H e a t in g V e n t il a t in g A ir Co n d it io n in g G u id e 1938
112
Table 9. Coefficients of Transmission (U) of Concrete Construction Floors and Ceilings
Coefficients are expressed in Btu per hour per square foot per degree Fahrenheit difference in temperature between the air on the two sides, and are based on still air (no wind) conditions on both sides.
TYPICAL CONSTRUCTION
TYPE OF FLOORING
-Thickness or
Concrete (Inches)
Type of Ceiling
No Ceiling
' .v
in. Plaster Applied Directly to Under Side
of Concrete
,s
Suspended or Furred Metal Lath and Plaster (H In.) Celling
Suspended or Furred Celling of Plaster Board (^ in.) and Plaster (H in.)
Suspended or Furred Celling of Rigid Insulation ( in.) and Plaster (H in.)
Plaster (H in*) on Corkboard (1M in.) Spt in Cement Mortar (>$ in.) on Concrete
4 6 8 10
4 6 8 10
4
e
8 10
4 6 8 10
4 6 8 10
4 6 8 10
Maple or Oak
No.
No Flooring (Concrete
Bare)6
Yellow Pine Flooring* on Wood 81eepers Embedded in Concrete*
Flooring* on YellowPine Sub-Flooring*
on Wood Sleepers
Tile or Terrasio' Flooring on Concrete
Embedded In
Concrete
A B .C D
1 0.65 2 0.59 3 0.53 4 0.49
0.40 0.37 0.35 0.33
0.31 0,30 0.28 0.27
0.61 0.56 0.51 0.47
5 0.59 6 0.54 7 0.50 8 0.45
0.38 0.35 0.33 0.32
0.30 0.28 0.27 0.26
0.56 0,52 0.47 , 0.44
9 0.37 10 0.35 11 0.33 12 0.32
0.28 O*. 26 0.25 0.24
0.23 0.22 0.21 0.21
0.36 0.34 0.32 0.31
13 0.35 14 0.33 15 0.31 16 0.30
0.26 0.25 0.24 0.23
0.22 0.21 0.21 0.20
0.34 0.32 0.30 Q.29
17 0.24 18 0.23 19 0.22 20 0.22
0.20 0.19 0.18 0.18
0.17 0.17 0.16 0.16
0.24 0.23 0.22 0.21
21 0.15
22 0.14 23 -0.14 24 . 0.14,
0.13 0.13 0.12 0.12
0.12 0.12 0.11 0.11
0.14 0.14, 0.14 0.14
K-m. Battleship linoleum Directly on Concrete
E
0.44 0.41 0.38 0.36
0.41 0.38 0.36 0.34
0.29 0.28 0.27 0.25
0.28 0.26 0.25 0.24
0.21 0.20 0.19 0.19
0.14 0.13 0.13 0.13
Computed from factors marked by * in Table 2. *The figures in Column A may be used with sufficient accuracy for concrete floors covered with carpet.
Thickness of yellow pine flooring assumed to be % in. The figures'in Column B may be. used with sufficient accuracy for maple or oak flooring* applied directly over the concrete on wood sleepers. Thickness of maple or oak flooring assumed to be % in. 'Thickness of tile or terrazzo assumed 1 in.
Table 10. Coefficients of Transmission (U) of Concrete Floors on Ground with Various Types of Finish Flooring. < Coefficients are expressed in Btu ter hour ter squarefoot ter degree Fahrenheit difference in temperature between the ground and the air over the floor, and are based on still air (no wind) conditions.
TYPICAL CONSTRUCTION CONCRtta ../FLO 0 MM 6
'cstURp.TR iN/ULATldN fiRTWERN TWO nUMBRANE. Uat&rfr-oofing cetra/e /
;
Thickness
. or Concrete-
No.
(Inches)
No Flooring
(Concrete Bare)
TYPE OF FINISH FLOORING
Yellow Pine Flooring6 on Wood Sleepers Resting on
Concrete
Maple or Oak Flooring* on Yellow Pine Sub*Flooring
on Wood Sleepers Resting on Concrete
Tile or Terrasso* on Concrete
K-in. Battleship Linoleum Directly on Concrete
Type and Thickness or-Insulation
A
B#
C
D
E
i 1 1.07
0.35
0.28
0.98
0.60
2 O.OOv
0.33
0.27
0.84
0.54
8 3 0.79
0.32
0.26
0.74
0.50
! v.
10 4 0.70 ,, . 0.30..
0.25
0.66
0.46
4 5 0.66 . 0.29
8 6 ,0.64;-
0.27
0.24 0.23
0.63 0.52
0.44 0.39
1 In. Rigid Insulation* 1 in. Rigid Insulation* 2 in. Corkboard* 2 in. Corkboard*
' 4 7 0.22 8 8 0.21 4 9 0.12 8 10 0.12
0.16 0.15 0.099 0.096
0.14 0.13 0.093 0.090 -
0.22 0.20 6.12 0.12
0.19 0.18 0.11 0.11
Computed from factors marked by in Table 2. ^Assumed % In. thick. Assumed in. thick. ' ^Assumed 1 in. thick.
The figures for Nos. 5 to 10, Inclusive, include 3-in. cinder concrete placed directly on the ground. The insulation is applied between the cinder concrete and the stone concrete. Usually the insulation is protected on both sides by a waterproof membrane, but this is not considered in the calculations.