American Society of Heating and Ventilating Engineers Guide, 1928
Table 6-H. Coefficients of Transmission (U) of Various Types of Masonry Wall Construction
Note.--These coefficients are expressed in B.t.u. per hour per square foot per i deg. fahr. difference in temperature between the air on the two sides and are based on an outside wind exposure of 15 miles per hour.
4" CUT STOOE VE.UEE.C. OKI CoUCfcETE WALLS
The values cf U in this Table are baaed on the
/bUowmq Internal Conductivities (C) which are expressed m B.t.u. per Ur. per Sq.ft, per l* f
Stone
10.00 per t'
Concrete (Stone Ul'.4 mix) &W per I'
Cement Mortar Plaster Board Plaster (.Gypsum)
8.00 per f ' 3.04 per f
l.'il per l'
Wood Lath f Plaster Cork board
2.00 as applied 0.30 per 1*
fiber Insulation (board/brm)' 033 per l*
Cellular Cypsum (18*)
0.59 per l'
Powdered Cypsum (26*) .
0.52 per
W all Uumber
Y-Thickrtess qf Insulation where specified Interior Construction
78 Plain Waite - Uo Interior finish
7^ Plaster on Concrete
Thickness o/ Concrete -X.
Y (o' a.
6* 10* u* 16*
bc d e
0.454 6.41$ 0.377 0.345 0.296
0418 0.380 0.348 0.321 0.279
80 J Plaster on Uefcal Lath - Purred
0.251 0.236 0.-224 0.212 0.193
81 Plaster on Wood Lath - furred
O.Z40 0227 0.215 0.204 0.186
82
i* * T Plaster on % Plaster Board - Purred
Plaster on Wood Lath on 2* Furrinq 83
Strips -Cellulur Cypsum Pill ^
plaster on Wood Lath on. Z* Furrinq 84 strips - Powdered Gypsum f\U
85 5i"* Piaster on Fiber Insulation -- (Board form) purred
86
87 Plaster.on Cork board.. 5et In fi. 88 Cement Mortac
0.249 0.235 0.223 0.211 0,192
%
yii 0.184 -0.176 0.169 0.163 0.151
V
0172 0.166 0.159 0.153 .0-143.
yi 0.185
i-- 0.145
0.177 0.170 0.140 0.135
0.163 0.151 0.131 0,123
tVz 0.134; 0.130 0.126 . 0.122 o.n'6
T 0.110 0.107 0.104 0.102 0.047
Based on in., the actual thickness of 2 in. furring strips.
28
Chapter I--Calculating the Heat Losses from Buildings
Table 6-1. Coefficients of Transmission (U) of Various Types of Masonry Wall Construction
tfofgj---These coefficients are expressed in B.Lu. per hour per square foot per I deg. fahr. difference in temperature between the air on the two sides and are based on an outside wind exposure of 15 miles per hour.
CchJchete Walls
WITH
.t Stucco AS EXTE.(210(1. flMlSH
The values of U in this Table are based on the
following Internal Conductivities (C) which are
etpressed in &ta. per I4r. per'Sg.Ft. .per lF
Stucco
. 800 per 1*
Concrete (Stone 1:2:4 mu) 8.10 per !'
Plaster board
3.04 per f
Plaster (Gypsum') Wood Lath 4 Plaster
2.12 per I" 2.00 as applied
CorL board
0.10 per l`
fiber. Insulotion (fcoard/brm)
0.11 per 1'
Cellular Gypsum (18*)
0.54 per P
Powdered Gypsum (26*)
0.52 per 1
4
V;' . * te,
Y- Thictness of Insulation where speci/ied
__S> -2 e
interior Construction
Y
r stucco oo
Wire
--
Thickness of Concrete - X
6" . 8' 10- ir a bcd
16' 20' eF
89 .Plain Walls - Uo Interior Finish
0.515 0.481- 6.431 0.391 0.329 0.284
90 & Plaster on Concrete
0465 0.437 0.395 0.361 0.308 0.268
91 % Plaster on Metal Lath - Furred .
0.267 0:257 0.242 0.229 0.206 0.231
92 14 Plaster on Wood lath - Purred
0.254 0.246 0.232 0.220 0.199 0.181
93 Vi Plaster on % Plaster board - Furred
0.265 0.256 .0.241 0.228 0.205 0.187
*
94
& Plaster on Wood Lath on 2*Furrinq Strips - Cellular Gypsum Fill
l* 0.193 0.188 0.179 0.172 0.159 0.148-
+
95
ft Plaster on Wood Lath on Z* Furrwq Strips - Powdered Cypsum Fill
i%
0.180 0.175
0.168 0.162 0:150 6:140
96 YL Plaster on Fiber Insulation (board form) Furred
97
98 Plaster on CorL board set m 'A Cement Mortar
99
Vi 0.194 0.189 0.180 0.173 0.160 0.148
f 0.150 0.147 0.142 0.137 0126 0.121 lit' 0.138 0.136 0.132 0.127 0.120 0.114 2" 0.113 0.1 El 0.106 0.105 0.106 0.046
Based on 1% in., the actual thickness of 2 in. furring strips. fThe figures on this page may be used with sufficient accuracy for plain concrete walls without stucco.