Document kGwGMD8DOEryzj8baaw8oJ4O

*56 CHAPTER 40 1950 Guide Sound Control 857 Fig. 6. Acoustic Treatment op Ducts A. Unlined metal duct. ,B. Absorption lined duct (Case y. C. Splitter plate type absorber (Case 2). (Channels 20 in. z 3.S3 in. inside). D.'Celi type absorber. (Cells 5 in. z 3.33 in. inside). 1 in. thick absorption material in all cases. Sample Calculations for Duct Treatment " 'Example t. An air conditioning installation is to be installed in a small theater. Determine the necessary sound treatment for the air distribution system to provide a satisfactory noise level in the theater utilizing these conditions:' Fan tip speed 4000 fpm, total pressure 1.25 in;............;.77 db Acceptable room noise level (Table 2)................................................40 db Required attenuation ............ ................. ........... I.......... . 37 db Solution: Natural attenuation of supply duct. Sheet metal duct 50 ft long 48 in. x 36 in. (Table 4) 50 x 0.01;.; 0.5 db : : .Elbows, two size 48.in. x 36 in. (Table 5) 2 x 1;............................... 2.0 db Attenuation grilles to theater air change 10 min (Table 7) outlet . velocity 1000 fpm.............................. .............................................. 22.0 db . : Total natural attenuation............................... .......... 24.5 db . Difference between required and natural attenuation, 37 minus 24.5, is 12.5 db. This attenuation1 inust' be supplied by sound treatment in the duct, either in the form of ,duct:wall lining or rectangular cells of the plate or cell absorber arrangement. . *: ;.! A similar analysis of the return duct system shows that 15 db attenuation is to be furnished by absorptive material. An inspection of the installation shows that the lining of the plenum on the suction side of the fan would prove the most economical, where it would secure the dual function of heat insulation and sound absorption. Example 2. A 10 x 20 in. duct is connected to a private office space in a quiet loca tion. Determine the length of. lining necessary to attenuate .averaga fan noise satisfactorily, using a lining material of'a type to which'Equation 6 applies, arid having an absorption coefficient of 0.40, at 256'cycles. Assume-that the duct is only 12 ft longias shiown.in Fig.' 6, and that a 30;.db reduction is required in this length. Solution: ..... ; Case 1. (fto splitters,; duct lining only). From Equation 6, : . 60 12,6 X 12.x --(XMO1*- 13 db. t Table 9. End1 Reflection of Plate ob CellAbsobbebs Percentage1 free area of absorber!............................ '50 ; 40: 3 25 20 Attenuation^db.. ...j..............;...... .----- 1. . ,4 .5 , 6 Fio. 7. Absorption Plenums With and Without Sound Cells Case i. (Two 1 in. splitter plates, 3 channels each 20 in. X in.). From Equation 6, 46.7 R-- 12.6 X 12 X --rz X 4.4011 = 29 db. 66.7. . Additional attenuation may be obtained by using additional Bplitter plates or use of egg-crate arrangement of absorbing material and application of Equation 6. Plenum Absorption In systems, where individual ducts are directed to a number of rooms and sound treatment is required in every duct, a sound absorption plenum on the fan discharge as shown in Fig. 7 will often prove the most economical arrangement. The absorption in the plenum may be approximated by Equation 7. db (Attenuation) 10 logio Plenum Absorption in Sabins Area Fan Discharge (7) , The area of the plenum should be at least ten times as great as the fan discharge area. The. plenum should be lined With 2 in. of muslin covered rock wool blanket, or 1 in. sound absorbing board preferably nailed to wood strips on the inside of the plenum. With such a lining, the plenum is particularly effective in reducing low frequency fan noise. The absorp tion of the-plenum in sabins is the sum of the products of. each interior area of the plenum measured in square feet multiplied by its corresponding absorption coefficient. Outlet Sound Absorbers Outlet sound absorbers are rectangular or plate cells installed directly behind ah outlet or they may be the lining of a pan or plaque outlet'. They are particularly effective in the elimination of high frequency whistles which are generated by air flow in the ducts. They are also employed in large systems with long runs where only a few outlets near the fan require treatment. Frequently outlet cells are the only means of correcting existing noisy installations, as the duct sections directly behind the .outlets may be the only sections accessible for treatment.'.. (See Fig. 8). AIR SUPPLY OPENING NOISES ` . When air is'introduced into a room through a grille or register at a constant velocity, sound energy'is being introduced into the enclosure At y