu Modu Modu lating lating lating FJ-2 7.0" w.c. 3" iy2 v3 230 3 115 150 6300 45 Modu Modu Modu lating lating lating FJ-2 7.0" w.c. 3" i'/2 '/3 230 3 115 'Unit Suffix denotes fuel. -- FG for gas; -- FO for oil; -- FGO for gas-oil combination firing. Example: L-IOO-FGO for low pressure construction, 100 boiler horsepower, gas-oil combination firing. "Based on 1000 btu cf gas at 0.60 sp. gr `Based on 140,000 btu/ga! No 2 oil iControls for other pressures or insurance requirements available JDirect connected to burner motor 28724 x. y `V,, KEWANEE ; with KEWANEE dependable burner--oil, gas or combination gas-oil This Kewanee unit offers you the same long-life dependable service in the higher capacities. Ratings are conservative. Construction meets or exceeds A.S.M.E. Boiler Code requirements. Firing rates are carefully matched to heating surface. Ample furnace volume assures efficient combustion. HIGH ?E.ESSTJTB.S 80 to 672 H.P. 125-150 lb. Steam W.P. Std. Kewanee dependable, automatically controlled, hori zontal rotary gas-oil combination burner handles efficiently all types of gas and the complete range of fuel oils. Each burner is carefully designed for the boiler it fires. X.OW FRSESUSE 2,882,000 to 23,211,000 Btuh. 15 lb. Steam or 30 lb. Water Std. REFERENCE: BULLETIN 149D Experienced sales engineering and service facilities in all principal cities assure each Kewanee owner XXXand prompt, efficient seivice for, complete and continued The owner of a new Kewanee Forced Draft Scottie Jr. Package Unit receives Starting Service which consists of the initial startup of the unit, checking the general operation of the unit making adjiistmeets required by local job conditions, instructing the operator in proper operating and maintenance procedures, and service for a period of 90 days after startup. 28725 # I fox* high or low pressure steam systems * * KEWANEE condensate pumps a,l receivers SIUFpx.or OtX3PJL,EX Packaged or Remote Mounted For 20 to 7S0 Bhp Kewanee Boilers REFERENCE: KEWANEE BOILER FEED DATA SHEET jrr. for domestic Mot water . all .year^^cmai ^ KEWANEE water heating coils r *. i -- Did vo'u k n o^v Amend',-Standard industrial 01v-ssor of*ers all ;nu ail L-ori-jom<\: you "jok io m e coin pan) foi your lota: fequiieinents lor systems of any fin col. inaction or \v:u-i:- .vm! terminal imds. package mute, mud'-cone -i:r cc'ditioners. cinders. boilers o: loot vemiutcrs You'd be sur prised at the convenience You talk to product spec.rdists "'he speak voui language You hmm; one sourre icsponslce to; quality arid pererm anre in equipment designed and manufactured to v;ork toectnnr 1Am e rican-St andard jZEssiaEssnEEEMma SALES OFFICES IN ALL PRINCIPAL CITIES Executive offices: Detroit 32, Michigan In Canada American-Standard Products (Canada) Ltd. Toronto A, Ontario Engineered Products AMERICAN RADIATOR & STANDARD SANITARY CORPORATION i Bullelm No. 7-nO 10M 11-62 SM 28727 Lillio in U.S A