Document mVQa6gYe1MBo3neG9bzBVqDg

HEAT TRANSFER FLUID THERMINOL FR - Lo Temp THERMINOL FR-Lo Temp is a low temperature, fire-resistant heat transfer fluid formulated specifically for practical pumpability at -20" F. THERMINOL FR-Lo Temp permits installation of a non-pressurized system operating with a liquid that has no fire point, and will not support combustion. The recommended operating range of THERMINOL FR-Lo Temp is -20"F. to 400"F. and will not show measurable change after years of exposure at such temperatures. The fluid is non-corrosive with all common metals used in heat transfer system design. Monsanto Company Organic Division Functional Fluids 800 North Lindbergh Blvd. St. Louis, Missouri 63166 0593017 TOWOLDMONOQ37472 TYPICAL PROPERTIES Composition Appearanoe Pour Point Flash Point Flame Point Autolgnltion Temperature Distillation Range: First drop 10# 90# Aoldlty Moisture Chlorinated biphenyls and hydrocarbons Oily, clear, nearly color less liquid -60 F. 280* F. None to boiling Over 1100 F. 432* F. 433* F. 627* F. <0.01 mgKOH/g. <50 PPM Temp. * F. -30 -20 0 40 100 200 210 300 400 Density gm/oc 1.5051** I.4985 1.4870 1.4630 1.4260 1.3665 1.3060 1,2460** Kinematic ViBcoslty cs. ' 658 264 65 <12.2 ' 3.39 1....084 0.459 Specific Heat Btu/lb *F. 0.2;'4 o.2;;6 0.23 0.238 0.26 0...27 0.29 0.31 Thermal Conductivity* Btu/hr-ft-"F 0.0633 0.0632 O.O63 0.0626 0.062 0.061 0.060 0.059 Vapor Pressure mm.Hr. 1.0 .-.- 1.1 2.7 12.6 69 300 * Cal.oulated values '* Extrapolated values 0593018 TOWOLDMONOQ37473