Document k9YN010N8pnGQg0E5nwB5JaBO
698
CHAPTER 42
1965 Guide AndDqfaBook
minimum flow rates. Factors to be considered:in selection are freedom from plugging, the.effect,cm water eliministacni from the discharge air stream, and available pump characteristics.
Centrifugal pumps of moderate head are in general use. The' water passages of such pumps makes them adaptable to han dling ofextraneous matter found in open recirculatingsystems.
Continuous bleed-off,, with rates based on the condenser evaporation rate and t.h^ twHnfiaa of the make-up wafer, are necessary to prevent an-increase in the concentration of solids and consequent precipitation of scale on the coil. Scale decreases the heat transmission through the coil surface and may reduce the air flow.: A bleed line from tire pump discharge or a means, of removing a portion of the water draining from
the coil maybe used.
Air How'
Although gravity circulation is possible, most evaporative
condensers utilize forced circulation with a fan to either blow
or draw.air through the unit (see Fig. 26).
;The drawrthnnigh type provides more even air distribution
oyer the coil, but, unless tire elimination of moisture is com
pletely effective, the carryover of water particles will tend to
deposit scale on the fan blades, thereby causing operational difficulties. The location of bearings and the materials used in
the Ian construction should be given consideration because
of the high humidity of the leaving air stream.
Effective elimination of moisture from' the leaving air
stream is essential to prevent projection of mist which can -deposit moisture on surrounding surfaces. This is accom
plished by eliminator plates, which are closely spaced surfaces providing abrupt changes in air flow direction. Moisture parti
cles are deposited on these surfaces and drained back to the
sump.
..... -
' If the air inlet is located near the sump, louvers may be
required to prevent water from splashing out of the unit as-it
drains off the coil.
''
Heat Transfer Process
!
Thatemperature relationship between the refrigerant-in the coil, the water temperature, and the air wet-buffi- tempera ture at different points within the evaporative condenser is shown in fig. 27. The heat transfer in an evaporative con denser occurs in two different processes.
-Heat first flows from the condensing refrigerant through the coil surface'and water film to the air-water interface. This brat flow depends upon the temperature difference and can be expressed as:
.
Q =. UA&1+,
\-
' (5)
where-
.- <7..s?'heat,flow, Btu per hour..
U -- coefficient of heat transfer, Btu per (hour).(square foot)
(Fahrenheit degree).
. ' 'A = coil, surface area, square feet. -
'
dim, ** mean effective- temperature difference between tefriger-
-ant and air-water interface Fahrenheit degrees. -.
- Between the air-water interface, and the air stream passiog
over the condenser, there, is both a heat transfer and smaa
transfer of water vapor. The mass transfer is accompanied by
an evaporation of the water so that the latent heat of vapori
sation is supplied to this water.
.
As shown in Chapter. 5, Mass Transfer, the sensible whd
latent transfer can be combined with the enthalpy potential
as the driving force for both, such.that:
Q - K^AAh.
(6)
tehett
. " mean effective, enthalpy difference between the air
stream enthalpy and the interface saturation state
enthalpy.
*
Derivation of Equation 6 relies upon the,'validity of the Lewis'relationship:
\/Km =
(7)
''Fig. 26 ..., Functional View of Evaporative Condenser -
Condenser*'
699
This relationship states that the ratio of the air side heat transfer' coefficient A, to the mass transfer coefficient Km equals' the humid specific heat of the air stream Cpm in Btu per (Fahrenheit degree) (pound of dry air). The Lewis relation ship is us"d to compute mass transfer coefficients'from a knowledge of the air film coefficients and the specific'heat
Values for V can be calculated by the resistance concept from data on refrigerants condensing intide tubes, water sprayed over tubes, and tube conductivity.' Because inade quate data are available on the first two items, V generally is determined experimentally.
Values for K^-generaDy are determined experimentally. A method of calculating _ is given in Chapter 5.
Establishing U and Km experimentally involves difficult interface temperature measurements. An indirect means is available. Referring to Fig. 28, plot the entering and leaving air specific enthalpy on a psychrometric chart and extend the line connecting.them to intersect the saturation line. Tins establishes an'average effective interface temperature Um- U can now be determined from Equation 5 if it is assumed that:
' aw-U-fc-
(8)
wftcre
Um m average saturated condensing temperature, Fahrenheit.
fe. = average effective interface temperature, Fahrenheit. Km " can be determined from Equation 6 if
dhm P him -- hem
(9)
toftoe
him = specific enthalpy of sir at Ca, Btu per pound. hem " average opeoinc enthalpy of air etreampBtu per pound.
- A very complex brat transfer mechanism is involved. In addition to being sensitive to the normal variables of loading and mass flow, transfer rates are also sensitive to changes in entering air wet-bulb temperatures which 'affect' water- film temperature, gradient and the accuracy of the calculated mean effective specific enthalpy difference.
Comparison of Atmospheric Heat Rejection Equip ment
Heat may be rejected to the atmosphere from condensing refrigerant by an evaporative condenser, a water-cooled
27 .... Heat:Transfer. DxtigrcBosfar an Evaporative Condenser-.:.,,
Fig. 28 .... Psychrometric Diagram for an -. Evaporative Condenser
condenser, a combination of water-cooled condenser and cooling tower, or an air-cooled condenser.'
When evaporation is part of the heat transfer process, ambient air has a high heat absorbing capacity. Therefore, by comparison' with ah air-cooled condenser, ah evaporative condenser has a lower condensing temperature and compact ness, due to lower requirements of coil surface and air flow.
While both the water-cooled condenser-cooling tower com bination and the evaporative condenser operate with evapora tion of water, there is an additional non-evaporative transfer of heat to tiie circulating water in the water-cooled condenser; cooling tower combination which raises its operating tempera ture levels and heat transfer surface requirements.
Ratings
Manufacturers customarily rate evaporative condensers in tons of refrigeration as a function of entering air wet-bulb and saturated condensing temperature. Ratings specify a model size, refrigerant, -constant air flow, water flow, and suction pressure. Rating in terms of refrigeration effect is possible by specifying the operating conditions, and thus the heat rejec tion to the condenser. This effectively describes the refrigera tion system of which the evaporative condenser is a part. This operating condition is.likely to be based on the rating con dition set up by ARI to establish the nominal capacity of a unit.
Fig. 29 shows typical generalized performance curves where the 100 percent value is the unit nominal capacity. These curves are usually drawn for a specific suction pressure. Per formance at saturated suction preraures otherthan the con stant rating value is determined by the use of correction fac tors which are sometimes supplied in atabular form. Figs. 1,2, or 3 may also be used to correct for suction pressures other than the base suction pressure used on rating curves similar to Fig. 29.
Accessory Coils
Some manufacturers produce,subcooling and desuperheat coils.
A suboooling coil may be placed on the entering air side of the condensing coil to remove heat from condensed liquid refrigerant This increases refrigeration system capacity and is useful in preventing flashing of refrigerant ahead of the ex pansion device if an evaporator location is elevated above the condenser. The design differs from that of the condensing oral due to the lower heat transfer rate on the refrigerant side. :
A desuperheat coil may be placed on the leaving air side of the -condensing coil to remove beat from superheated, re frigerant vapor,-prior to condensing. Its greatest value .is in