Document karvwge3qExxr1Z3OrpxmBNNO
FILE NAME: WR Grace (WRG)
DATE: October 28, 1970
DOC#: WRG128
DOCUMENT DESCRIPTION: 1970 Letter from Underwriters Laboratories regarding full-scale fire testing.
R4339
UNDERW. RITERS' LABORATOK' E-s7lN-C. 7 --
a;i.1 l`K i v ; s i > i ii i m i
ii.l.i'-'io i,iki..:
r
anindependent, not-for-profit urpav Action test upfor m!,lr sail hj
October 28, 1970
Zonolite Construction Products Division
W. R. Grace Company
62 Whittemore Avenue
.Cambridge, Massachusetts 02140
Attention: Mr. T. Felt
Gentlemen:
.
, v
-
'* V . The following will confirm the results of our
full-scale UL263 (ASTM E119) fire testing, the to-date
results of additional small-scale fire tests, and our
engineering analysis to date; namely, that the cementitious
mixture (formulated without asbestos) and identified as
Mono.Kbte IV possesses thermal and heat resistance properties
equal to those of Mono Kote III and is eligible to bear
. 5 label of Underwriter;;' Laboratories with the following
,'xre Resistance Classifications;
Floor end Ceiling Design los. 10-4 Hr, 19-4 Hr, 17-3 Hr, 28-3 Hr, 72-3 Hr 30-3 Hr, 227-3 Hr, 17-2 H r ' 49-2 Hr, 90-2 Hr, 227-2 Hr, 294-2 Hr, and 28-1-1/2 Hr.
Roof and Ceiling Design Nos. RC7-2 Hr, RC10-2 Hr,
'
RC5-1-1/2 Hr, and RC10-1 Hr.
Beam Protection Design Nos. 40-4 Hr, 216-3 Hr, and
239-2 Hr.
,
Column Design Nos. 15-4 Hr, 27-4 Hr, 37-4 Hr, 46-4 Hr,
17-3 Hr, 23-3 Hr, 32-3 Hr, 37-3 Hr, 7-2 Hr, and'
* 22-2 Hr
.
.
Confirming the UL723 (ASTM E84) fire hazard results, the existing Fire Hazard Classification of 10 - flame spread, 5 - fuel contributed, and zero smoke developed remains unchanged for this new material. .
RMB:Jb
PLAINTIFF'S EXHIBIT
Very truly yours,
f V
'ROBERT H. EERHINIG
Project Engineer
v
Fire Protection Department
AU4TATC LEGAL SU m V C G L