' rMAmerican Society of Heating and Ventilating Engineers Guide 193^1
of ventilation and cooling and the additional direct humidificati '
vides for increase in humidity without interfering the cooling effected by the indirect system.
with
the
ventila?lonPr3
In general, it may be stated that direct humidification is most
factory where high humidities are desired but where little cooline satis* tilation or air motion is required. Therefore, the indirect system is V&n^-
applicable where either low or high relative humidities are desired m\2
maximum cooling and ventilation effect. For conditions that require '
unusually large amount of heat to be absorbed by ventilation, toeeth^
with the maintenance of high humidities, it is ofttimes preferable to maF
use of the combination system of indirect and direct humidification
the indirect system alone were used it would mean an unusually lar *
volume of air to be handled, which might interfere, due to air motio^
with production, even though it would result in greater cooling effect If
direct humidification alone were used, no ventilation would be obtained
with consequently higher room temperatures.
, '\
Inasmuch as cooling and humidification requirements in summer are ' much more severe than those in winter, an excess of humidifying and , cooling capacity must be provided to meet extreme conditions and this requires automatic control if the best results are to be obtained. Such applications of humidity control may be considered standard practice today in the United States.
The same type of equipment as used in cotton mills largely is applicable to other textile industries, including rayon manufacture and also is applicable to tobacco factories, paper mills and many other buildings.
Systems of Dehumidification
In many industries it is as important to control the temperature in summer as in winter and, at the same time, the relative humidity must be controlled both in summer and in winter. To accomplish this the air must be.warmed and the humidity must be increased in winter, and the . air must be cooled and the moisture content of the air must be reduced in summer, so that both temperature and humidity indoors may be held at a definite point regardless of outside weather conditions, and regardless of conditions within the plant itself.
The design of air distribution equipment and the external appearance of such equipment is the same as described for systems of humidification. The main differences are found in the internal construction of the dehu midifier, in the use of refrigeration or of heat as required for controlling the water temperature, and in differences in the general methods of control.
Dehumidifiers are of two general types. First, the spray type in which . the water is cooled outside of the spray chamber and then introduced. Second, the type in which the refrigerating coils are placed directly in the spray chamber and in which the water is sprayed over this surface, air coming in contact both with the wetted coils and the spray.
The use of refrigerated surfaces for cooling and dehumidifying air has given way almost entirely to the use of the direct spray of cooled water. One of the principal reasons for this change is the high effectiveness of
462
' - Chatter 29--1Air Conditioning op Buildings
, between the finely divided spray, and the air, which is
BBgttrans i^d substantially to the temperature of the leaving water. Kfifeby . t jjgat transfer reduces greatly the temperature head required KBnsetnc1 . __ . therefore, reduces the size and cost of the refrigerating Rgrefngerauu ,
the spray type of dehumidifier, all the water vapor is condensed
fljgvty.e air to the point of saturation at the temperature corresponding
BP?' t1 j the air leaving the dehumidifier and all free moisture is removed
. 0j baffles or eliminators, in the same manner as in the standard
b^-aser r
spraying of water into the air to remove moisture from
FI; V`eht seem paradoxical, except for the application thereto of easily
IIEtood laws of physics. HiRoth types of dehumidifiers have air-distributing baffles at the inlet
L anfj eliminators at the outlet end. The dehumidifier usually is con-
Brlerably longer than the humidifier and in the spray type there are two Ur mre sets sPrays> some f which may be directed against the air flow.
S - The object is to obtain a coarser spray and, at the same time, a much i&lareer qUantity of cold water per unit of air to be treated, than in the ^humidifier. Heat absorbing capacity as well as surface must be provided
H'in the spray water: The usual allowable rise in spray water temperature ^entering ancj leaving the dehumidifier is from 6 deg. to 10 deg. fahr., and
weIl-designed dehumidifiers of the spray type the final temperature of
t|,e air is substantially identical with the final temperature of the leaving water. This is made possible by the counter-flow effect employed in such
apparatus. The air velocities through the dehumidifier usually are lower than those employed in the humidifier, normal velocities being from
400 to 550 ft. per minute through the cross-sectional area.
Greater care must also be taken to obtain the'elimination of free water than with the humidifier, as an entrainment beyond the eliminator defeats
the purpose of the equipment.
r
Dehumidifier systems usually are provided with two essential control
elements; a dew-point control at the apparatus and a'room control. The
former maintains a uniform temperature of saturated air leaving the
dehumidifier at all times of the year. In summer, in industrial work, this
.is so constructed as to use nearly all return air, thus reducing the refriger
ating load required, while when the wet-bulb temperature outside is
below the dew point required within the room the latter is controlled
by the dew-point thermostat which'brings about a mixture of fresh and
return air as required. The room temperature is controlled independently
at a definite point above the dew-point or saturation temperature either
by a thermostat or by a hygrostat, depending upon whether the more important factor is the temperature or the relative humidity. Frequently
the nature of the process is the governing factor in the selection of control.
For example, if moisture is given off or taken up by the materials in the
process of manufacture, and if the relative humidity is the more important factor, then the hygrostat would be used. The amount of infiltration,
which affects both temperature and humidity, may also be the governing
factor in the selection of control, and the instrument selected would
depend on whether the control of temperature or humidity is the more important. The control operates either with volume dampers controlling