Document k6nXY370bvvNrgmyvEyYDx1rO
774
CHAPTER 56
1960 Guide
heated per day, and the maxm-mm amount which will be used
in any one hour, as well as the duration of the peak load. In where the requirements for hot water are reason-
ably uniform, as in residences, apartment buildings, hotels, and the like, smaller storage capacity is required than in the fjLa of factories, schools, and office buildings, where practi
cally the entire day's usage of hot water occurs during a very short period. Correspondingly, the beating capacity must be
proportionately greater with uniform usage of hot water than with intermittent usage where adequate storage can be
provided to carry over the momentary peak load. With inter mittent usage there may be several hours between peak de
mands during which the water in the storage tank can be brought up to temperature. As a general rule, it is desirable to have a large storage capacity in order that the beating
capacity, and consequently the size of the heater, or the load on the heating boiler, may be as small as possible.
In estimating the hot water which can be drawn from a
storage tank, it should be borne in mind that only about 70 percent of the volume of the tank is available, since, by the
time this quantity has been drawn off, the incoming cold water has cooled the remainder down to a point where it can
no longer be considered hot water. Where steam from the heating boiler is used to heat do
mestic hot water, the computed load on the boiler should be increased by 4 sq ft EDR (equivalent direct radiation) for
every gallon of water per hour heated through a 100 deg rise.
The actual requirement i3 (100 X 8.33)/240 = 3.48 sq ft per gal heated 100 deg. The value of 4 allows for transmission
losses. There are two methods in common use for estimating the
hot water requirements of a building: (1) by the number of
people, and (2) by the number of plumbing fixtures in stalled. Where the number of people to be served can be rea sonably estimated, the data in Table 11 may be used.
Example 3: Determine the heater size and storage tank capac ity for a residence housing five people.
Solution: From Table 11, a residence housing five people would have a daily requirement of 5 X 40 = 200 gal per day, and a maximum hourly demand of 200 X 1/7 -- 28.5 gal. The heater should have a storage capacity of 200 X 1/5 -- 40 gal, and a heating capacity of 200 X 1/7 = 285 gal per hr.
The conditions given in Example 3 may be cited as aver age. It is possible to vary the storage and heating capacity by
increasing and decreasing one over the other. Such a condi tion is illustrated in Example 4-
Example 4-' Determine the required heater capacity for an apartment housing 200 people, if the storage tank has a capac ity of 1000 gal. What heater capacity will be required if the storage tank is changed to 2500 gal capacity?
Solution.* Assume an apartment house housing 200 people. From the data in Table 11; Daily requirements -- 200 X 40 = 8000 gal. Maximum hours demand ~ 8000 X 1/7 -- 1140 gal. 'Duration of peak load = 4 hr. Water required for 4-hr peak = 4 X 1140 = 4560.
If a 1000-gal storage tank is used, hot water available from the tank -- 1000 X 0.70 = 700. Water to be heated in 4 hr = 4560 -- 700 -- 3880 gal. Heating capacity per hour -- 3860/4 ~ 965 gal.
If instead of a 1000-gal tank, a 2500-gal tank had been in stalled, the required-beating capacity per hour would be-[4560 -- (2500 X 0.7Q)J/4 = 688 gal.
Table 12 may be used to determine the size of water heat ing equipment from the number of fixtures. To obtain the
probable maximum demand, multiply the total quantity for
the fixtures by the demand factor in line 19. The heater or' coil should have a water heating capacity equal to this prob
able maximum demand. The storage tank should have a capacity equal to the probable maximum demand multiplied by the storage capacity factor in line 20. Example 5 will illustrate the procedure.
Example 5: Determination of heater and storage tank size for an apartment building from number of fixtures.
60 lavatories................................................ X 2 = 120 gal per hr 30 bathtubs.................................................. X 20 - 600 gal per hr 30 showers.................................................... X 75 = 2250 gal per hr 60 kitchen sinks........................................ X 10 = . 600 gal per hr 15 laundry tubs......................................... X 20 " 300galperhr
Possible maximum demand................ Probable maximum demand..............
Heater or coil capacity......................... Storage tank capacity...........................
= 3870 gal per hr ** 3870 X 0.30 = 1161 gal per hr ** 1161 gal per hr -- 1161 X 1.25 = 1450 gal
Although, in private dwellings a water.temperature of 140 F
is reasonable for dishwashing, in public places sanitation
regulations make 180 F water mandatory in the rinsing cycle.
Thus the hot water requirements for food service establish
ments present special problems, due to the need for two
water temperatures. The lower temperature water is dis
tributed for general use, but the 180 F water should be con
fined to the equipment requiring it, and should be obtained by
boosting the temperature at that point. It would be danger
ous to distribute 180 F water for general use.
The U. S. Public Health Service, the National Sanitation
Foundation, and other health and sanitation organizations
have formulated rules and standards of cleanliness for com
mercial food service establishments. Certain of these rules as-
siime that the dishes in public eating places are sufficiently
free of bacteria. The National Sanitation Foundation has pub
lished standards for the design of dishwashing machines and
water heaters used by restaurants.
In a restaurant, bacteria kill is usually achieved by exposing
the washed dish to a rinse of 180 F water for several seconds.
In addition, an ample supply of general purpose hot water,
usually 140-150 F, is required for the wash cycle of dishwash
ers, as well as for personal use, pot washing, general cleaning
and other restaurant uses.
In order to correctly size a water heating system it is neces
sary to determine:
,,
1. Types and rises of dishwashers used.
2. Required quantity of general purpose hot water (manu facturers' data,should be consulted to determine the initial fill requirements of the wash tanks).
3. Duration of peak hot water demand period. 4. Inlet water temperature. 5. Type and capacity of n*i<Amg water heating system.
6. Type of water heating system desired.
The American Gas Association has published a recom mended procedure* for siring gas-fired water heaters for res taurants. This procedure is discussed in the following para graphs.
Table 13 is used to size the required heater or heaters after .allowance has been made for the quantity of hot water that may be withdrawn from the storage tank each hour. The gen eral purpose and 180 F water requirements are determined from Tables 14 and 15.
To determine the quantity, in gallons per hour, of usable hot water from storage, the duration, in hours, of consecu-
Water Services
Table 13.... Gas Input Requirements for Heating Water*
Temperature kite, Deg F
Wafer Requirements, gph
40
50
60
70 00
00
,00
no
Gas input Required, tn Thousands of Bfw per Hour
25 12 15 IS ' 50 24 30 36 75 36 45 54 100 48 60 72
125 60 75 90 150 72 90 108 175 84 105 126 200 96 120 144
225 108 135 162 250 120 150 180 275 132 165 198 300 144 180 216
325 156 195 234 350 168 210 252 375 180 225 270 400 192 240 288
425 204 255 306 450 216 270 324 475 228 285 342 500 240 300 360
525 252 315 378 550 264 330 396 575 276 345 414 600 288 360 432
650 312 390 468 700 336 420 *504 750 360 450 540 800 384 480 576
850 408 510 612 900 432 540 648 950 456 570 684 1000 480 600 720
Values extracted from Reference *. * Supply water pressure assumed to be tO pexf.
21 42 63 84
105 128 147 168
189 210 231 252
273 294 315 336
357 378 399 420
441 462 483 -504
546 58$ 630 672
714 756 798 840
24 48 72 96
120 144 168 192
216 240 264 288
312 336 360 384
408 432 456 480
504 528 552 576
624 672 720 768^-
816 864 912 960
27 54 81 108
135 162 189 216
243 270 297 324
351 378 ' 405432
459 486 513 540
567 594 621 648
702 756 810 864
918 972 1026 1080
30 60 90 120
150 180 210 240
270 300 330 360
390 420 450 480
510 540 570 600
630 660 690 720
780 840 900 960
1020 1080 1140 1200
33 66 99 132
165 198 231 264
297 330 363 396
429 462 495 528
561 594 627 660
693 726 759 792
858 924 990 1056
1122 1188 1254 1320
,20
36 72 108 144
180 216 252 288
324 360 396 432
468 504 540 576
612 648 684 720
756 792 828 864
936 1008 1080 1152
1224 1296 1368 1440
775
,20 uo
39 78 117 156
195 234 273 312
351 390 429 468
507 546 585 624
663 702 741 780
819 858 897 936
1014 1092 1170 1248
1326 1404 1482 1560
42 84 126 168
210 252 294 336
378 420 462 504
546 . 588
630 672
714 756 798 840
882 924 966 1008
1092 1176 1260 1344
1428 1512 1596 1680
Table l 4 .... Rinse Water (180 F) Requirements for Dishwashing Machines*
Type and Sire of Dishwasher
flow Koto, gpm
Hot Wafer Requirements, geflon* per hour of 180 F
Heaters With no internal Storage*
Heaters With tntemal
Storage to Meet gpm Row Demand*
Door type, 16 x 16 in. rack................ ...........................
18 x 18 in. rack............................................ 20 x 20 in. rack............................................ undercounter type......................................
Conveyor type single tank.............................................
multiple tank (dishes flat)................. multiple tank (dishes inclined).........
Silver washer*
Utensil washers.............................
.....................
Make-up water requirements.........................................
Value* extracted from Refereaoe S.
* Flow pruwiiik at dishwashers is b Based on the (pm Bow rate.
--d to be SO petg.
* Based oo dishwasher operation at 100 percent of mechanical capacity.
6.94 8.67 10.4 5
6.94 5.78 4.62
7 8 2.31
416 520 624 300
416 347 277
420 480 139
69 87 104 70
416 347 277
45 75 139