Document kaDo2wv6BpmNzoJkMpwaQxjqb

/ 442 CHAPTER 18 19S3 Guide y from Table 3 is 0.875. Solving 0.875 X 0.00383 = 0.00335; Making a further cor rection for the heating.value, 0.00335 X'IjVISh = 0.00328 gal per 1000 Btu per hr calculated heat loss per degree- -- 144,UUU day. '! From Table 2, the total normal degree-days for Toledo are 6269. Since U is expressed in 1000 Btu, g is equal to 240. Substituting in Equation 4 F = 0.00328 X 6269 X 240 = 4930 gal. Estimating Coal or Coke Consumption Coal or coke consumption estimates are made by following exactly the same procedure as. for oil. Values of U are given in Table 6 which only apply to an inside design ,temperature of 70 F and an outside design tem perature of O F. A correction must be made for other conditions by use of Table 4. Unit Fuel Consumption Constants ({/) fob Gas*' Based on 0 F Outside Temperature, 70 F Inside Temperature Hot Water ' - Steam , Warm Air Heating Value of Gas Btu peb Cu Ft Cu Ft Gas per Degree-Day per Sq Ft EDR Up to . 600 Sq Ft 500 to 1200 Sq Ft Over 1200 Sq Ft Cu Ft Gas per Degree-Day per Sq Ft EDR Up to 300 to 300 700 Sq Ft . Sq Ft Over 700 Sq Ft Cu Ft Gas per DegreeDay per 1000 Btu Hourly Design Heat Loss Gravity Fan Systems 500 535 800 1000 . 0.149 0.139 0.094 0.075 0.142 0.132 0.087 0.071 0.134 0.126 0.085 0.068 0.254 0.237 0.159 . 0.127 0.242 0.226 0.151 0.121 0.231 0.216 0.144 0.116 0.896 0.840 0.560 0.449 0.861 0.805 0.538 0.431 1 Therm. Gas Consumption in Therms per Degree-Day 100,000 Btu 0.000743 0.000709 0.000675 0.00127 0.00121 0.00116 0.00450 0.00430 Abstracted from Comfort Heating, Amman Gat Association, 1938 and 5 percent added for operation without night reduction ol temperature. the multiplying factors in Table 3. Data in Table. 6 are based on 12,000 Btu per lb coal, and for other heating values of coal they must be multiplied by the ratio of 12,000 divided by the heating value of fuel used. Example 6: A building in Scranton, Pa. has a calculated heat loss of 240,000 Btu per hr based on an inside design temperature of 70 F and ah outside design temper ature of --10 F. What will be the estimated normal seasonal anthracite or coke consumption for heating if 13,000 Btu per lb fuel is burned in a hand-fired boiler, with automatie control, at a seasonal efficiency of 80 percent, and what part of the total will be used during November, December, and January? Solution: From Table 6, U is 0.0444 of coal or coke per 1000 Btu per hr heat loss per degree-day. Correcting for the outside design temperature of --10 F from Table 3, the value of U is 0.875 X 0.0444 = 0.0389. From Table 2, D is 6218 and from the problem, N is 240. Substituting in Equation 4, F = 0.0389 X 240 X 6218 = 58,100 lb. Fuel used over any period is, according to the theory of the degree-day, propor tional to the number of degree-days during the period. From Table 2, the average numbers of degree-days for November, December, and January in Scranton are 717, 1074, and 1162 respectively, a total of. 2953. The yearly total is 6218, so that during these three months the estimated consumption is ---- X 58,100 = 27,600 lb. 0218 .Estimating Fuel Consumption for Space Heating 443 Table 5. Unit Fuel Consumption* Constants. (U) fob Oil11 Based on 0 F Outside Temperature, 70 F Inside Temperature Unit Efficiency in Percent 70 80 Gal Oil per Sq Ft Steam Radiator............................. 0.00105 0.00092 Gal Oil per Sq Ft Hot Water Radiator..................... 0.00066 0.00058 Gal Oil per 1000 Btu per Hour Heat Loss................ 0.00437 0.00383 * Based on. a heating value of 141,000 Btu per gallon. - . b Abstracted by permission from Degree-Day Handbook (Second Edition, 1937), by C. Strode and C. H. B. Hotchkiss. Seven percent added for operation without night reduction of temperature and change to heat* iog value of 141,000 Btu per gallon. Per degree day. Estimating Steam Consumption In estimating steam consumption the efficiency is generally assumed at 100 percent. If for low-pressure steam an average heating value of 1000 Btu per pound of steam is used, no correction is necessary. In comparing values from different cities, correction should be made for design tempera ture (see Table 3) when the unit figures are in terms of heat loss but not when the values are in terms of building volume or floor space. Where the heat loss is calculated in Btu per (hour) (degree difference, in temperature) the simple Equation 5 may be used: g X 24 X D 1000 (5) where F = pounds of steam required for estimate period, g = calculated heat loss, Btu per (hour) (degree difference). 24 = hours in one day. , D = number of degree-days for the period of estimation. 1000 = Btu delivered per pound of steam condensed. In this method the number of degree-days automatically takes care of average inside and outside temperature difference. When degree-days are taken from Table 2, an average inside temperature of approximately ,70 F is assumed throughout the period. If an average inside temperature other Table 6. Unit Fuel Consumption* Constants (U) fob Ck>ALb Based on 0 F Outside Temperature, 70 F Inside Temperature Unit Efficiency in Percent 40 SO GO 70 80 Lb Coal per Sq Ft Steam Radiator.... 0.0216 0.0172 0.0143 0.0123 0.0108 Lb Coal per Sq Ft Hot Water Radiator.. 0.0135 0.0108 0.0091 0.0078 0.0068 Lb Coal per 1000 Btu per Hour Heat 0.0889 0.0717 0.0592 0.0507 0.0444 || Based on a beating value of 12,000 Btu per pound. b Abstracted by permission from Degree-Day Handbook (Second Edition, 1937), by C. Strock andC. H. B. Hotchkiss. Eight percent added for operation without night reduction of temperature. 0 Per degree-day.