PERMIT NO. NPDES - IA-000^1 (NON-COMPLIANCE REPORT)
eporllng Period: 3/18-24/84
' :
fflucnl
Lb*./Day
treom Effluent
Discharge
lo. Charocterhtio Limitation
001 pH (units)
6-9
-
/
----
**
,
Lbs./Day Effluent Devialion
+0.4
+0,4
*
.:
Date of Time of
Devfollon Deviation
3/19
4:30 p.m.
*
*
3/23
3:03 a.m.
,
Reaion or Explanation
March 29, 1984
--1----------------------------------------- r
ctmn-*
| tn
(2 hr. 19 min.) While washing a weak caustic storage
tank to a recovery sump, the drain basin at the tank
plugged with solids and overflowed to an adjacent
storm runoff sewer which discharges downstream of our
pH neutralization system. A change in operating
procedures has been implemented to have the retention*
gate in the storm sewer closed during washing out of area tanks.
-
(1 hr. 8 min.)-Misinterpretation of instructions i . regarding the clearing of a caustic product storage tanl for essential maintenance resulted in caustic reaching Outfall 001 downstream of the pH neutralization system. To prevent future occurrences, the necessity of effective communication will be stressed in a group session with unit operators ip April.
t irw-
/ CJ
h
I certify under penalty of law that I have personally examined and am familiar with the information submitted
in this document and all attachments and that, based
on mv inauirv of those individuals immediately responsible for obtaininq the information. I believe
that the information is true, accurate, and complete. and I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment. *
, PPG INDUSTRIES, INC.,..^AKE CHARLES, LA. PERMIT NO. NPDES - LA-000qj( {NON-COMPLIANCE REPORT)
eportlng Period:
3/11 "17784
*
fflucnf
Lbs./Doy
(ream Effluent
Discharge
Jo. Characteristic Limitation
001 pH (units) 6-9
~CD5
'
pH (units)
6-9
Lbi./Day Effluent Deviolion
+0.3
+0.2
Dote of Time of
Devlalton Deviation
3/11
2:53 p.m.
3/11
.
*
March 21. 1984
Reason or-
Explonotion
i
(62 min.) Abnormal process conditions resulted in
surge of alkaline wastewater which temporarily depleted
the acid reagent supply.
*
Investigation by PPG personnel failed to*determine the reason for-this excursion. Subsequent samples taken have all been within the NPDES permit limits.
*
"
`
>
.(
--- i1
*
i
oo
^
\ VJL,S
- a-sTs^
)
*
t
*
'I certify under penalty of law that I have personally
examined and am familiar with the information submitted
in this document and all attachments and that, based
on my inquiry of those individuals immediately
responsible for obtaining the information. I believe
that the information is true, accurate, and complete.
and I am aware that there are significant oenalties for
submitting false information, including the possibility
of fine and impri sonnfient.
*
. *
t w II I vw>i Iikikjf I I <v.
C v.1 tnni.LJj Lrt,
PERMIT NO. NPDES - IA-000(|^ (NON-COMPLIANCE REPORT)
eporllng Period; 3/4-10/84
. March 12, 1984
fflucnl treom Jo.
001
lbs,/Day
Effluent
Discharge
Cliorocterlstlo Limitation
pH 6-9
(also a
Lbj./Doy
Effluent Date of Time of Reason or
Deviation Deviation Devlotion Explanation
+1.2
3/7 2:57 p.m (100 min.l "Upset" condition: this incident occurred
+2,6 violation of maxirum)
as a result of a partial power failure in the Complex
(fault developed on 13.8 KV bus) which shutdown numerous
pumps, instrument air, and other equipment causing both .
an abnormal amount of caustic to be discharged to the pH control system and at the same time loss of acid for
neutralization. -This excursion was reported as an "upsei to R. 5. Rameshof Region VI EPA by phone on 3/8/84.
001 pH
6-9 +0.8
3/8 10:42 p.m. (62 min.) Mechanical failure of an agitator in the i Caustic Dept, caused salt to plug a line resulting in a discharge of caustic which exceeded the capacity of the pH neutralization system. Design has begun on a system
to contain.any such future discharge.
V.
I certify under penalty of law that I have personally
examined and am familiar with the information submitted
in this document and all attachments and that, based
on mv inquiry of those individuals immediately responsible for obtaining the information. 1 believe
that the information is true, accurate, and complete,
and 1 am aware that there are significant penalties for
submitting false information, including the possibility
of fine and imprisonment.
_________________ __________