Document kmaybE3EvGekv0D12koqNNqNb
622
CHAPTER 58
1962 Guide And Data Book
Table 1 .... Storage Temperature and Humidity Conditions
Piodmt
Vegetables ifauta Meats (cut) Meats (carcass) Poultry
Fish
Butter. Cheese Bottled beverages Frozen Foods
Sfori-Tim Storage
f Moufore
36-42 36-42
34-38 34-38 32-36
Class 2 Class 2 Class 2
Class 3
Class 2
35-40
36-42
38-45 35-45
Class 1
Class 2 Qasa 1*
C9ass4
24 to 72-hr Storage
f
32-36 32-36 32-36 32-36 30-35
Motifor*
Clftsn 1 C3i2 Class 2 Class 3 Class 1-2*
35-40
31-35 35-40 40-45
0
Class 1
08^2-3* Class 4 Class 2
Teupentane and moisture condition* choirs above ere customary retasraat practice. Some varieties* ttay be expected due to different varieties d traits or vecoteble* sad the growing conditions in different geographical loca tions. For complete and detailed information' including approximate long-time storage life, on all types of foods, refer to Table 1. Chapter 23. The USDA Hand book N<l 66 is another authoritative eontce for conditions for the long-time
- u paoKageo.
* Freese and hold at 0 F or below if bdd for more than 72 hr. CIgm 1. Such product* as eggs, onpadcaged butter and cheese and most vegetables held far comparatively long periods of. time. These products require very high relative humidity berimes it is necessary to effect a minimum of motataie evaporation during storage. Clan 2. Saeb foods as cut meats, traits and similar products. These require high relative humidities but not as Myh as Class 1. Class 3. Carcass meats and fruit such as melons which have tough skins. Those products require only moderate relative bumidities because they have Rufeeas whose rate of moisture evaporation is moderate.
Clam 4. Canned goods, bottled goods, and other product* which have a pro tective covering. Tteee are produets which need only low relative humidities or which are unaffected by humidity. Products from whose surfaces there is a very low rate of moisture evaporation or none at aO, faO into this class.
venient or necessary to make use of them. This is accomplished by controlling the temperature and moisture conditions pri marily, but other factors such as air flow, initial condition of the food, and the packaging or surface protection of the food must also be controlled to get optimum quality in foods held under refrigeration.
Storage requirements will vary according to the character istics of the particular product and the length of tim* stored, but if the storage space is kept under proper conditions, fresh food will be on hand at all times with the assurance that its quality will be unimpaired for a reasonable period of time.
TEMPERATURES, HUMIDITY AND
STORAGE CONDITIONS
As a general rule, foods not frozen should be stored between 32 and 50 F and the lower the storage temperature the longer will be the period of storage (within the maximum storage pos sibilities of the product in question). Current trends are to provide the optimum quality in foods, with less emphajaa on maximum storage life.
In considering the important factors of temperature and humidity, it must be remembered that the food service oper ator has two separate and distinct problems: (1) long-time storage, where bulk or quantity lots of food can be kept re frigerated, and (2) short-time storage where many types of food can still be kept refrigerated but handled quickly and con veniently. Long-time storage in this connection is not to be considered the same as long-time storage for wholesale opera tions (as, for example, in a cold storage warehouse, where foods are frequently held for periods approaching their maximum life), but rather as a condition where foods are generally turned over in 24 to 72 hr. Short-time holding conditions are exemplified in the cheTs refrigerators or salad boxes found in most restaurant kitchens. Differences in the long- and shortrime applications are brought out in the subjects that follow.
Table 1 shows refrigerator temperatures for long- and sbort-
time food service storage for such typical commodities as fresh' meat, fruits, and vegetables. Storage temperatures as shown are probably the most important factor in the preservation of food and the data presented represents experience or custom, ary limits usually prescribed for storage room temperatures and are not absolute or final. Often, more than one product will be stored in a cooler, in which case a mean of the temper ature for each product, somewhere in the temperature range shown, would be chosen.
Just as different foods require different temperature for good keeping, so do they require different amounts of moisture in the air. Too much moisture in the air will help accelerate the growth of bacteria and mold, ranging sliming, discolora tion and loss of flavor in some foods, while not enough mois ture results in dehydration and shrinkage. Proper requirements of moisture or relative humidity could be expressed in definite percentages for ail food products, but it is dangerous to rely too closely to this factor alone; other factors are in volved, as the following example will show.
Assume that a refrigeration application requires a 90 per cent relative humidity to protect the foods against dehydra tion and shrinkage. However, 90 percent relative humidity produced in a room with gravity cooling units may not pro duce the same results, insofar as optimum food storage condi tions are concerned, as 90 percent relative humidity produced by forced-air cooling units. This is so because the additional velocity of the air passing over the food as created by the forced-air cooling unit tends to dry out the food more thn when using gravity coils. As a simple analogy, every housewife knows that clothes dry quickly on a windy day. This same principle applies to the use of forced air as opposed to gravity circulation for food refrigeration. Therefore, relative humid ity, expressed in percentages, can be very midp-ading when ap plied to refrigeration. A more practical answer is found if rela tive humidities are considered in terms of the over-all mois ture conditions in the storage area.
It is the function of the refrigeration engineer to classify any product according to its moisture requirements and to de sign the refrigeration equipment to provide those conditions. Where two or more types of products are stored in one re frigerator, a compromise favoring the product most subject to dehydration should be made.
Desired moisture conditions must be obtained by properly designed refrigeration equipment. The choice of the correct differential between storage fixture temperature and the evaporating refrigerant in the cooling unit, to provide the proper balance in the system, is the simplest, least expensive and most practical method to achieve this end.
FROZB4 FOODS
In addition to fresh foods, many restaurants are making generous use of frozen food products. Ice cream, of course, has been known and accepted for many years. Many varieties of frozen pre-cooked meals and pre-cooked portions of meals which need only minutes in the oven before serving are rapidly finding a place in the commercial food industry. As a result, adequate freezer storage capacity is essential.
The latest information available indicates that frozen fruits and vegetables should be stored at approximately 0 F, espe cially if they are to be kept for periods of three months or longer. Above this temperature they will suffer appreciable loses of Vitamin C and possibly lose some of their color, aroma and flavor. Certain mold organisms also grow at tem peratures of about 15 F and above. Just,as important as hav ing 0 F in the storage area is the necessity for keeping the tem perature as nearly constant as possible. Fluctuating temper atures, which may be caused either by poor design of the
pood Service Refrigeration
623
fri-eration system, or placing warmer products is the storage may damage the product and shorten its storage life,
fluctuation of more than 2 to 3 F deg should be avoided, ptojen foods should be properly packaged or wrapped, other wise they desiccate rapidly and their storage life is materially
reduced. la general, no damage, whether caused by temperature nse,
(jpeiccatioP, or any other cause, can ever be repaired. Storage
at 0 F or any other temperature will not improve a poor prodfjet that has been damaged mechanically or physically in ship ment or handling, or was of inferior quality before freezing.
REACH-IN REFRIGERATORS
By far the largest category of refrigerated equipment in the food service field is that of reach-in refrigerators. According to all available statistics, the reach-in refrigerator comes closer to fring a fundamental requirement in every food service estab lishment than any other refrigerator.
Although all refrigerators except walk-ins are technically reach-ins, the industry has generally confined the term to up right cabinets with straight, vertical fronts, and hinged or slid- ing doors. The reach-in refrigerator is usually about 2H 3 ft deep, about 6 ft high, and ranges in width from about 3 ft to about 10 ft. In net capacity, the range is from about 20 to 90 cu ft These capacities and dimensions refer to cabinets that are available as standard from the manufacturers. Other
Biaag and capacities are available on special order. There are reach-in refrigerators used in other industries besides food service, but the food service types are distinguished by fr*jr requirement for heavy duty use and specialized features.
Types of Construction
Reach-in refrigerators are available in two basic types of
construction. First is tire older method of making a wood frame
substructure clad with a metal interior and exterior. The
a newer method, talla for a welded assembly of the ex
terior p*rHs *nd inaprtmg an insulation liner. Both methods
have advantages and both have drawbacks. A well-designed
and properly constructed cabinet can be satisfactory in use,
whichever method of construction is used. Generally speaking,
those manufacturers that concentrate on stock models have
gtanHarriitpH on welded construction and those whose lines
are more fl*xihb have stayed with wood framing, or use both.
In either case, the importance of the frame is in providing
solidity and rigidity to the structure, square, true door open
ings with strong door-hanging arrangement and a ample,
effective and lasting base for the vapor-proofing seal that is so
necessary to the exterior shell.
In descending order of cost, the materials used on exteriors
and interiors are stainless steel, porcelain enamel on steel,
synthetic
on steel, and aluminum. The requirements,
of course, are for a material that matches or blends with that
Used on nearby equipment; is easy.to keep clean; is not'dis-
teJored or etched by commonly-used cleaning materials; is
strong enough to resist denting, scratching and abrasion; and
provides the necessary frame strength. The material that is
chosen by the individual purchaser will to a large extent de
pend on layout and budget.
Temperature Ranges
Reach-in refrigerators are available for medium or low tem perature range. The mwd'mm temperature range has a maxi mum of 45 F and a minimum of 32 F, with the most desirable average temperature being close to 38 F. The low temperature ^age need not be below -- 10 F and should not exceed 4-10 F- The desirable average is 0 F for frozen foods and -- 5 F for
ice cream. Both ranges are available in cabinets of many sizes, and there are some that combine both ranges in one cabinet.
Another type of cabinet of recent development that is be coming very popular in the food service field, is the dual tem perature refrigerator-warmer, one part of which is refrigerated while the other part is heated.
Remote refrigeration systems are often used when the cabinet is to be mstalled in a hot or otherwise unfavorable location, with several other refrigerators and the noise or heat of the flanging units would be objectionable, where every possible cubic inch of refrigerated space is needed and under various other special circumstances that cull for remote loca
tion of the condensing unit. The location of condensing unite close to the equipment
which they serve minimizes installation costs and permits high operating efficiency. However, this consideration should never
cause unite to be installed in rooms used for food storage. Ideally, remote condensing units should be installed in rooms Hprignari for the purpose, and if the units are air-cooled, the rooms should be mechanically ventilated.
Self-contained systems having the condensing unit and con trols built into the refrigerator structure are of two general types. The first type has the condensing unit beneath the cabinet. In some designs the condensing unit compartment tfrVp* up the entire front of the refrigerator, while in others the compartment occupies only a corner at one lower end. The second general type has the condensing unit on top. There is no important advantage in locating a self-contained condens ing unit beneath the refrigerator. Although the air near the floor is generally cooler and thus beneficial to the condensing unit, it is usually dirtier. Location of the condensing unit on top of the cabinet allows full use of cabinet space, and, al though tiie air pairing over the condenser may be warm, it is clean and more abundant. In addition, top mounting permits the use of refrigeration plugs (see next section).
REFRIGERATION SYSTEMS
Refrigeration systems are of two basic types, with several
variations.
1. Direct expansion with gravity air circulation. This system is
used almost exclusively in low-temperature cabinets. Evapora
tors are usually plate type, and thus are used as shelves, or they
may be wall or ceiling mounts. This type of refrigeration has the
disadvantage of requiring periodic manual defrosting, but has the
advantage of slow air movement, which lessens dehydration of
bakery and similar products.
2. Direct expansion with forced-air circulation. This system is
used in almost all medium-temperature cabinets and in all auto
matic defrosting low-temperature cabinets. Coil housings, which
are sheet metal enclosures of appropriate shape to which are
attached evaporators, expansion devices, heat exchangers, air
circulating fans, fan motors, defrost water drain pans and other
minor parts, are mounted either horizontally in the upper part of
the cabinet or vertically against the back wall or between the door
openings. The horizontal, or top mounted installation, is ade
quate Tor wmall cabinets where complete circulation of air is
almost automatically achieved, but must be used with care in the
larger
because of the danger of short-circuiting the air when
the upper shelves are loaded. TT*e vertical unit uses the bousing as
a duct, and usually takes air in at the top and discharges it at the
bottom, thus automatically providing complete air circulation
from top to bottom within the cabinet.
A variation of the above systems is embodied in the so-called plug system, which consists of a removable section of the insulated cabinet top having a coil and expansion device attached to the inside and connected through to the condens ing unit on the outside. The entire refrigeration system is com pletely sealed and readily removable and replaceable. When the plug is in place, the coil fits into a housing attached to the cabinet, thus providing top-to-bottom air circulation.