Document k926zD42RzBn0Xd2NLe95b1LO
PLAINTIFF'S EXHIBIT
January 31, 1963
Public Service Co. of Colorado Engineering Department 5525 Seat 38th Ave Denver, Colorado
Attention! Mr. Fred Anderson
Ret Our Contract RB-251 & RB-295 Your units ho. 1 and Ho. 2 Cherokee station Gas Recirculation Plue
Dear Fredi
Attached please find two copies of drawings 668981-0 which have been narked to show the stiffening done on the gas recircula tion flues for Units Ho. 1 and Ho. 2 at Cherokee Station. Also, attached is a sketch shewing a few additional stiffeners to be instal led at the next outage for each unit in the flue where it enters the top of the boiler at the front. Originally this vibration seeswd fairly minor compared to the rest, but maw that the vibration in the general run of the flue has been eliminated, it seems more se vere. we suggest using 2" pipe for the stiffeners welded to the inside without disturbing the outside insulation and lagging.
You will note that drawings 66898X-0 was originally prepared
for adding the stiffeners on the Ho. 2 unit in the field before startup from the experience with the Ho. 1 unit. On the Ho. 2 unit we merely added stiffeners in the other direction, which seemed to
give a satisfactory Job. Zn all oases on the Ho. 2 unit pipe stif
feners were used.
On the drawing marked up for the Ho. 1 unit the only stiffeners that apply are the ones marked in red. Xf you have any questions
Very truly yours.
WAD00198
THE BABCOCK & WXLCOK COMPANY Denver District service Dept.
R. V. Mourer District Service Engineer
/HI BABCOCK * WILCOX CO.
m WAD00199
uvtomu
c n osr raio
iaubct Pfcj3postr> AlTFpaTi&M -To r,AS C.F.r.ifc.
Doer -- ^UDW/lsUk ADD IT1 Qhl nc TlC FtNFJLSu
-". ft-2^i l 'i <*<r
* J.F.C, pTM JAM.
3____