Document kmnpjj10oYEvy83o4pLQDKodq
198
CHAPTER 15
1962 Guide And Data Book
buildings but its comparisons and conclusions are largely applicable to the other types of moltiroom buildings.
LOCAL SYSTEM DETAILS
To meet the requirements common to multiroom buildings,
all peripheral systems considered must provide wide flexibil ity and range, to meet individual room requirements. The
means for meeting the requirements may be:
1. Controlled miring of air at two different temperatures. 2. Controlled use of water at two different temperatures. 3. Use of local refrigeration and local steam or hot-water heating 4. Use of air to obtain heating together with water for cooling. Systems of type require, in many climates, seasonal change over, so as to reverse operation between summer and winter conditions.
In addition to maintaining acceptable temperatures and humidity, all these systems should:
1. Introduce into each individual space a sufficient amount of filtered and conditioned outdoor air, tor satisfactory ventilation.
2. limit outdoor air to the required amount and thereby reduce neediest refrigeration or beating demands and costs.
3. Recirculate air, either centrally or locally, and recondition enough return air, in addition to tin outdoor air, so that the total air circulated in the occupied spaces will do the necessary cooling and dph^mirfifying in aimnwf at permissible temperaturedifferentials, as well as the necessary heating in winter.
4. Distribute and diffuse the air in the occupied spaces, at such temperatures, velocities, and directions as not to cause drafts objectionable to the occupants.
5. Operate without objectionable noise-levels in the occupied spaces.
6. Be easily maintained, kept clean, and adjusted to suit varying tastes of occupants.
7. Automatically differentiate between the cooling and heating requirements of different floors or zones, different directional exposures, and different individual rooms (due to sunshine, wind, etc.), as well as the load-variations resulting from occupancy, lighting, local equipment, etc., and to adjust the performance, smoothly and rapidly, to compensate for such variations.
Double-Duct Systems (Scheme 1)
In the double-duct method of local temperature control, air
(previously filtered, and often partly conditioned) is delivered by asingle high-pressure fan to two sets of coils connected in parallel. One coil cools the air in hot weather to a temperature
20 to 25 deg lower than the desired room-condition; the other one warms the air (already sufficiently dehumidified, in sum
mer) to a temperature at or aboot the room condition. In cold weather the cold air temperature can be secured without using refrigeration. The warm air temperature is raised progressively as the weather becomes colder.
The two coils feed into two parallel high-velocity duct
systems; while the cold duct should usually be sized for 100
percent of the total fan-capacity, the hot duct, in most cases, need be sized only for 50, GO, or 70 percent. From the two ducts, a pair of mixing-dampers (or valves) deliver, to each
individual room or bay, air at the right (mixed) tempera ture for the then current cooling or hating demand of that particular space. A local thermostat controls the setting of the
mixing-valves. Since the pressure drop through these gen erates noise, acoustic attenuation is needed here. Quite often,
the valves, the attenuator, and a constant air volume regula
tor are incorporated in a fabricated package or box, which
feeds air into the room. An important element in many such systems is static-pressure control to maintain reasonably equal pressures in both ducts, at or near the mixing-valves,
as the total flow through each duct varies.
Duct sizes usually limit vertical distribution (at outside
wads) to 3 or 4 floors in height. Beyond this, horizontal dis
tribution is often needed.' In long, narrow buildings, it may be
the preferred method.' Such systems can sometimes be so de
signed that the same duct system serves several, or all, dif
ferent zones. In this case, and if windows are large, the cold
duct may sometimes be smaller than for 100 percent capacity,
since not all facades will receive sunshine at the same time.
In tropical climates (and even in colder climates if windows
are very small and double-glazed) all boxes and outlets may
be at the ceiling. Where winters get cold and windows are
average or large in size, those for peripheral zones should be
under windows.
Radiant Cooling and Heating (Scheme II)
This is accomplished by the circulation of cooled water, in
summer, through coils, which extract heat from an aluminum
ceiling, attached under the coils, and exposed to the room to
be thus cooled. The same equipment obtains effective winter
heating by warming the circulated water. To absorb heat, the
ceiling must be appreciably colder than the air (or than other
surfaces in the room). For example, a suitable surface, about
15 deg cooler than the room-air, will absorb sensible heat of
about 20 Btuh per sq ft in a room not receiving sunlight. With
solar radiation entering through windows, this value may
increase to 25 or more. This iB about equal to the differential
between typical inride and peripheral zone demands, if win
dows are small or well shaded, and permits a large reduction
in tire amount of conditioned-air required. It may also make
it possible to combine outside and inside zones into a single
system of fans and ducts, with room and tone control only, by
varying the water supplied to the radiant ceilings. Small
convectors or radiant panels under windows (for winter use
only) may be needed as a supplement in corner rooms and in
colder climates. in order to apply radiant cooling and heating, careful con
sideration must be given to fundamentals as follows:
1. To absorb heat adequately, the surface of the ceiling must be materially eolder than the air.
2. The circulating water must, in turn, be colder than the ceiling surface. With well-designed coils, and raling* of aluminum, the coldest water might be 3 or 4 F deg lower than the average ceiling temperature, with plaster or concrete ceilings which are much poorer beabconductors this differential would have to be several times as great.
3. It is not economical to maintain dew points lower than 54 F to 56 F in miHmmir>r throughout a conditioned building.
4. To avoid any risk of condensation, therefore, no indoor air should contact any surfaces at a tower temperature than 58 F. To avoid the high cost of (vapor-tight) heat-insulation for the cooled water system, this implies that the coldest water in any part of the system should be little (if any) below about 60 F.
5. Recessed lighting fixtures may be integrated with a radiant ceiling design. They may also be directly connected with the coils, so that much of the heat (emitted by lights) can be removed directly without first becoming room load. When thus used, or when the ceiling receives heat from floors directly heated by the sun, the cooling water (at a given temperature) will absorb much more heat than from the room air alone.
6. In very low dew point climates, such as deserts, lower water and filing temperatures may be used to increase capacity.
7. .Where an ample supply of natural 60 F, or lower, water is available, radiant ooohng plus chemical-adsorption dehumidifrcation may eliminate the need for marhanir^l refrigeration.
For further information on panel cooling see Chapter 3.
Aluminum is advantageous for radiant-cooling ceiling ma
terial, because:
1. It is the best heat conductor (except silver or copper). 2. It is easily formed and worked and comparatively inex pensive. 3. It is not subject to corrosion which would interfere seriously
Public Building Air Conditioning
199
irith heat conduction from ceiling to coils. Steel coils should be mJJ galvanized, to avoid reduction of heat transfer due to rusting.
4 It can be coated with a wide variety of finishes, and seldom needs refinishing. A fiat finh which may be painted, anodized, etc is sential for good thermal performance.
Sectional aluminum radiant-cooling ceiling panels (usually
12 X 12 in. or 12 X 24 in. are advantageously used for jrcdubu- layouts consistent with spacing of windows, lights,
aod partitions and can also serve for acoustic treatment. Acoustic perforations represent a negligible percentage of the
heat-absorbing surface, while the acoustic'blanket of fiber
glass or the like above the ceiling, is also efficient thermal {pollution against reverse loss above the ceiling, and thereby improves performance and control of cooling panels.
While radiant cooling, where applicable, eliminates the occupied by unit enclosures and primary-air conduits,
and greatly reduces the amount of air handled as well as the
axe and space for fan-rooms and ducts, etc., it cannot elimi nate fans and ducts. It can only reduce their size, cost, and complexity. It is still necessary to introduce enough outdoor
air for:
1. Ventilation. 2. Comfortable air-motion. 3. Removal of most of the sensible cooling load due to people mwH lights. 4. Removal of latent load due to people and to obtain dohumidification to a point where the internal dew point will be low enough to avoid condensation on cooled pipes or surfaces.
Fan-Coil Units (Scheme III)
These systems make use of package fan-ond-coil units,
located under windows and supplied with circulating water
which is chilled in summer or heated in winter. Good design
includes:
1. Operating the fan-coil unit with only recirculation, to oontrol the temperature of each room separately.
2. Controlling water flow by a room thermostat. 3. Providing a separate central fan-room and duct system (high or low .velocity) of capacity onfu great enough to provide each room with proper ventilation and humidity control. The air may enter the room either through a branch duct connecting into the unit, or through a separate ceiling outlet. The former arrangement has been successfully used in tropical hotels, where the conditioning, unit was located overhead on the corridor side of the room. The latter arrangement may be ad vantageous for apartment houses. It may be noted that air quantities supplied through ducts will be ample with only 15 to 20 percent of that required for an all air system for peripheral cones so that the central fan-and-duct system becomes quite low in cost, and simple in design. These systems are applicable to buildings having almost no . interior zone space, or to the peripheral zones of those in which a separate conditioning system is provided for the interior sones. (See also Chapter 2.) A variation is to let the interior zone all-air system deliver ventilating air to rooms in peripheral zones. This is not an efficient method, because (a) the intenor zone supply (much of the time) nay be about 75 percent recirculated air. To supply the same outdoor air ventilation, about 4 times as much air must be blown into peripheral spaces, and (b) the interior zones nearly always teqinre cooling. In cold weather, then, the fan coil unit must supply extra beat. This causes a waste in both heating and oooling
Zoned All-Water Systems (Scheme HIA)
This is a scheme in which each room has its own fan-andoofl conditioning unit, with no ductwork. For adequate con
ditioning, each unit should have an outdoor-air intake under
a window, or through the wall or roof, so as to deliver a mix ture (fixed or variable) of outdoor and locally recirculated air.
Water-circulating piping is zoned by direction of the facades
--or otherwise, to suit the particular building. Chilled water may thus be pumped to areas that require cooling, and, at the timA., warmed water to areas that require heating. Such systems are being used for apartment houses; they are materially 1^h costly to install than what would be considered good practice for an office building or hotel, but decidedly better than the self-contained units formerly mostly used for apartments. They are suitable only where no large interior spaces require cooling and ventilation, since they have no central air supply system.
A variation of this scheme accomplishes beating, when needed, by separate coils, connected to a separate steam or hot water circulating system. Such an installation will be somewhat more costly and will have more complications. Its one major advantage is the ability to control, separately, the temperature and humidity (in climates where this may be essential), by cooling humid air as necessary to take out enough moisture, and then reheating it to the correct delivery temperature.
Induction Systems (Scheme IV)
In this scheme, now widely used in large office buildings,
hotels, and the like, the peripheral zones (areas extending
about 12 to 18 ft inward from the windows) are cooled or
heated by means of compact local units, enclosed in metal
cabinets under the windows or in a continuous metal sill con
struction.
unit circulates, locally, as much conditioned
air as will properly serve the peripheral zone space bounded
by one window or by one small group of windows, while the
inner zones of the building are conditioned by separate air
duct supply systems. In the most usual method, toe units
under the windows receive as primary air about 15 to 20
percent of the total to be circulated in the room from a remote
fan-room, through Email high-velocity conduit ducts which are
run vertically whenever possible, near each outride wall. The
primary air'(largely or entirely outdoor) is filtered, humidified,
or dehumidified as necessary, cooled or heated at different
seasons, and delivered at considerable pressure to the under-
window units in which, by means of ejector-nozzles, the pri
mary air aspirates or induces several times its own volume
of air to flow from the room into the unit, mires with it, and
delivers the mixture back into toe room in such a manner as
to give good local distribution. The aspirated room-air passes
into the unit through a finned-coil where it is cooled in summer
or heated in winter by tvoter circulated from a piping system
connecting to each unit, and distributed much as is the pri
mary-air ductwork. Preferably, the flow of water (or in some
models, the flow of. air) through the coil is controlled by a
room thermostat responding to the temperature of toe room
air entering the unit. (See also Chapter 2.)
Many available combinations of nozzles, coils, operating
pressures, etc., can produce units of many capacities, having
several different ratios of primary-air to total thermal
capacity, and having various heights, and thicknesses, etc.
Generally speaking, the more liberal the proportions of the
unit, for a given capacity, the quieter is its operation; but
all units include careful acoustic treatment.
Two-Pipe Secondary Water. The majority of installations
have employed a two-pipe water-circulating system, often
zoned by facades, so that water at different temperatures
could be supplied as required to compensate for sunshine,
wind, and outdoor temperature effects. Whether or not water
is zoned, good practice is to zone the primary air, because the
local damper, after it has been adjusted for the correct amount
of aspiration, maintains a fixed quantity of flow and there-