SECTION A TRANSFORMER ASKAREL
I. Introduction
II. History of Trade Name Types Table I - The Composition of Transformer Askarels
III. Interchangeability IV. Table II - Official Transformer Askarel Shipping Specifications
V. Ordering Instructions
VI. Stability
VII.
Precautions When Handling Drums, Tankcars and When Opening
Transformers
A. Keep Dry During Handling
Table III -
a
_ temper*
^.
B. Use Ordinary Personal Precautions
C. Precautions on Opening an Askarel Transformer
VIII. Avoid Environmental Pollution fl X, Labeling Askarel Transformers S X. Disposal of Liquid and Solid Wastes OX. Conditioning of New or Recycled Askarel 0 J<. Teardown of Transformers for Repair or Scrap c. S'". Transformer Disposal
IX. Expected Service Life
X. General Characteristics of Transformer Askarel Fluid
XI. Sampling Transformer Askarel Fluid
XII. Evaluation of Askarel Received in New Equipment
XIII.
Dielectric Breakdown Voltage - Moisture Relationship Table IV * Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil
XIV. Turbidity
DSW 357421
STLCOPCB4086196
2
XV. Check Points for Maintaining Askarel Insulation A. General Considerations B. Modern Sealing Procedures C. The Older Sealing Arrangements
XVI.Periodic Fluid Inspection and What checkpoints Mean A. Visual Inspection B. Dielectric Breakdown Voltage
XVII. Inspection Checklist
XVIII.
Contamination in Transformers Table VI - Effect of Common Insulation Materials on Power Factor and Dielectric Strength
Table VII- Effect of Common Insulation Materials on Volume Resistivity of Askarel
XIX. ASTM Method For Investigating The Compatibility of Transformer Insulation and Construction Materials in Askarels
XX. Refining Askarel for Re-Use A. Filtering Through Dry Blotter Paper to Remove Moisture and Extraneous Particles Table VIII - Guide to Rate of Dissolved Water Removal by Filtering Askarel Through a Paper Press
B. Disposal of Solid Wastes
C. D. Earth Treatment for Maximum Improvement of Power Factor and
Volume-Resistivity Table IX - Volume Resistivity
XXI. Cleaning Arced Transformers
XXII. Sampling Askarel
SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS I. Introduction II. Sources of Contamination III. Sealing Switches and Terminal Chambers IV. Askarel Used Under Mild Arcing Conditions V. Maintenance for Askarel Filled Switches VI. Askarel Under Excessive Temperature or Fault Conditions
DSW 357422 STLCOPCB4086197
3-
SECTION C ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO
Types of Analyses Available;
Routine Maintenance Check Complete Analysis Analysis After Earth Refinement
Appendix A - Askarel Stability and Composition of Arc Formed Gas
Appendix B - Solubility of Gas in Transformer Askarels
Appendix C - Effect of Temperature on Dielectric Breakdown Voltage of Askarel
Appendix D - Comparison of the Approximate Viscosity in Saybolt Universal Seconds of Transformer Askarels & Mineral Oil
Appendix E - The Density of Inerteen 54201 KA 7336-9 and Transformer
Pyranol A13B3B-2
Appendix F The rntfi) C
'vti y
c ^ Trwn j to t *n-e r ' * * * cl A13 S3 ft '
Appendix G - Heat Capacity
Appendix H - Coefficient of Expansion
Appendix I - Fire Resistance
Appendix J - Seals, Properties and Procurement
Appendix K - Caution Label
DSW 357423 STLCOPCB4086198
DATE JOB
July 10, 1973
ASKAREL Inspection & Maintenance
Guide. IC/FF-38
____________
r
ASKAREL Inspection & Maintenance Guide
Technical Bulletin IC/FF-38
Section A Transformer Askarel
I. Introduction
.
The term "askarel" as defined by IEEE, ASTM and the National Electrical Code generally describes a broad class of non-flammable synthetic chlori nated hydrocarbon insulating liquids widely used in transformers, reactors and accessory equipment operated at power frequencies. Askarels of various compositional types are in use. (For the general properties and types see ASTM D-2283.) Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride, can contain varying amounts of combustible gases depending upon the askarel type.
This manual describes the operating characteristics of transformer askarel liquid insulation and how it differs from mineral oil. Appropriate handl ing and disposal procedures for both scrap askarel liquid and impregnated solid materials are given in accordance with the guidelines recommended by the American National Standards Institute.
2-3259-0372-6
The information is based on facts gathered by Monsanto over 40 years as a producer of askarel, plus knowledge gained from the experience of trans former manufacturers and users. This guide outlines the very simple main tenance required for. askarel fluid in "modern" transformers and offers suggestions for sealing and maintaining askarel in old units. By following this guide, we believe users will obtain maximum service from askarel in sulation with a reasonable minimum of maintenance. If questions arise re lating to the designing and building of transformers, these should be re ferred to regular transformer suppliers.
DSW 357424
STLCOPCB4086199
-2-
Monsanto gratefully acknowledges the assistance, guidance and the con tributions of certain data by the following:
Edward L. Raab -- General Electric Dr. T. K. Sloat -- Westinghouse Electric
II. History of Trade Name Types "Askarel" is the generic name for the non-combustible liquid insulation and coolant first used by General Electric Company in 1932 for their Pyranol* brand name fire-resistant transformers.'
Other brand names used by electrical manufacturers to designate transformer
askarels used in their products include;
Asbestol** Chlorextol*** Inerteen No-Flamol Saf-T-Kuhl
.
Whatever the trademarked brand, the askarel contains chlorinated biphenyl - - - one of the best liquid insulations developed by science. This inert material is chemically stable, fire-resistant, heat stable, non-corrosive, and has high dielectric strength under the operating conditions encountered in transformers.
In addition to manufacturing Aroclor (chlorinated biphenyl), Monsanto also mixes this dielectric fluid with chlorobenzenes to produce the presently used Inerteen and Pyranol blends described in Table I.
Table I
'
The Composition of Transformer Askarels
____________ Method ASTM D 2283__________
Ifype D
Type E
Type P
Trade Names Inerteen 54201KA Inerteen 54201CM Pyranol A13B3B2
Inerteen 70-30
Inerteen 100-42
Ingredients by wt.)
Aroclor!i>1254, pentachlorobiphenyl 70
Aroclor^1242, trichlorobiphenyl
-
trichlorobenzene
30
tri-tetrachlorobenzene
-
phenoxypropene oxide scavenger 0.18
diepoxide scavenger
-
100
--
'.
- 0.22 0.18 to 0.22
45
mrn
55 0.115 to 0.135
* Trademark of General Electric Company ** Trademark of Carbola Chemical Company, Inc. ***Trademark of Allis-Chalmers
^Registered trademark of Monsanto Company
357425 D
STLCOPCB4086200
-3-
ASTM Method D 2283, titled "Chlorinated Aromatic Hydrocarbons (Askarels) For Transformers", also lists the composition of all transformer askarels used at various times since 1932.
Monsanto manufactures similar transformer askarel fluids in England where the trade name Pyroclor is used.
III.
Interchangeability In general all transformer askarels are interchangeable. However, it is suggested that the transformer manufacturer be consulted prior to mixing in significant proportions or total substitution.
IV. Official Transformer Askarel Shipping Specifications
'
The official shipping specifications for the three modern transformer askarel
fluids are shown in Table II.
V.Ordering Instructions Monsanto's current policy is to sell askarel transformer fluids only to transformer manufacturers. Others interested in these fluids should contact the manufacturers of askarel transformers and not Monsanto. The transformer name plate indicates the transformer maker and usually gives sufficient data to identify the specific askarel fluid used.
VI. Stability Askarel liquid insulation is highly pure, fire-resistant liquid made under close chemical control to meet the exacting specifications as shown in Table II. It does not vary in composition like the commercial range of mineral oils.
Askarel insulation must never be mixed with mineral oil. Over two percent of mineral oil by volume in askarel begins to lower its fire resistance.
Askarel does not deteriorate when exposed to air, heat, hot metal; it does not break down over long use to form conducting or corrosive chemicals; it does not oxidize or sludge. Askarel will remain perfectly stable year after year unless broken down by severe electrical discharge.
DSW 357426
STLCOPCB4086201
CO O P
era
p oH>O
3o 300
3 O H" M
o p. 3 P* O
O H- K H-t 3 ct ct**
ct H 3 <
P O H" "* p
3 3 O 3)
ct
3
oEJ* era
5
MW
0o
3w
m&orxa .
<D
u
a 1
o*
O f*
3X 3 fl>
o CO
o.
h- o
o Er
EJ m
ct-
o 3
a> h-
w3
C+ CD
t* td w 3) < H-CdO pi
tf > ^ o o
MO P O O --- H* ct 3 M . > M P P Cb O O CO P H- 3 H" 3 O 1-3 o Cf ct* ct 3 ct ^ o H3 3* O O > H- fcl H- 3 3 3)
O COO e3ra ca>t 3P2
O-'J W 3 O I CfXct 3 P3 O'* CO VO (D 22 ct-- 3 \d
ora era -a ct 3
to CO P Uit-3 Co
o3 H O3
ovB t)
Sh M PVn
I VO H" VJIVO 3 vn i '----OA era <S
p
*0
CO TJ p o H" *3 H o p ct H" o 3
3) 3 o ro p 3ct H p M
: at 1
R
H" o H" p H
8>3
3 u n o
=d o oO ct O 3O O -a ct
tJOO o OMhS ct- P VJ1 VO CTAVJ1 WH2H I
M* M OOP 3 3> OOVnvnvnVJI W O P
OHO H o o s: h- P ct >R>R>s3,>& ct- 3 vn ro
t) HP VJ1 t-- H-cra P VTl
OM
O VJ13 P3 3 3" P 3
Qj VJ1 O
net
3 p
3
p era X
ct m i+ww ro ro 3
C 3 -0 OAVO P o
ct 3 O ct
0,0 x p w H- 3 p vnvnvn o 0*0 O (--*
U)M VO*
OA ct O o OA
o pU) Ct
3 p X
o
X O 3 H- P ^
cr o
o
o p w 3 ct ct ct ct ct ro o HS
O *0 3 H* O O O O M H- P
M to
H" <D 3, O
33 era
u>u>
vo
ro
oH. Ut on* ro
3
OA
Vjl
H* ct 3
VO COU)-4 o 3 VJ1
o
>a O H* P 5- mooo era
P O C0 H"
3
o
ct 3 ct ct
H"
H* ET
3
OP
33 P
CQ P M
c
d o o ro o ro
O O O -a
3* op X3 H- O P. X Pi
m MP OOP
3 ct O
O 3 P X
o oo M P3
P 3X P
ct 3 vn 3 h-vn P 3 _
O P Oa PO3 3 ?r 3 33 p OOH"
vowh2h i OU1 M o U)
ct 3 U1 O Pm
pj COO 3 ct 3 WOO O ct -O P 'P O M
Ul M OA*
OA Ct M
O vjl
U) OA M ct
o
M o
3 p X
d
3 o *d
ro ro
p
3
3 Pi 3 3 PP M P> OA Cf) o ej* 3* 3 3 Ow P p.
VO M O* O O tO O M 52
ctS OH* P O O HU1 3 ro oh- ro
u>--a O 3 00 vo o ora -P- 3
o
M
OA ia U)
M O M"
P. ct P
,3
ET ct
i^i Art
3 p -P P 3 tOU)
vOh2h i OOO M
COM
to*
o
V5> P oh-
Mawra
OA o
o o Oa oo
i X
-- ^
ct
ct Er p
OO
ctvjl o ro
P 03 MO
CO 00 ct 3 OAto o ct OVJ1 O M
o o' o
ct ro O -p
o vo
ro ct
o
\_n
3 p X
' *3 ro
3 o o m s:
oO
PP
O X 3 MU) 3
O
H" H-VO 3 3 to
OroA
ora
OA
o
tt
3
M
wow o
P 33 o p
o o
ro
vji* o mvn op
CO'< p to H 3 3 X*
M3 p
2 P 1-3 P p
ct <; -PP 3 3 o^X p
3 X 3P
si3 3 3 opp M3 M ro Cf)
3 a> M
MX
co> *-* M tn
OA 3
VO
M
vo
O
M p
3 H
*3 tn o V
^o wro
ct d 3H
p I H 3
ro p era
oo
to d
p
o
>*
U> OW O M
H s: *3
o vn* o mvn
3P H
o
ro
rra
O
m
3
P
p
o
P ca o H 3 ct p
ct <; -PP ^ g
3 Ui H" ct
o^X 3
3H-XP
p X
sro.3pct OOP
3> 3 o ora 3 3* 3O
H" o 3 a
VJl 3
vo p vn p p
3 P- 3 ca
K3 ro p
Mo
*d o m
OI
U) P
oo
-p VO O VO O OA
o vn vn m o
o -a O P
M3 P 3
ct
o
< P3p ^3 X X
p
Jr 3 X
vo
H- 3
DSW 357427
P o hs:
CO 3
3P
1-3 p u
H 3 ct
3 CQ H"
p 33
ro 3ct
o ora 3 3*
OOP s
vo p vn p
3 P3
h ro
<4ho
rd 0 M
p 1 2Q
Mp
STLCOPCB4086202
-5
Footnote 1
.
Askarels of various compositional types are used. Under
arcing conditions the gases product^, while consisting
predominantly of non-combustible hyarogen chloride, can
include varying amounts of combustible gases depending
* upon the askarel type. Insulation systems incorporating
these askarels and cellulosic or other organic materials
may, when arced, produce gaseous mixtures which are moder
ately flammable. As a precaution, ouch gases should be
_ removed from the askarel by bubbling dry nitrogen through
the askarel and flushing the gas sp^ce with dry nitrogen before any work is performed on tho apparatus.
DSW 357428
STLCOPCB4086203
In modern transformers, the only real "enemy" of askarel is contamination by water. Keeping askarel water-free will insure long-time service.
Askarel is heavier than water. If water gets into askarel insulation, only a tiny amount (approximately 125 ppm) dissolves - - the rest floats on top. Askarel is very insoluble in water, only about 200 parts per billion of askarel dissolve in water, at normal temperatures.
VII.
Precautions When Handling Drums, Tankcars, and When Opening Transformers The American Institute of Electrical and Electronic Engineers Guide No. 76, December, 1958 has been revised to give more detailed instructions and guidance "For Acceptance and Maintenance of Transformer Askarel in Equip ment" . This guide is published by the Institute of Electrical & Electronics Engineers, Inc., 345 East 47th Street, New York, New York 10017.
The following are significant precautions: A. Keep Dry During Handling;
In handling, storing, sampling and inspecting askarel - - and in operat ing askarel transformers - - take every precaution to guard the askarel insulation from exposure to high humidity and moisture contamination. Keep 5, 30 or 55 gallon drums of askarel dry; lay stored drums on their sides with the bung at the highest point from floor to keep water off the drum head (which can be sucked into the askarel by the drum "breath ing"). This precaution is not necessary when drums are stored indoors, which is the preferred place for storage.
To avoid leakage the drums used for askarel are of heavy construction. Sixteen gauge metal is used, with special rim seal and bung construc tion. The drums should be drained as completely as possible and then flushed twice with kerosene type solvent to remove all of the askarel. Accumulated liquids and washings should be collected and should be in cinerated at high temperatures, e.g., about 2000F, to destroy the poly chlorinated biphenyls (PCBs). See Section A, VIII.
Tank cars used to transport askarels are in exclusive service and not used interchangeably for other products. All cars must be unloaded through the top (dome fitting) either by pumping or with controlled pressure using dry air or dry nitrogen. If nitrogen has been used for
DSW 357429
1
STLCOPCB4086204
7
unloading it is necessary to advise the shipper so that when the car returns the nitrogen can be replaced with dry air before any one may enter the car. If the car is to be unloaded by pumping it will be necessary to use a dryer on the air intake line to remove moisture.
All tank cars are fitted with steam coils, which are available for unloading under extreme low temperature conditions.
Convenient handling and pumping temperatures and the related approximate viscosity ranges are given in Table III.
Product Pyranol A13B3B-2 Inerteen 54201KA Inerteen 54201CM
Table III
'
Unloading, Handling and Pumping Ternperature C
15-40
20-55
35-75
. ., ' .
'.
9. *
Approximate Viscosity SUS
100-40
100-40
100-40
B. Use Ordinary Personal Precautions: Transformer askarel has been made, handled, and used for over 40 years. It can be handled safely with recommended precautions. If accidentally spilled on hands, no serious skin irritation will occur. However, liquid askarel has a solvent action (similar to paint thinner) on the fats and oils of the skin and prolonged contact may lead to drying and chapping of the skin.
In case of contact, wash the skin with soap and water; remove and dry clean saturated clothing. Clean up spills with rags, sawdust or absor bent clay. Eye contact may result in painful irritation but no perman ent damage to tissues. If askarel gets in the eyes, flush with large amounts of water. As with all eye first aid, refer to a physician. To relieve irritation, physicians have used an opthalmic anesthetic solu tion as well as opthalmic cortisone acetate solution, or caster oil.
DSW 357430
! STLCOPCB4086205
-8-
Infrequent exposure to askarel vapors will not cause ill effects. However, prolonged exposure to high vapor concentrations should be avoided. If hot askarel oust be handled in a closed or confined area, provide the area with mechanical exhaust ventilation - - or - - wear an organic cartridge respirator approved by the U.S. Bureau of Hines.
C. Precautions On Opening an Askarel Transformer: Askarels of various compositional types are used. Under arcing condi tions the gases produced, while consisting of predominantly non combustible hydrogen chloride, can jield varying amounts of combustible gases depending upon the askarel type.
Insulation systems incorporating these askarels and cellulosic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus.
VIII. Avoid Environmental Pollution Transformer askarels contain polychlorinated biphenyls (PCBs) which have been used in the United States and elsewhere over the past 40 years for many industrial and consumer applications. During the past several years evidence has accumulated to indicate that PCBs are widely dispersed throughout the environment and that they can have adverse ecological and toxicological effects.
The United States Government's Interdepartmental Task Force on PCBs, Com72-10419, in their March 20, 1972 report titled, "Polychlorinated Biphenyls and the Environment", recommended restricting PCBs to use in capacitors and transformers.
This report is distributed by the National Technical Information Service, U.S. Department of Commerce, Springfield, Virginia 22151.
DSW 357431
STLCOPCB4086206
-9-
A document titled, "Guidelines for Hand ling and Disposal of Capacitor and Transformer Grade Askarels, Containing Polychlorinated Biphenyls", has been prepared and is available from the American National Standards Institute, Committee C107, 155 East 44th Street, New York, New York 10017.
The scope, objectives and the composition of this committee are:
Scope;
ANSI Committee C107 Procedures and guides for safe use, maintenance and disposal of askarel and askarel-soaked materials used in electrical equipment.
Objectives:
1. Source of technical information and advice for Federal, State,
local authorities and all others concerned.
.
.
2. Encourage development of suitable disposal facilities and keep
all concerned informed.
.
3. Serve as the advisory group for United States participation in international organizations: CEE, IEC, CIGRE.
Composition; Organizations active in or represented by this ANSI committee include: National Electrical Manufacturers Association, Electronic Industries Association, Institute of Electrical and Electronic Engineers, American Society for Testing and Materials; Electric Light and Power Association; Certified Ballast Manufacturers Association; Environ mental Protection Agency; Office of Environmental Affairs; General Services Administration; National Bureau of Standards; Department of the Army; Rural Electrification Administration; Division of Environ mental Research, TVA; American Public Power Association, Water Pollu tion Control Federation; Food and Drug Administration; National Fire Protection Association; Underwriters Laboratories; and several sec tions of the U.S. Department of Interior.
The following are pertinent excerpts taken from the ANSI Guidelines for askarel transformers:
SW 357432
STLCOPCB4086207
- -
-10-
* . I ' ' . i `41 / , \ .
k ..T ;
A Labeling Askarel Transformers "All new askarel transformers should be .labeled;
Caution
The Insulating Liquid in This Transformer Contains Polychlorinated Biphenyls (PCBs). Care Should Be Taken To Prevent Entry Into The Environment. In Case Of Malfunction Or Leaks, Consult The Instruction Manual Or The Manufacturer.
The transformer manufacturer should make similar warning labels available for use on previously installed transformers."
$ JZ.
Disposal of Liquid and Solid Wastes "Disposal of askarel fluid and askarel-soaked materials must be accom plished by means in which there is no significant release of askarel to the environment. At present, disposal is accomplished by carefully controlled high temperature incineration of liquids and soaked software; and by controlled dry land-fill burial of apparatus and other hardware from which askarel has been previously drained and washed.
,
"Present knowledge indicates that proper incineration should involve a suitable biance between dwell time and temperature in the incinerator plus oxygen availability and finally suitable scrubbers to remove HCl formed; e.g., (1) two-second dwell time at approximately 2000F and 37 excess oxygen in stack gas; (2) 1-1% second dwell time at 2700F and 27. excess oxygen in stack gas."
The ANSI Guide lists the locations of facilities that conform with the above requirements. Monsanto has such an incinerator at the W. G. Krummrich Plant, Department A-246, Sauget, Illinois 62201, where arrangements can be made for scrap askarel liquid disposal for a modest fee, currently 3 cents per pound. For disposal of solid scrap a con trolled dry land-fill can be used where permitted by Federal, State and local regulations.
<S Conditioning of New or Recycled Askarel Conditioning of new askarel or recycled askarel requires Fuller's earth treatment. The spent Fuller's earth in cartridges or bags when replaced should be allowed to thoroughly drain over drip pans to remove as much liquid askarel as possible. The cartridge units of steel mesh construc tion should be placed in the "Steel Contaminated with Askarel" container for disposition. Cloth bags filled with Fuller's earth should be placed in the "Scrap Burnable Askarel Waste" container for disposition.
DSW 357433
1
STLCOPCB4086208
-11-
Qtytfl Teardown of Transformers for Repair or Scrap l.-a'I Drain all askarel from the unit either into a holding tank for reuse or into the drum labeled "Scrap Askarel" for disposition, then allow sufficient time for all the askarel to drain from the core and coils.
Jt.b. Remove the core and coil assembly from the transformer and place it on the floor. Sufficient absorbent material should be placed on the floor to absorb any askarel fluid that still drips from the trans former.
3.j. Place all materials in the appropriate salvage containers during the dismantling for later disposition.
*V. -d'l
All used materials, including rags, sawdust, tape, etc., regardless of quantity, should be put into the appropriate containers for dis position.
t /if. Transformer Disposal
The ultimate disposal of an askarel-filled transformer may be accomplished in either of two ways.
I. X* Complete drainage and dismantling with the proper disposal of the askarel liquid and askarel-soaked components as described above.
M'i Disposition of askarel transformers by means of junk or scrap dealers should be avoided unless a transformer is first drained, followed by soaking of the interior with a suitable solvent, such as kerosene. Accumulated liquids and washings are to be disposed of as described earlier.
IX. Expected Service Life Manufacturers indicate that properly designed and installed askarel trans formers are expected to give trouble-free service for at least 30 years. Since their introduction in 1932, the manufacturers report finding the over-all failure rate to be less than 0.57. for all units under test and service conditions. The Edison Electric Institute's report (1956-1958) on their member utilities publishes the failure rate for askarel transformers as 0.13 per hundred banks per year.
Mr. Frank M. Clark, who invented transformer askarels at the General Electric Company in the early 1930s, made the highly pertiient comment based on his many years of experience with G.E. Pyranol (askarel type) transformers that--
DSW 357434
STLCOPCB4086209
12
"The Important thing is to keep them dry -- otherwise leave them
alone".
.
These words of wisdom became especially applicable in more recent years when welding shut rather than gasketing became the main method of sealing askarel transformers. These units are sold with the understanding that the liquid is in a normally hermetically closed system.
X. General Characteristics of Transformer Askarel Fluid Appreciation of the following characteristics, as given in the IEEE Guide, leads to understanding the reasons for selecting dielectric breakdown volt age and moisture as the prime practical tests to judge the quality of trans former askarel fluid. Also, due to these characteristics the power factor of transformer askarel will be normally much higher than the corresponding values for mineral oil.
In comparison to mineral insulating oil, askarel is a relatively polar ma terial; i.e., its molecules are dipoles, free to rotate around their axes and responsive to orientation by electrical forces. Askarel also exhibits a much higher dielectric constant and capacitance than insulating oil, and these differences must be kept in mind when interpreting electrical test data.
Because it is relatively polar, and possesses high solvency power, askarel is much more electrically sensitive than mineral oil to traces of extraneous soluble polar materials, and consequently the choice of constructional ma terials destined for use in askarel is very critical. This sensitivity is reflected in the power factor and resistivity (specific resistance) of the askarel.
It is important to note that, with the exception of water, the dielectric breakdown voltage of askarel is not generally adversely affected by many of the soluble polar materials to which its power factor and resistivity (spe cific resistance) are so sensitive. In fact, the dielectric breakdown volt age of askarel is somewhat greater than that of insulating oil. Therefore, the values assigned these dielectric fluids in newly supplied transformers are 30 KV min. and 26 KV min., respectively.
s&.i
DSW 357435 STLCOPCB4086210
_ ' -13- ' ` ` ' ' ' ' ' `
As with insulating oil, askarel must be kept dry. It can pick up moisture from exposure to humid atmosphere. Under similar conditions of exposure, askarel can pick up nearly twice as much moisture when measured on a parts per million weight basis.
XI. Sampling Transformer Askarel Fluid The following precautions about sampling are quoted from the IEEE Guide.
"Representative samples, whether of the complete contents or only parts thereof, are extremely important from the standpoint of evaluation of the quality of the product sampled. Obviously careless sampling procedure or contamination in the sampling equipment will result in a sample that is not truly representative. This generally leads to erroneous conclusions concern ing quality and incurs loss of time, effort, and expense involved in securing,, transporting, and testing the sample. It is strongly recommended that all of the procedures and precautions outlined in the latest revision of ASTM D 923 (Sampling Electrical Insulating Liquids) be followed.
"Because of the high specific gravity (relative density) of askarel (greater than 1), water and some other impurities are most likely to be found at or near the surface. The top sample, therefore, is considered to represent the worst condition."
XII. Evaluation of Askarel Received in New Equipment Some users of askarel equipment find it desirable to make "as received tests" on all equipment. It is quite common to use the dielectric breakdown voltage test and visual appearance as the most significant tests. If suitable equip ment and trained personnel are available additional information may be obtained from the power factor, color, and moisture content tests.
In sampling askarel contained in apparatus extreme care must be exercised in order to obtain a representative sample. ASTM Method D 923 should be followed.
New equipment with askarel exhibiting the following characteristics is con sidered acceptable:
OS\N 357436
r
STLCOPCB4086211
-14-
Dielectric Breakdown Voltage
Color Condition - Visual Water Content Power Factor at 25C
30 KV min. 300 max. (Straw color) Clear
35 ppm max. *
ASTM Methods
D 877 D 2129 D 1702 D 1533 D 924,
*The power factor of askarel taken from new transformers, reactors and accessory equipment can. reflect the presence of moisture, dissolved polar compounds, or other contami nants and may vary with the type of equipment from which the sample was taken due to the different ratios of liquidto-solid insulation and to the high solvency power of the askarel. Given an acceptable water content and dielectric breakdown voltage of the askarel as indicated above, a high power factor seldom impairs the serviceability of the askarel within rather broad limits and is indicative of the degree of extraneous soluble polar materials pres ent .
Recognizing the possibility of a wide range of power fac tors being recorded for askarel in new equipment, it is difficult to establish a single limit which would be ac ceptable to both suppliers and users for all applications. However, as a broad guide, power factors up to about 10% at 25C and 60 cycles per second (hertz) do not in general indicate any abnormal contamination providing that the other criteria (water content, dielectric breakdown volt age, etc.) are met. Much higher power factors may indi cate excessive contamination or the misapplication of the solid materials used in manufacture in contact with the askarel and should be investigated.
XIII. Dielectric Breakdown Voltage - Moisture Relationship The dielectric breakdown voltage of askarel is highly sensitive to excess moisture; not sensitive to ordinary dissolved polar materials. While the dielectric breakdown voltage can also be lowered by severe arcing, askarel turns noticeably black or has particles of sooty carbon floating in it if arcing has occurred. Then the transformer should be repaired and the askarel replaced.
If the dielectric breakdown voltage is checked periodically and decreases significantly - - this indicates moisture pick-up, arcing, or both. When the dielectric breakdown voltage has dropped to 26 KV or less, an analysis for water is necessary. If water is found in excess of 40 ppm at room temperature, its source should be located and corrections made.
DSW 357437
STLCOPCB4086212
15-
When the moisture content approaches 125 ppm (saturation level at room tem perature) , the dielectric breakdown voltage of askarel drops below the value required for efficient insulating. The moisture content should not be allowed to rise over 70 ppm, sampled at operating temperature. If the moisture con tent is found to be in a satisfactory range and the dielectric breakdown voltage is low, the transformer manufacturer should be consulted.
Table IV shows the relationship of dielectric breakdown voltage vs. moisture and Table V indicates the approximate water solubility limits in askarel and mineral oil.
TABLE IV
' Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel
and Mineral Oil
Breakdown Voltage (ASTM)
^a^er Content (PPM)
Askarel
Mineral Oil
. OM OOOOO-OtrfOOO
TO KV
4o
38 10
50 KV 39
39
26 22
5
TABLE V
APPROXIMATE SOLUBILITY OF WATER IN TRANSFORMER
ASKAREL AND MINERAL OIL
c.
--30 --20 --10
0 10 20 30 40
Temperature
*F.
--22 --4
14 32 50 68 86 104
Amount of Water (PPM) Dissolved
Askarel
Mineral Oil
88 16 10 28 13 . 41 20 65 33 94 . 58 128 85 170 130
XIV. Turbidity . . .may be the visual sign of undissolved water, or may indicate dirt. (Joudiness may also result from cold precipitation of tin tetraphenyl "scavenger" that was used in the earlier Pyranol transformers. This scaven ger begins to come out of solution around 15F above zero. To redissolve it requires heating to 150-200F and agitation.
DSW 357438
STLCOPCB4086213
-16-
.
High dielectric breakdown voltage will quickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askarel is still excellent. However, if the dielectric strength is below 26 KV, mois ture should be determined, using the Karl Fischer method (ASTM D1533-60).
The dielectric breakdown voltage test for askarel serves primarily as an indicator for moisture. It is by far the most important maintenance test for transformer askarel.
XV. Check Points for Maintaining Askarel Insulation A. General Considerations: Modern askarel transformers with welded construction or silicone or Viton* gaskets (hand hole-cover, switch and terminal compartment covers) and with properly constructed bushings require little or no maintenance. With properly constructed transformers, annual or semi-annual visual inspection and dielectric breakdown voltage test of the askarel fluid should suffice for routine maintenance checking over many years of serv ice.
However, many askarel units were installed in the early 1930s - - before the development of some of the better modern gasketing materials and before improved designs were developed for sealing out moisture. Such early units should be, and can be, modernized. Leaky or deteriorated gaskets should be replaced. If the askarel has become contaminated, it should be reconditioned. At the same time, a general clean-up of the unit and possible refinishing may be desirable.
If it is not convenient to take an old transformer out of service for general repairs, leaky gaskets can be sealed temporarily by painting over the leaky area with epoxy cement.
A survey of users indicates a good number of early-built askarel trans formers (over 20 years old) are kept in continuous service in critical installations by the following steps (instead of modernization).
Trademark of E. I. DuPont DeNemours & Company, Inc.
DSW 357439
STLCOPCB4086214
17
The operating units are equipped with compound pressure gauges for read ing pressure above and below atmospheric. Positive pressure is maintained on the shell by introducing nitrogen at 2 to 3 pounds above atmospheric. Regular workmen in the area daily record the temperature and pressure. If a sudden pressure drop is noted more nitrogen is introduced and the gaskets are checked for leaks with soap solution. Leaks are sealed by applying epoxy cement.
B. Modern Sealing Procedures: Transformer purchasers should specify the following modern techniques for sealing: 1. Welding Construction; Covers, radiator connections, switch and terminal housings, instrument connections, etc. should be welded.
2. Bushing Connections: A number of bushings have been developed to obtain a proper seal for the electrical connection through the tank wall. They are classified as follows:
A) Welded Type - (Bushing flange welded to tank wall)
\ rSe', Cast resin bushing with a molded seal to the bushing stud and external stainless steel or copper flanges.
Rolled flange bushing with the metal to porcelain seal at the cap and flange made by being rolled into grooves in the porcelain over silicone rubber rings. The seal between the cap and stud is made by welding.
Porcelain or glass bushings with metal to glass or metal to porcelain seals.
$ Z) Bolted Type - (Bolted to tank wall)
i ,/tf. Cast resin bushings with either cast or metal flanges con taining recessed gasket grooves.
Porcelain or glass bushings with flanges containing recessed grooves or gasket stop.
The gaskets may be either of rectangular or circular cross-section, usu ally 1/4 inch thick. Bushings with recessed grooves are suitable to use with cork, cork-nitrile rubber combinations or nitrile rubber as well as gasket materials such as silicone or Viton.
DSW 357440
uj
STLCOPCB4086215
-18
3. Small Size Connections: When not possible to weld, small size connection seals should be made with Flexitallic* stainless steel Tings. The surfaces must be machined and parallel. The filler between the steel laminations of the Flexitallic ring should be either silicone or Viton.
4. Gaskets for Hand-Hole Covers: Modern design specifies silicone gaskets. Such gaskets must be retained in a groove. The groove preferably is machined into the flange or cover. However, it can also be formed by welding concentric steel strips to the flange or the cover. Generally the gaskets should be 5/16 to 1/2 in. thick for covers, depending on the depth of the groove or stop. A rectangular cross-section is usually used.
'
The silicone material should be Dow-Corning No. 50 Silastic** or equivalent. This is a low compression set material. For best sealing 20-257. compression is recommended, with ample clearance in the groove or stop to allow for this compression.
No cement is required. With reasonable care the gasket is re movable without damage and is reuseable.
Silastic 50 is slightly swelled by askarel which contributes to the tightness of the seal. It is not deteriorated by askarel fluid or vapors. It resists weathering and it is thermally stable and flexible at all operating temperatures. It is an . excellent moisture barrier.
NOTE: Dow-Corning, Midland, Michigan will supply a list of Silastic 50 gasket fabricators to all transformer manu facturers or users. They will also furnish technical data. See Appendix K: Seals, Properties and Procurements.
C. The Older Sealing Arrangements: The older type gaskets consist of either cork or cork-nitrile rubber combinations or straight nitrile rubber.
* Trademark of Flexitallic Gasket Company ** Trademark of Dow Corning
DSW 357441
STLCOPCB4086216
19
1. Cork-Nitrile Combinations; Covers for the main tank, hand-holes, switch and terminal chambers, relief diaphrams, etc., are held in place by studs welded to the flange or by bolts. The gaskets are cut w'ith openings and placed over the bolts. Often Shellac (Westinghouse Style No. 1150419, or General Electric Company's Glyptal* 1276) is used to cement the cork to the flanges.
The following is recommended for sealing with the cork - - nitrile rubber combination:
Use Armstrong NC-757 cork-nitrile material or equivalent. The gasket can be cut from a single sheet or by scarfing strips of the material. A convenient method for joining strips is to make a Keystone Type joint. For this purpose, Westinghouse, Sharon, Pennsylvania, offers their gasket cutter Style No. 328 B614 GOl, (about $15).
The joints - and also the gasket - should be cemented to the flange, using one of the above cements. Excess cement should not be allowed to reach the interior of the transformer.
After installation and bolting, the outside edge of the gasket should be coated thoroughly with epoxy cement to increase weather resistance.
This epoxy cement is a paste to which a curing catalyst is added immediately before use. Typical are;
a. Epoxy Patch Kit #1-C Hysol Corporation, Olean, New York
b. Scotchcast** Resin #4 Minnesota Mining & Manufacturing Company St. Paul, Minnesota
c. Adhesive A-l and Activator Type B Armstrong Products Company Argonne Road, Warsaw, Indiana
d. Adhesive 9860-1, Synthetics Organic Company, Cleveland, Ohio, used with activator diethylene triamine (Carbide and Carbon Chemical Company)
* Trademark of General Electric Company ** Trademark of Minnesota Mining & Manufacturing Company
DSW 357442
STLCOPCB4086217
-20-
2. Straight Nitrile Rubber: When straight nitrile rubber was originally used, invariably the gasket was recessed in a groove. This was to prevent gasket flow and to protect the material against excessive compression. Although this type seal was not cemented, the nitrile rubber gasket is not reuseable. Since grooves or stops have already been provided for the nitrile rubber seal. Silastic 50 can be easily substituted and is recom mended. This conforms with modern practice.
XVI. Periodic Fluid Inspection and What Checkpoints Mean On a regular schedule - - at six, nine, or twelve-month intervals - - make a simple visual inspection of your askarel insulation and run a dielectric breakdown voltage check. A. Visual Inspection; Askarel is a clear, faint-yellow liquid. After long-term use this color may gradually intensify to light brown. The fluid should remain clear and free from turbidity or cloudiness. Any color change - - such as to a green, red or blue cast - - indicates extraction of impurities (color materials) from the solid insulation. If a distinct foreign color pick-up is noted, check the complete range of electrical characteristics and notify the transformer maker. Black ening of the askarel may indicate an arcing condition. Other color changes alone are not danger signals since the dielectric breakdown voltage is not likely to be impaired. B. Dielectric Breakdown Voltage If the dielectric breakdown voltage has decreased significantly from the last inspection, or if it has gradually decreased below 26 KV range (at 25C) - - RUN A CHECK FOR MOISTURE. Use ASTM D1533 (Karl Fischer Method). The dielectric breakdown voltage of askarel is the major indicator to the operating efficiency of your liquid insulation. Besides the visual inspection tests, dielectric breakdown voltage is the only test necessary to run on a routine basis. Well-sealed askarel transformers have service records of 25 to 30 years on the original askarel.
DSW 357443
STLCOPCB4086218
-21-
XVII. Inspection Checklist f{ If askarel is clear - even though darkened to light brown, has no sediment or turbidity, has dielectric breakdown voltage over 26 KV - give it the inspection "OK".
^ If askarel is clear, but has foreign color of blue, green, red. . . it is "extracting color" from internal materials. This is not, of itself, an operating hazard when the dielectric breakdown voltage stays over 26 KV and moisture remains low. However, this rare occurrence calls for checking into the condition of the interior construction and consulting the transformer maker. However, when sampling the fluid care should be taken to avoid getting color into the askarel from paint that may be inside or outside of the sample valve.
C fa.
If the moisture content is found to be above 70 ppm at operating tempera ture, then sampling should be done at more frequent intervals to establish a possible, trend, particularly on outdoor installations.
0 /. If askarel is clear, but dielectric breakdown voltage drops to 22 or lower KV, and moisture rises over 80 ppm when sampled at operating tem perature. . .the askarel is ready for simple "refining". If the moisture is near the saturation level (about 125 ppm at room temperature) a thorough inspection should be made for water droplets in the transformer tank, and even for "globules" of water floating on the askarel surface. If found, the transformer manufacturer should be consulted for recondi tioning both the transformer and the fluid.
If askarel is dark brown to black, if black particles of carbon are seen, and dielectric strength is low. . .the askarel has been broken down by arcing. It cannot be refined and should be removed and incinerated under proper conditions. (See ANSI Committee C 107 report on Use and Disposal of Askarel and Askarel-Soaked Materials. 155 East 44th Street, New York, New York 10017).
If any of these four simple inspection tests appear out of the ordinary or the relationship between appearance and test values is abnormal, con tact your transformer supplier for a complete analysis.
Whenever a sample is to be shipped to Monsanto, please follow the direc tions shown under: "SAMPLING ASKAREL".
DSW 357444
STLCOPCB4086219
22-
XVIII. Contamination in Transformers Moisture, particulate matter and arced decomposition products are known to be serious contaminating influences on transformer askarel.
The power factor test normally used for the detection of contamination in mineral oil filled transformers is of little use for this purpose in askarel filled transformers, due to the extreme effect of extraneous soluble polar materials. This increase in power factor as illustrated in TableVI has no adverse effect on dielectric breakdown voltage.
TABLE VI
EFFECT OF COMMON INSULATION MATERIALS ON POWER FACTOR AND DIELECTRIC STRENGTH
(HEAT AGED 96 HOURS IN ASKAREL AT 100C.)
<V . .
Material Immersed
None (control)....................................... Black varnished cloth................. ............ Copper................................................... . Pressboard........................... ................. Manila paper......................................... . Phenol formaldehyde resins.................. ... Shellac................................................... . Iron....................................................... Synthetic rubber.......... ..........................
.
Askarel After Exposure
Power Factor, Percent at 60 eye., 100C.
Dielectric Strength
25C.
35 KV 42 40 37 39 1.6 41 36
* 39 39 .
i.!
Similarly, trace contaminants from commonly used construction materials can lower the volume-resistivity of askarel, without affecting its di electric breakdown voltage. This is shown in Table VII.
TABLE VII
EFFECT OF COMMON INSULATION MATERIALS ON VOLUME . RESISTIVITY OF ASKAREL
Sample
1. New askarel before heat aging.......... .. 2. New askarel after heat aging 96 hours at 100C. 3. After heat aging with 1 sq. inch specimens of:
8. Phenolic resin tap changer material............. .
b. Paper............................................................. .
c. Grade A press board (tan)........................... . d. Grade A press board (gray)....................... e. Grade A press board, laminated strip...........
f. Cotton wrapping...........................................
g. Glyptal 1276 cement, cured 48 hrs. at 110C.
Volume Resistivity x 10' ohm-cm (at 100C., 500 Volts DC., 0,1* gap)
2,000 1,900
1.200 750
500 500 400
300 100
-
DSW 357445
STLCOPCB4086220
23
While trace contamination easily lowers volume resistivity from high levels, it is important to note that heavy contamination (as when arced) does not lower the resistivity below the order of 109 ohm-cm. at 100C.
The different behavior of askarel vs. mineral oil in these respects can be summarized as follows;
High power factor and low volume resistivity in transformer mineral oils are commonly regarded as "danger signals" that the oil has deteriorated and broken down chemically or ex cessive moisture is present.
This is NOT TRUE of askarel liquid insulation unless the di electric breakdown voltage is low or the moisture content is high.
Manufacturers of askarel type transformers point out that it is quite well known that askarel transformers with initial power factor of the askarel fluid in excess of 507. at room temperature and 60 Hz are giving satisfactory service life. However, there needs to be assurance that both dielectric breakdown voltage and moisture are at satisfactory lev els and do not show adverse trends.
XIX.
ASTM Method For Investigating The Compatibility of Transformer Insulation
and Construction Materials in Askarels 9
This methodzuses the change of electrical and/or chemical characteristics
of transformer askarel resulting from its controlled exposure to^insula-
tion and construction materials, in order to evaluate their immediate
major "contamination" effect on the askarel fluid. Delayed or long time
contamination effects may not be detected.
The method also utilizes various physical tests on the insulation and construction materials after controlled exposure to the askarel to de termine the compatibility of these materials with transformer askarel.
Properly proportioned specimens of the insulation or structural materials are immersed in refined askarel for 168 hours at 10(H1C in a forced draft oven. Changes in electrical and chemical properties of the trans former askarel are compared against a control sample of the askarel treated in the same manner, in absence of the test specimens.
2 In process of publication by ASTM, as of this writing.
DSW 357446
STLCOPCB4086221
-24-
Dissipation factor (ASTM D 924) change is one of the criteria used. The askarel fluid is refined by absorbtive treatment to a dissipation factor level of 0.05 max. at 100C and 60 Hz and 0.01 max. at 25C and 60 Hz. Corresponding values of the askarel fluid after heating 168 hours at 100C in absence of a test specimen are 0.075 and 0.02 respectively. The maxi mum dissipation factor levels suggested for the askarel after heating in presence of the test specimen are 0.20 at 100C and 60 Hz and 0.04 at 25C and 60 Hz.
XX. Refining Askarel for Re-Use
s
A. Filtering Through Dry Blotter Paper to Remove Moisture and Extraneous Particles:
Most operators prefer portable refining apparatus, such as a plate
press fitted with a dolly, available from Sparkler, Mundelein,
Illinois or General Electric Company, Pittsfield, Massachusetts; or
the earthen cartridge filter type available from Industrial Filter
Corporation, Lebanon, Indiana. Filter paper liners for the plate
press are available from Carl Schleicher and Schuell Company, Keane,
New Hampshire and manufacturers of filter presses listed above.
The filter paper must be dried immediately before use. For best re sults, spread the paper for maximum surface exposure in a hot air circulating oven and heat it for 4 to 6 hours at 110C.
Circulate the askarel hot (but not over 40C) through the filter fitted with the dry paper liners.
After filtration the dielectric breakdown voltage of the askarel should be 35 KV minimum. 1. Precautions: Filtering should not be done when the relative
humidity exceeds 757,,.
trademark of E. I. DuPont DeNemours & Company, Inc.
Any flexible hoses and gaskets on the refining equipment should
be lined with or made of materials that will not be softened by
contact with askarel fluid. (Materials lined with Silicone, Viton
or Teflon*or flexible metal materials are suitable.)
TABLE VIII GUIDE TO RATE OF DISSOLVED WATER REMOVAL BY FILTERING ASKAREL THROUGH A PAPER PRESS
Passes Through Paper Press
0 1 2 3 4 5 6
Water in Askarel
PPM
115
35* 22
18 12
.'
10 10
OS\N 357447
STLCOPCB4086222
25
B. Disposal of Solid Wastes: The ANSI Guide states that, "All solid wastes which have been saturated with askarel should be disposed of by the following procedure: 1. The saturated wattes should be placed into leak-proof containers and transported to a supervised dry landfill site meeting State requirements. Alternatively, they can be disposed of by incin eration in State-approved facilities.
2. Solid absorbents used for spills can be disposed of uncontained in the supervised dry landfill site; transport to the site should be in closed containers. Alternatively, incineration can be used in accordance with par. B (See Section 4 for facilities)."
C. If the solid insulation of the transformer requires drying, consult the transformer manufacturer or an apparatus service shop, as in such case oven drying is preferred.
D. Earth Treatment for Maximum Improvement of Power Factor and VolumeResistivity: We question whether pumping and filtering the fluid solely to achieve a change in power factor or volume resistivity alone is justified in today's ecological climate regarding PCBs. We recommend that in these situations the original transformer manufacturer be contacted. 1. Procedure: The askarel liquid should be relatively dry prior to the follow ing earth filtration. As a coating on the filter paper surface use finely divided Attapulgus clay or Fuller's earth dried and activated by heating for 12 hours at 300-350F immediately prior to use. The amount of earth used should be 0.1 to 0.2 percent by weight on the weight of the askarel to be treated. Askarel weighs about 12.5 pounds per gallon.
To deposit the earth evenly, stir one-third of the earth with a small
portion of askarel in a clean container. Pump the mixture through
the filter and follow with two more one-third portions. Then circu
late askarel taken from near the top of the transformer, pass it hot
(not over 55-60C) through the earth-coated filter and feed back
through the bottom transformer outlet. Continue circulation until
the fluid is clear and test shows that the electrical properties are
fully restored.
DSW 357448 STLCOPCB4086223
-26
2. Effect of Earth on Removal of Scavengers Only slight and insignificant loss by selective absorption of tin tetraphenyl and epoxides occurs when askarel is refined by treatment with 0.1 to 0.2 percent by weight of earth. To re move significant amounts of the scavengers requires repetitious treatment with much larger amounts of earth.
3. Table IX - - Approximate Relationship Showing the Insignificant Effect of Power Factor and Volume-Resistivity on Dielectric Breakdown Voltage of Transformer Askarel
Power Factor (60 eye.)
100*0 25*C
Volume Resistivity x 109 bhm-cm (at 100C, 500 Volts
DC, 0.1" gap)
Breakdown
Voltage 25C, 0.1'
2#
55#
*5# 20-25# 40-50#
0.05# 0.1#
0.7#
2.0# .
1500 500 100
60-70
25
.
35 KV 35 35 35 35
XXI.
Cleaning Arced Transformers If a unit has arced so that the askarel is no longer fit for use, a thorough cleaning of the unit is necessary before refilling with new askarel insulation and returning it to service*. Follow this procedure: A. Drain out all dark, carbon-contaminated askarel. Arrange to have the
scrap fluid incinerated under proper conditions. (See ANSI Committee C107 report.)
B. Carefully brush carbon deposits from internal parts and insulation, using a soft bristle brush making sure that insulation is not damaged.
C. Flush thoroughly using new askarel - not an oil, not a cleaning sol vent.
D. Flush a second time with fresh askarel; drain; then fill to the proper level with new askarel.
. Energize transformer to warm the fluid for 24 to 48 hours; then circulate the askarel through a
, filter, returning it to the unit filtered and
ready for use.
*This assumes that the cause of arcing has been established and corrections
made. When severe arcing occurs, major repairs are usually necessary and
the unit rebuilt. This procedure can be applied for flv~hing out the re
paired units.
DS>W 357449
'
; i
STLCOPCB4086224
27-
XXII. Sampling Askarel Take a sample as close to the top of the liquid surface as possible. Many large askarel transformers have a built-in sampling tube near the surface for convenient sampling. Then, to make sure that your sample truly represents your askarel insulation, take another sample from the bottom. If additional sampling tube connections are contrived on the valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; and silicone, or Viton or Teflon tubing for flexible types.
Use NEW containers for the askarel sample. A new and thoroughly pre dried small-mouth quart glass bottle fitted with a Bakelite*screw cap with aluminum or tin cap liner is recommended for quick, on-site testing. (If complete analysis is to be made, a 5-pint size sample is required.)
Be sure that the new bottle does not stand open to collect dust or mois ture. Rinse the sample bottle and cap lining two or three times with askarel from the transformer, then fill it. If the sample will be tested promptly, a clear glass bottle can be used. If sample is to be stored indefinitely, use an amber glass bottle or wrap clear glass with aluminum foil. A. Select a dry day. Do not sample insulation on a warm, moist day when
humidity exceeds 75%, and . . .
B. Make sure that the askarel is at least as warm as the surrounding air. (Cold liquids can condense moisture from humid air.)
C. When sampling askarel frcro transformers, it is best to take the sam ple when the unit is warm and operating at average or maximum load, especially for a check on moisture as reflected by a dielectric breakdown voltage test. Sampling the warm askarel more truly rep resents its condition during operation.
Experience shows that water will migrate from a transformer's solid insulation to the askarel liquid and vice versa, depending on tem perature. Therefore, when the transformer is hot, the moisture is most likely tobe found in the liquid. This accounts largely for periodic variations in dielectric breakdown voltage. For example.
trademark of Union Carbide Corporation
DSW 357450 STLCOPCB4086225
28a relatively high dielectric breakdown voltage may be found during winter months and a relatively low dielectric breakdown voltage dur ing the summer months on samples taken from the same unit. When testing has been completed, the remainder of the fluid sample should be destroyed by high temperature incinceration described in Section VIII.
DSW 357451 STLCOPCB4086226
-29Section B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS I. INTRODUCTION High voltage leads are usually connected to askarel or mineral oil-filled network transformers and power centers through terminal chambers and switches. In some cases terminal chambers are not used, and the high voltage leads are connected directly to the switch terminals. They may be filled with either askarel or mineral oil. Switches are usually ro tary or drum type fitted with a revolving block and porcelain unit as the principal element arranged for three-phase service.
Askarel transformers with attached switches have been in use for about 30 years. When they were first introduced, the availability of insulat ing and gasketing materials was rather limited and even the best materials at the time had no service history. As a result, inadequate gasketing materials such as cork, nitrile rubber, and nitrile rubber-and-cork particles were used. While satisfactory for a limited period of time, these materials cannot be depended upon for the expected long life of the equipment.
DSW 357452
STLCOPCB4086227
V *
i --
. .' .
.- a ` -V
' =*? SiJ
. -30_ The terminal chamber is usually above or below the switch
compartment and separated by a steel wall through which the
bushings are inserted. When bushings are properly selected
and correctly installed, there is no leakage from one com
' . partment to the other. With poor bushing seals, and the
. terminal chamber above the switch, potting compounds or cable
*
' oil can seep into the askarel. When the terminal chamber
'v
is below the switch, askarel can drain into the terminal
. - chamber.
. .
`
-v . . '
'
/ II. SOURCES OP CONTAMINATION
There are three possible sources of contamination for askarel
' in switches and terminal chambers; they rank in this order
of frequency: (l) water entering through poor gaskets;
(2) decomposition products from arcing when switch is used -
- to break magnetizing current; (3) entrance of pothead or
.
..."
cable compounds through leaky bushing seals.
-
.
. " Unlike an askarel transformer where the amount of contami. nant is likely to be very small (probably only trace amounts)
in relation to the volume of askarel fluid -- in switches or terminal chambers with faulty seals, the amount of contami nation can be relatively large.
i1
I
i
1
STLCOPCB4086228
-31-
Experience has shown that, based on the number of installed .
askarel-switch units, the percentage of failures is extre
mely small. When investigated, it has been found that most
failures originate in the switch chamber. Water is the
. chief source of contamination. However, heavy contamination
of askarel with petrolatum and asphalt material, due to
- leakage, have caused a few failures.
.
.
Petrolatum is used frequently for filling terminal chambers. .-When either cable oil or petrolatum seeps into askarel, no - great harm results. The fire resistance will be somewhat .* decreased and power factor of the askarel will increase with
'an accompanying drop in resistivity. While highly undesir. . able, it is doubtful that failure of the unit results. Where . . asphaltic compounds are used in place of petrolatum, the : danger is increased somewhat because asphaltic contamination
may cause excessively high dielectric losses in the askarel.
` When the terminal chamber is below the switch chamber, the potting compound can be contaminated by askarel if the bush ing seals are leaky. This is undesirable because the askarel
. will increase the power factor and conductivity of the potting compound or cable oil and develop heat from dielectric loss. If this mixture is drawn into the cable insulation, a cable failure is likely. This again emphasizes the importance of
tight bushing Assemblies.
DSW 357454
STLCOPCB4086229
i \i. - *.. .sp-.s-asLi
-32-
III. SEALING SWITCHES AND TERMINAL CHAMBERS Proper bushing construction, use of Silastic seals and
. welding wherever possible Is highly desirable (as covered in Section A). Where an elastomeric seal Is to be used
in contact with both askarel and petroleum oil, DuPont's Viton is suggested.
For new equipment the user should specify these modern
sealing arrangements to keep out contaminants and minimize
.maintenance.
*.
IV. ASKAREL USED UNDER MILD ARCING CONDITIONS
.
. The IEEE Guide for Transformer Askarel calls attention to
. the following:
.
.
^ "Askarel is used, to some extent. In apparatus
. . where it Is subjected to light intermittent
arcing, such as in self-contained induction
. ` regulators, where operating switches are con
. tinually.producing slight arcs. In transformer
''
deenergizing switches, etc. Under normal con-
ditions, deterioration of the askarel is very
slight. However, Improperly adjusted or defec-
tlve switches in this type of apparatus can
. produce excessive and prolonged arcing and ac
' cellerated deterioration of the askarel. It is
recommended that when askarel is used under
. these conditions, checks of the liquid, espec-
ially for moisture and dielectric breakdown voltage
made more frequently than.when It Is used only
as a cooling and insulating fluid. Deteriora
tion of this type is indicated by a blackening
of the liquid. It can usually be reconditioned
as previously described. Special attention
should be given to maintaining the scavenger at
the appropriate concentration.''
DSW 357455 STLCOPCB4086230
"SWOT
-33
V. MAINTENANCE FOR ASKAREL FILLED SNITCHES
A. Switches used for grounding after power source has been
de-energized will not undergo arcing,
.
B. Switches Interrupting magnetizing current will be sub
ject to arcing; the amount of decomposition will depend
on power interrupted, time and frequency of operation.
As a general rule, the liquid should be checked after
.. ` 5 to 10 operations.
..
. .
. 1. On newly Installed switches, check the askarel at
3, 6 and 12 month intervals; If found satisfactory,
:
. 1, '
. ..
check once annually thereafter. "With proper atten-
' S'
tion to the gasketing of covers and bushings, exper-
. ience will probably indicate that less frequent in
. . . jspection is warranted.
`' . . .
.' .
' 2. Check askarel for:
.
.'
'/
a* Dielectric breakdown voltage (ASTM D877) :__It should 4 . . voltage
( be 26 KV minimum. If dielectric breakdown/is low,
. ' . .
confirm presence of water by Karl Fischer method
' ASTM D-1533. Filter to remove moisture. Die
. . . lectric strength should then be 30 KV minimum.
b. Presence of carbon from arcing: Fluid should be
. relatively free of carbon. If badly arced and
very black, replace fluid. If only minute amounts
of carbon are present, filtration is recommended.
. Check power factor of liquid (should not be over
.5# at 25C. and 60 cycles). Flush out switch
.
* chamber with several gallons of fresh askarel
. . before refilling.
dsw 357456
STLCOPCB4086231
3. If there is discoloration, high power factor,
. detectable change in specific gravity or refrac
tive index, or if fluid flashes below 250F,
there Is a possibility of seepage of potting com
pound into the switch compartment. In this case,
. correct any leaky bushing seals with proper re
placements and fill with new askarel.
4. If terminal chamber is below switch, check potting
compound for presence of askarel (can usually be
detected by odor or by an increase in specific
'
gravity). If askarel Is present, correct any leaky
bushing seals with proper replacements, and renew
compounds.
' ...
.
5. Examine cover gaskets visually. Deterioration can
be detected by swelling and cracking of the exposed
. edge. In cases of severe deterioration, liquid
seepage is usually present.
..
6. Check for leakage at packing gland of switching
shaft. If leaking, repack with a Silastic ring type
gasket.
.
VI. ASKAREL UNDER EXCESSIVE TEMPERATURE OR FAULT CONDITIONS!
The IEEE Guide also points out that,
"Chlorobenzenes used in transformer askarels begin to boil
r : Si ! II i
X
DSW 357457 STLCOPCB4086232
-35-
.
at temperatures of about 205C, under atmospheric con
ditions. If the material is heated to such high tem
perature in a sealed system, pressure develops. Pres
sure will also develop in the system if the askarel is
arced sufficiently to generate copious hydrogen chloride
gas.*^
.
.;
"Therefore, it is recommended that wherever possible, sealed askarel filled equipment be provided with pressure relief devices. These devices must be large enough to . provide immediate relief at a definite pressure, and to prevent further build up of pressure if decomposition continues. It must be remembered that the presence of devices of this sort does not necessarily preclude the rupturing of containing vessels, since pressure build up can be extremely rapid under violent arcing conditions."
0S\N 357458
STLCOPCB4086233
-36-
'
SECTION C
*
ANALYTICAL SERVICES ON TRANSFORMER. ASKAREL AVAILABLE
FROM MONSANTO
..
.
. Transformer users not wishing to make their own fluid analyses can obtain the service from
Monsanto. Simpiy contact Monsanto and specify what analyses are wanted. You will be
sent the proper-sized'sample container fitted with a proper label. When you re
ceive this, carefully ' take your sample (following the procedure for sampling in this
guide). Send the container to Monsanto's laboratory. Charges listed include sample
container, shipping, handling and laboratory costs.
e*.i
Types of Analyses Available
Analysis 1)
.
.'
ROUTINE MAINTENANCE CHECK
...
'
- Total Charge: $25.00 *
To determine the general condition of the fluid and find whether further analysis is neces
sary, (one-quart sample required)
..
Properties Tested
.
Color and Condition
Dielectric Breakdown Voltage
'.
Moisture
..
'
'- *
. . ' .
' .
You will be notified of the results of this test. If further testing is indicated, and you want a
complete analysis, you will be sent a five-pint sample container. This sample will be used
for the following series of tests:
'
Analysis 2)
"
COMPLETE ANALYSIS
Total Charge: $55".' 0p~ ` 7
(a) To determine the extent of fluid contamination, (b) earth refinement to determine what degree of restoration of electrical and insulating properties is possible, (c) check test to see how the fluid responded to earth treatment.
a) Complete Analysis: to determine the extent of contamination
Properties Tested
Color and Condition
Specific Gravity
Refractive Index
Water
.
Free Chlorides
.. _
Acidity
' Dielectric Breakdown Voltage
Power Factor, Dielectric Constant, and Resistivity
.
.
. '
DSW 357459
STLCOPCB4086234
-37-
b) Earth Refinement Response:
Consists of treatment for 2.5 hours at 50-60C. with 0.1 to 0.2 percent by weight of properly conditioned Atiapulgus clay and then filtration through dry filter paper.
<) Analysis After Laboratory Earth Refinement:
.
properties Tested
.
'
Refractive Index
`
Water
.. Free Chlorides
.
Acidity
._
.........
'
Dielectric Breakdown Voltage _
'
. Rower Factor, Dielectric Constant, and Resistivity
.
.
You Will be notified of the results of this test series on your sample. Then aftei refining
your entire transformer fluid fill you can check on the results by requesting the
fallowing analysis:
*.
Analysis 3)
.'
ANALYSIS AFTER EARTH REFINEMENT
\- ,
Total Charge:^35 # QQ(Thls charge will not apply when . analyses 1 and 2 have already * been made.)
To determine" whether'the entire lot of the askarel fill responded to the same extent as the
laboratory sample, (five-pint sample required)
properties Tested
. . _
Color and Condition
'
Refractive Index Water
' : " " ' ..
.
Free Chlorides
. . .
.'
Aridity _
; v
Edelectric; Brerikdqw;*. Voltrigd
.
''
Rower Factor, Dielectric Constant, and Resistivity
To arrange for*the tests described above" write to the following address:
Raul G. Behignus
Monsanto Company
BOO North Lindbergh Blvd.
' St. Louis , Missouri 63166
dimples to be" tested' should be dearly marked for identification and sent directly to:
Monsanto Chemical Company ,, ,W. G. Krummrich Laboratory.
. Sauget, Illinois 62201
Attention: R. Kuster
.
'
.
'
DSW 357460 a
STLCOPCB4086235
-38APPENDICES
= .- .#* jy^l
.}
'i i!
1
APPENDIX A -- Askarel Stability and Composition of Arc Formed Gas:
Askarel insulation is one of the most inert, chemically-stable
heat resistant, non-corrosive liquids known. It will not break
down, oxidize or sludge when exposed to air and high tempera
tures, 150C. or even somewhat higher. Arcing, however, will
break down the compound to liberate some hydrogen chloride and
email amounts of carbon.
' . .
.
APPROXIMATE COMPOSITION
'
ARC FORMED GAS FROM TRANSFORMER ASKAREL BLENDS
.
ASTM TYPES D AND F
..
(INERTEEN 54201KA AND PYRANOL A13B3B-2, RESPECTIVELY)
'
Gas . Amount
carbon monoxide.......................
0.3 per cent
carbon dioxide................................................................. 0.3
oxygen...............
0.6
Inert gases................................................
1.5
hydrogen chloride..................................
97.3
(note the absence of phosgene)
.
This arc-formed gas from ASTM Type D and Type F transformer ask-
arels is non-flammable and non-combustible.
'
For all practical purposes, the amount of gas liberated from
askarel under a given set of arcing conditions is about
.
100 cubic centimeters per kilowatt-second.
*
'
.
DSW 357461 STLCOPCB4086236
T-
' -39-
APPENDIX B
SOLUBILITY OP GAS IN TRANSFORMER ASKARELS . ASTM TYPES D AND F
Percent of Gas By Volume Corrected to:
. '
Carbon dioxide Air Nitrogen Hydrogen chloride-*-
25C 760 mm
100'~C
*71^
47#
5.7 6.0
4.9 4.8
37*8
50.9
0C. 760 mm
25'PC"
100 C
1:25.8
5.5
l) In absence of scavenger _______
APPENDIX C
- EFFECT OF TEMPERATURE ON ' ' DIELECTRIC BREAKDOWN VOLTAGE OF ASKAREL
.
Temperature C
-60 -40
20
0 20
40 60 80
'
Dielectric Breakdown Voltage
ASTM D877
. fc>7 KV . 63
57 , 55
50
.
50 48
45
. .
'
DSW 357462 STLCOPCB4086237
-40-
APPENDIX D
Temp.C
~ -20 0
20 40 60 8o 100
COMPARISON OP THE APPROXIMATE VISCOSITY IN
SAYBOLT UNIVERSAL SECONDS OF TRANSFORMER
. ASKARELS AND MINERAL OIL
Inerteen
Pyranol A13B3B-2 10 -C Mineral Oil
54201 KA
1,000
1,000
2,800
100 150
195
745 39
85 85
49 4o
4?0
34 34
36
30 .
30
33
APPENDIX E
'`
THE DENSITY OF INERTEEN 54201 KA
7336-9 AND TRANSFORMER PYRANOL A13B3B-2
Approx. Density gmycc.
.
Temp. C
Inerteen 54201 KA
0
.
1.574
20
-. : -
1.552
40 ' 1.529
60 ' , - .. 1.507
80 1.485
Pyranol A13B3B-2
1.577 1.555 1.532 1.510 1.488
APPENDIX F
'.
.
..
The thermal conductivity values of transformer Pyranol A13B3B-2
at 27C and 58C are 25.2 and 25.8 x 10~5 calories centimeters"1,
degrees centigrade"1, second"1, respectively. Or, approximately
0.06 BTU per (hr.;(sq.ft.)(F.) per foot. This same approxima
tion applies to Inerteen PPO (7336-9).
. ..
'
APPENDIX G
'
Heat Capacity
.
Over the temperature range of 25 to 125C the specific heat of
transformer askarel is close to 0.30 calories per gram per
degree.
.
.
APPENDIX"H
' . >
" '
Coefficient of Expansion
The average coefficient of expansion -of transformer askarel over the temperature range 20 to 100C is 0.0007 cc/cc/C. One galIon would increase to 1:056 gallons on heating from 20 to 100C.
DSW 357463
STLCOPCB4086238
-41-
APPENDIX^I
;
*
Fire Resistance
.-
Askarels of various compositional types are used. Under arcing
conditions the gases produced, while consisting of predominantly
non-combustible hydrogen chloride can yield varying amounts of
combustible gases depending upon the askarel type.
Insulation systems incorporating these askarels and cellulosic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitro gen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus.
APPENDIX J '
Seals, Properties and Procurement '
.
Dow Corning Corporation, Midland, Michigan with Districts at
Atlanta, Boston, Chicago, Cleveland, Dallas, Los Angeles, New
York City, Washington, D.C. and Toronto has available Bulletin
09-019, August 1962 entitled "Silastic Design Data". This lists .'the gasket fabricators throughout the country from whom the '
"Silastic 50" gasketing can be purchased In sheet, extrusions
or molded shapes.
. .. '
Generally Silastic 50 sheet goods are stocked by local die cutters, hence, c.ould be generally purchased locally. Usually small quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other . elastomers.
. . DSW 357464
STLCOPCB4086239
-42-
Itfhere the gasket is extruded for fitting into a machined
groove or between gasket stops, Dow-Corning advises use of
3ft acarved Joint. This Joint is then cemented using Dow
Coming's Silastic 140 (clear) or their RTV 731 (white) mate
* j*JLals, which air cure.
** . ..
Dow Corning points out that the local "rubber" fabricators
purchase the Silastic 50 in billet form. This is worked on a
-roll mill in preparation for sheeting or extrusion. Then to
Obtain the desired physical properties the fabricator must
oven cure the Silastic 50 for 24 hours at 480P.
.'
:
- SPECIFICATIONS*
' ' ' . '
* ASTM DS76--. ASTM D4l2 ASTM D4l2 ASTM D395
Color.........................................................White
Specific Gravity at 77F............... 1.20 0.02
Hardness, Shore A. Scale..............45 to 60
Tensile Strength, psi, min.......... 800
Elongation, percent, min............... 250
Compression Set after 22 hrs...
..
at 300F, percent, max...................30
All physical properties measured on 0.075 inch thick samples molded 5 minutes at 240F, and oven cured 24 hours at 480F.
DSW 357465
STLCOPCB4086240
-43-
APPENDIX K
'
Caution Label
.
The following or equivalent caution statements should be fixed
on all containers of transformer askarels and the transformers
themselves:
This product contains Polychlorinated Biphenyls (PCBs). Care
should be taken to prevent entry into the environment through
spills, leakage, use, vaporization, or disposal of liquid or
containers. Avoid prolonged breathing of vapors or mists. Avoid
contact with eyes or prolonged contact with skin. If skin con
tact occurs, remove by washing.with soap and water. Following
eye contact, flush with water. In case of spillage onto cloth
ing, the clothing should be removed as soon as practical, skin
.' washed, and clothing laundered.
. / .
f ?
DSW 357466
STLCOPCB4086241
* - ,*?* Mii
. ' :
i
The information herein regarding obtaining optimum results from askarel fluids in your transformer has been accumulated by Monsanto for over **40 years from the experience of makers and users of askarcl transformers and it Is believed will be helpful.
Nothing herein shall be construed as applying to other than askarcl insulation. Data and maintenance suggestions herein do not apply to the other components of the transformer. All operating and maintenance suggestions recommended by the manufacturer of the transformer should also be carefully followed.
Because these maintenance directions apply only to the askarcl insulation,
Monsanto disclaims any liability for damage to property or injury to persons
arising from transformer operation.
.
. '
" -