Document kp5ODqmgvjJVEzzaqvwkRZxV
C.A. Dunham Company
Specialties, Heating
The "D" series Dunham
Central Station Heating
Differential Vacuum System is for the heating of office buildings, hotels, apartment
--y/Difr~ensbal~\hcm
The Dunham Differential Vacuum Heating System is
houses, schools and groups of
especially adapted to Central
buildings, etc., of more than
Station Steam Supply. It
3,000 sq. ft. of equivalent di The Dunham Differential Vacuum offers great economy of steam
rect radiation.
Heating Sjratem and individual consumption and very low
The boiler serves as a heat storage from which steam is supplied according to the de
parts of the apparatus used in that system are fully protected by United States Patents Nos.
1,644,114 and 1,706 401, and.Can*
condensate temperatures. Another advantage is com plete circulation even though
mand of the Sub-Atmospheric Pressure Reducing Valve or Temperature Control Valve.
adian Patents Noe. 282,193,282,194 and 282,195. AdditionaJ patents in
the United States. Canada and foreign countries are now pending.
the pressure carried on the distributing mains from the boiler plant is low. This sys
The manually controlled sys
tem therefore is ideal both
tem uses two sub-atmospheric pressure re from the standpoint of the Central Station
ducing valves. The small valve "A" supplies Company and the Consumer.
steam in mild weather, valve " B " in cold
weather. In extreme weather both valves
Exhaust Steam
may be used, if necessary. By shifting the weights of the valve in use, the steam pres sure (vacuum) is controlled in accordance with outside weather conditions.
In the automatically controlled system a Temperature Control Valve "C" is sub stituted for valve " B."
The Dunham Differential Controller starts and stops the pump maintaining, under all steam supply conditions, a greater vacuum in the returns than in the radiators.
This assures complete circulation at all times. In severe weather when steam pressure above atmospheric is required (to maintain the room temperature) the Dif ferential Controller automatically stops the pump until pressure conditions in the system make its operation necessary.
Exhaust steam may be circulated under
vacuum, thus saving steam formerly
wasted. The application of this system re
duces the back pressure to a vacuum and
greater power output will be obtained.
In installations where high steam pres
sures and temperatures are necessary for
process work the building heating system
can be operated more economically by ap
plying the differential principle to it. By
reducing the high steam pressure through
reducing valves the heat input may be con
trolled and the overall economy of the
plant improved.
'
Dunham Differential Vacuum Pump, ``D" Series
The Dunham Differen
tial Vacuum Pump oper
ates on the Jet Exhauster
principle. The Dunham
Exhauster is a special de
sign and has great air and
vapor handling capacity.
Under high pressures
water is supplied from the
receiving tank to the ex
hauster by a motor driven
enclosed impeller type
centrifugal pump of high
efficiency.
The pump exhausts air
and water from return
piping under very high
vacuums and discharges
condensate to the boiler.
It is a completely assem
bled compact unit ready
for piping and wiring con nections.
792
C. A. Dunham Company
Specialties, Heating
Dunham Thermostatic Radiator Trap
Sectional View of Trap Sectional view of Dunham Differential Thermostatic Radiator Trap, sixes, etyles and specifications, see Dunham Hand Book.
All traps used in connection with the Dunham Differential Vacuum Heating System are known as "D" Series. They function uniformly over a wide range of pressures*and temperatures from 25 in. of vacuum to 25 lb. gauge pressure.
Dunham Packless Radiator Valve
Types of Control
The system of control is arranged so
that: A single valve may be controlled by a
single thermostat. A single valve may be controlled by
several thermostats. Several valves may be controlled each
by its own thermostat. Several valves may be controlled each
by several thermostats. The control panel in each case is cen
tralized in the boiler room. Where heating systems are divided into
complete zones (or for systems where only one thermostat is intended to control one valve) Control Panel Type 391 is used.
Either control provides the following
advantages: It centralizes control of the entire steam
supply. It permits either automatic or manual
operation. It gives the attendant the information
he desires regarding temperature condi tions prevailing in various parts of the building, in addition to informing him whether or not the valve is admitting,
steam to the system. Each panel is provided with a red and a
green light for each thermostat and valve. Switches are provided for transferring the
Sectional View, Type 105, Dimham Packlut Radiator Valet with Regulating Platt
For sixes, styles and specifications, see Dunham Hand Book.
Dunham Packless Radiator Valves with Regiilating Plate must be used on all radia-; tors to secure proper balance. Either Type 105 (lever handle) or Type 145 (wheel handle) njay be used.
The valve is made packless by means of the bellows construction. The plate orifice is calibrated to the number of feet of radia tion in each radiator.
Dunham Regulating Plate, Type 192
793
Type 891