Document k6jBzZBK1gm80Jdmegbe0v9EB
Ratings & Data of
Discontinued American - cvtai?dai>d Boilers & Radiators
Units Manufactured From 1898 to 1956
I 20510
FOREWORD
- - Boilers prior to 1925, but including the Ideal Arco Round Boiler (1925 - 1929)> Ideal Type "A"' Boiler (1925)> and Ideal Yonda Sectional and Smokeless Boilers (1925), were rated on the basis of gross output with allowance for piping loss.
The Ideal Assembled Sectional Boiler (1924) was rated in a different manner, with Recommended Load including piping shown in Sq. Ft. E.D.R. This constitutes the dividing Line between "Gross Output"' ratings with allowance for piping loss and current "Net Installed Radiation" ratings which include allowances for normal piping (covered) and Pick up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
In replacing any boiler, the actual heating requirements of the installation should first be determined, since, as has been pointed out, printed ratings have varied from time to time with changes in Boiler Manufacturers' methods of rating their products; whether on new or replacement work, the chief consideration is that "Sufficient Radiation must be installed for the Requirements of the Building". If, because of additional loads placed on the boiler since its installation, it is of insufficient size to take care of the job, it is now even more important that the replace ment be correctly sized in accordance with present-day standards to insure satisfaction.
20511
2
IDEAL SECTIONAL BOILER (1898 - 1906) 30" & 40"
Boiler No.
502 or 512 602 or 612 702 or 712
084 or 184 085 or 185 086 or 186 087 or 187 088 <jr 188 045 or 245 046 or 246 047 or 247 048 or 248 049 or 249 050 or 250 051 or 251
STEAM
`Load Inc.
Rating
Piping
- -225 300
375
188 250
314
375 500 625
750 900 900 1100 1300 1500 1700 1900
2100
314 420 520 630
750
750 920 1090 1250 1420
1590
1750
HOT WATER
`Load Inc.
Rating
Piping
375 313 500 420
625 520
625
825
1025 1250 1250 1500 1825 2150
2475
2775 3100
3450
520 690
855 1045
1045 1250 1520
1790 2060 2320 2590 2880
Grate Area Sq, Ft
1.2 1.5 1.8
2.25 3.00 3-75 4.50 5.25 5.00 6.00 7.1 8.2 10.0 7.1 8.2
Water Line Inches
43 43 43
44 44 44 44 44 50 50 50 50 50 50 50
602 or 62 603 or 63 604 or 64
605 or 65 606 or 66
703 or 73 704 or 74
705 or 75 706 or 76
1000 1200 1400 1600 1800 2000 2300 26 00 2800
835 1000 1170
1340 1500
1670 1920 2170 2340
1650 2000
2350 2700 3050 3500 4000 4500 5000
1380 1670 1960 2260
2550 2920 3340 3760 4180
6.2 6.2
7.5 8.7 10.1 10.1 12.1 14.1 16.1
58 58 58 58 58 58 58 58 58
IDEAL PORTABLE ROUND (1898 - 1906)
103 or 14
104 or 15
203 or 24
204 or 25 205 or 26
303 or 35 304 or 36
305 or 37 403 or 45 404 or 46
405 or 47 504 or 46
505 or 57
506 or 58
13
34 44
55
300
350 400
450 500 550 600 650 850 1000 1100 1300 1500 1700
250 292
334 376 418 460 500 544 710
835 920
1085 1252 1420
400 450
550 625 675 875 975 1100 1400 1600 1700 2000 2250 2400
350
775 1200
1775
334 376 460 522
565 730 815 920 1170 1340 1420 1670 1880 2000 292
647 1000 1480
1.97
1.97 2.4 2.4 2.4
3.4 3-4 3-4 4.9 4.9 4.9 7.1 7.1 7.1 1.97 3-4 4.9 7.1
41 46-1/2 42 48-1/4 54-1/2 43-1/2 50-1/4
57 45 52 59 53 61
69
IDEAL JUNIOR BOILER (1898 - 1908)
201 301 302
1500 or 1501 1600 or 1601 1800 or 1801 1900 or 1901
175 250 300 300
340
525
575
146
209 250 250
284 440 180
`The highest ratings listed are taken.
1.22
46
1.76
46
1.76
50
500
420
1.22
48-1/4
600
500
1.22
52-1/4
875 900
730 750
1.76 1.76
48-3/8 52-3/8
An allowance for piping has been made on these loads.
20512
Boiler No.
16 18 20 120 113 or 130 114 223 or 230 224 or 240 225 333 or 330 334 or 340 335 443 or 430 444 or 440 445 or 450 554 or 530 555 or 540 556 or 550
IDEAL INVINCIBLE BOILER (1898 - 1908)
Rating
STEAM `Load Inc. Piping
350 '500 650
225
325 375 425 475 545 615 800 900 1000 1150 1350 1500
250 360 465
161 197 232 268 304 340 390 440 570 645 715 820 965 1070
HOT WATER
`Load Inc.
Rating
Piping
550 800 1050 375 425
600 675
850 1000
1250 1500 1650 1825 2150 2400
395 570 750 268 304
430 485
610 715
895 1070 1180 1300 1540 1720
3
Grate Area So. Ft.
Tnrhec
1.4 1.76 2.18
1.97 1.97 1.97 2.4 2.4 2.4 3.4 3-4 3.4
4.9 4.9 4.9 7.1 7.1 7.1
38-1/2 39-3/4 41
41 46-1/2 42 48-1/4 54-1/2 43-1/2 50-1/4 57 45 52 59 53 61 69
A or C-015 or 152 A or C-018 or 182
A or C-019 or 183 A or C-020 or 211 A or C-021 or 212
A or C-022 or 213 A or C-024 or 241
A or C-025 or 242
A or C-026 or 243 A or C-027 or 281
A or C-028 or 282
A or C-029 or 283 A or C-031 or 321 A or C-032 or 322 A or C-033 or 323
IDEAL PREMIER ROUND BOILER (1900 - 1908) (HARD COAL)
225 300
375 400 450 500
550 610 670 850
925 1000 1100 1200 1300
188 250
313 334 376 418 460 510 560 710 770
835 920 1000
1085
375 500
600
660
750
825 900 1000 1100
1400
1525 1650
1825 2000 2150
313 418 500
550 625 690
750
835 920 1170
1275 1380
1525 1670
1795
I.23
1.77 1.77 2.4 2.4 2.4
3.14 3-14 3.14
4-3 4.3 4.3 5-6 5.6 5.6
49-1/2 52-1/2
57 47-1/2
53 58-1/2
49 54 59-1/2
51 57-1/4 63-3/4 53-1/4 60 66-1/4
IDEAL PREMIER ROUND BOILER (SOFT COAL) (1900 - 1906)
or D-015 or 152 or D-018 or 182 or B-021 or 212 or D-022 or 213 or D-025 or 242 or D-026 or 243 or D-028 or 282
or D-029 or 283 or D--032 or 322
or 0-033 or 323
200 250 400
450 500
600
800 900 1050 1200
167 209 334
375 418 500 670
750
875 1000
325 400 650
750
825 1000
1325 1500
1725 2000
270 334 542
625 690
835 1105 1250
1440 1670
1.23 1.77 2.4 2.4
3-14 3.14
4.27 4.27 5.6 5.6
49-1/4 52-1/2
53 58-1/4
54 59-1/2 57-1/4
63-3/4 60 66-1/4
`The highest ratings listed are taken. An allowance for piping has been made on these loads.
20513
4 HEAL SECTIONAL BOILER (1900 - 1904)
Boiler No.
065 or #5 066 or 366 067 or 367 068 or 368 069 or 369 0610 or 3610 0611 or 3611 0612 or 3612 0613 or 3613
15-1-w 15-2^W
17-3-W 17-4-W 17-5-W 19-3-W 19-4-W 19-5-W 22-3-W 22-4-W 22-5-W
25-3-w
25-4-W 25-5-w 28-3-Vf 28-4-W 28-5-W
31-3-w 31-4-W 31-5-w
34-3-w 34-4-W 34-5-W
Rating
STEAM *Load Inc. Piping
HOT WATER
*Load Inc.
Rating
Piping
1800 2250 2700
3150 3600 3250 3600 3950 4300
1500
1880
2260
2630
3000
2720
3000
3300
36 00
3000
3700 4450
5200
5950 5350 5925 6500
7075
2500 3100
3720
4350 4970 4460
4925 5420
5900
IDEAL STANDARD WATER BOILER U904 - 1909)
400
425
500
550 600
750 825
900
875 950
1025
1250
1350 1425
1500
1600
1700
1750 1950
2050
2350
2500 26 50
334
355 420
460
500
625
690
750 730
795
855 1040
1130 1190 1250
1340
1420
1460
1630
1710
I960 2090
2210
Sq. Ft.
8.U 10.0 12.0 14.0 16.0 14.0 16.0 16.0 16.0
1.06 1.06 1.40 1.40 1.40 1.76 1.76 1.76 2.40 2.40 2.40 3-44 3-44 3.44 4.12 4.12 4.12 4.90 4.90 4.90 5-94 5-94 5*94
Water I j nc
Inches
61 61 61 61 61 61 61 61 61
ACME FIRE BOX BOILER (1904 - 1914)
1 900 835 1400 1300 4.3 51
2
1000
925
1600 1480 5-3 51
3
1200
1110
1900 1760 6.3 51
4
1400
1300
2200 2040 6.7 56
5
1700
1570
2700
2500
8.0
56
6
2100
1940
3400 3150 9.2 56
7
2200
2040
3500 3240 9.5 6l
8
2500
2320
4000
3700
11.0
61
9
10
2900
3200
2680 2960
46 00
5100
4250 4720
12.5 13.0
61
66
11
3800
3520
6100
5650
14.7
66
12
4400
4070
7000
6500
16.4
66
13 14
4900 5800
4540 5360
7800 9300
7210 86 00
18.6 20.6
68 68
IDEAL RETURN FLUE PORTABLE STEEL 1BOILER (1904)
1200 1500
1200 1500
1110 1390
1800 2100 26 00 3000 3500 4500
1800 2100 2600 3000 3500 4500
1670 1940 2400 2780 3240 4160
`He highest ratings listed are taken.
2000
2475 2975 3475 4300
4950 5775 7425
1850 2290
2750 3220 3980 4580
5350 6850
7.5 9.0 9*0
12.0 12.2 14.0
15.7 17.5
67 67 67
67 77 77 n7r7? 77
An allowance for piping has been ade on these loads.
20514
Boiler No.
S or W-2-4 S or W-2-5 S or W-2-6 S or W-2-7 S or H-3-5 S or W-3-6 S or W-3-7 S or W-4-5 S or W-4-6 S or W-4-7 S or W-5-5 S or W-5-6 S or W-5-7 S or W-5-8 S or W--5-9
Rating
- -225 300 375 450 500 600 700 800
1000 1200 1400 1700 2000 2300 26 00
IDEAL COKE BOILER (1904 - 1906)
STEAM `Load Inc. Piping
HOT WATER
'Load Inc.
Rating
Piping
188 250
313 376
418 500
585 670
835 1000 1170 1420 1670 1920 2170
375 500 625
750
825 1000 1150
1325 1650 2000
2325 2800
3300 3800 4300
313 418 522
625 690
835 960
1105 1380 1670 1940 2340 2760 3170 3600
Grate Area Sq. Ft
1.05 1.46 1.82 2.18 2.1 2.6
3.1 3-4
4.3 5.1 5-0 6.2
7.5 8.8 10.0
Inches
45-1/2 45-1/2 45-1/2 45-1/2 47 47 47 57-1/2 57-1/2 57-1/2 64 64 64 64 64
T-30-S or W T-33-S or W T-3S-S or W T-44-S or W T-50-S or W T-56-S or W T-62-S or W T-68-S or W
250
325
385 535 700 900 1125
1575
IDEAL PERFECTION BOILER (1905)
179 400 286
232 525 376
275 635 455
383 680 486
500 1155
825
645 1485 1060
805 1860 1330
985 2270 1620
1.2 42 1.6 4J-1/4 2.0 4`J-l/2 2.6 45-3/8
3.4 45-3/4 4.3 46-3/8 5-2 46-5/8 6.3 46-7/8
1-19-S or W 1-22-S or W 1-25-S or W 1-28-S or VT 1-31-S or W 1-34-S or K
** IDEAL ARC0 ROUND BOILER (SOFT COAL) (1906 - 19 09)
275 400 500 800
1000 1250
229 332
415 665
835 1040
450 650 825 1325 1650
2075
375 540
685 1100
1375 1730
"Equipped with First Pattern Arco Base
1.76 2.40 3.14 4.12 4.90 5*94
45-1/2
49 49-1/4 50 52-1/2 54-3/4
2-19-S or W 3-19-S or W 2-22-S or W 3-22-S or W 2-25-S or W 3-25-S or W 2-28-S or W 3-28-S or W 2-31-S or W 3-31-S or W 2-34-S or W 3-34-S or W
* IDEAL AR00 ROUND BOILER (SOFT COAL) (1906 - 1909)
350 400
525 575 625 700 900 1000
1275 1400 1500
1650
292 332
437 480 520 582
750
835 1060
1165 1250
1370
575 650
875 950 1025 1150 1500
1650 2100
2325
2475 27 25
480 540
730 790 850
955 1250 1370 1750 1940 2060 2280
1.76 1.76 2.40 2.40 3.14 3.14 4.12 4.12 4.90 4.90
55C ..99C44iA
50 54-1/2
53-1/2 56-7/8 54-1/4 59-1/4
56 61-3/4 57-1/4 63-1/4 59-3/8
65-1/2
"Equipped with First Pattern Arco Base
Hie highest ratings listed are taken. An allowance for piping has been made on these loads.
20515
6
Boiler No. S or W-36-5 S or W-36-6 S or W-36-7 S or W-36-8 S or W-36-9
Rating
21U0 2625 3150 3675 4200
IDEAL SECTIONAL BOIIR (1904 - 1925)
`Load Inc. Piping
1640 2050 2460 2860 3280
Rating
3450 4325 5200 6050 6925
`Load Inc. Piping
2700 3380 4050 4720 5440
Grate Area Sq. Ft.
9.12 11.4 13.7 16.0 18.2
Water Line Inches
60-3/4 60-3/4 60-3/4 60-3/4 60-3/4
S or W-30-5 S or W-30-6 S or W-30-7 S or W-30-8
1275 1625 1975 2325
1000 1270 1540 1820
1904 - 1906
2100 2675 3250 3825
1640 2080 2540 2980
8.9 10.9 12.8
14.7
60-1/2 60-1/2 60-1/2 60-1/2
S or W-28-5 S or W-28-6
S or W-28-7 S or W-28-8
1300 1625 1950 2275
1015 1270 1520 1780
1904 - 1925
2150 2675 3200 3725
1680
2080 2500 2900
6.24 7.80
9.36 10.92
53-3/8 53-3/8 53-3/8 53-3/8
S or W-25-5 S or W-25-6
S or W-25-7 S or W-25-8
1100 1350 1600 1850
860
1055 1250 1440
1909 - 1925
1825 2225 26 50 3050
1420 1740
2065 2380
5.44 6.80 8.16
9.52
51 51 51
51
S or W-22-5 S or W-22-6
S or W-22-7 S or W-22-8
800 1000 1200 1400
S or W-21-5 S or W-21-6 S or W-21-7
800 1000 1200
S or W-19-5 S or W-19-6
S or W-19-7
600
750 900
S or W-15-4 S or W-15-5 S or W-15-6 S or W-15-7 S or W-15-8
300 425
550 675 800
625 780
935 1090
1904 - 1925
1300 , 1650
2000 2350
1904 - 1906
625 1325 780 1650 935 2000
1909 - 1925
470 1000 585 1250 700 1500
1906 - 1920
234 500 332 700 430 900 525 1100 625 1300
1015 1290 1560 1830
1035 1290 1560
780 975 1170
390 545 700 860 1015
4.08 5.10 6.12 8.00
46-1/4 46-1/4 46-1/4 46-1/4
4.1 50
5*1 50 6.1 50
3.32
4.15 4.98
43-3/8 43-3/8 43-3/8
1.95 2.60
3-25
4.9 5.7
40-7/8 40-7/8 40-7/8
40-7/8 40-7/8
`Hie highest ratings listed are taken. An allowance for piping has been eade on these loads
20516
Boiler No.
3 or T-48-6 S or T-48-7 S or T-48-8 S or T-48-9 S or T-48-10 T-48-11 T-48-12
W-48-6 T-48-60
IDEAL SECTIONAL BOILER (1906 - 1922)
Rating
STEAM *Load Inc.
Piping
HOT WATER
*Load Inc.
Rating
Piping
- 5275 6300
7325 8350 9375 10,400
11.425
4400 5260 6100 6960 7820 8700
9550
8700
7250
Grate Area Sq. Ft.
18.00 21.60 25.20 28.80 32.40 25.20 25.20
18.0
7
Water Line Inches
72 72 72 72 72 72 72
W-48-7 W-48-70
W-48-8 T-48-80
10.375 12,050
8650 10,070
21.60 25.20
W-4S-9 W-48-90
W-48-10 W-48-100
T-48-110 T-48-120
13,725
15,400
17,075 18,750
11,500
12,900 14,250 15.650
28.80
32.40 25.20 25.20
1200 1500 1800
2200 2600 3000 3600 4500
IDEAL CYLINDRICAL STEEL BOILER (1906 - 1914)
1200 1500
1800 2200
2600 3000 3600 4500
1110 1390 1660 2040 2400 2760
3325 4155
2000 2500 3000 3600
4300 5000 6000 7500
1850 2310 2780
3325 3980 46 20
5550 6840
8,75 8.75
8.75 12.0 12.0 14.0 16.0 18.0
58 58 58 61-1/2 61-1/2 61-1/2 61-1/2 61-1/2
IDEAL PREMIER BOILER (1908 - 1909)
1015 or 1115
175
146
300 250
2015 or 2115
200
167
325 270
3015 or 3115
225
188
350 292
1018 or 1118
275
230
450 375
2018 or 2118
300
250
500 418
3018 or 3118 1021 or 1121
325 400
270 334
550 460 600 500
2021 or 2121
425
355
650 542
3021 or 3121 4021 or 4121
450 475
375 396
700 585 750 625
1024 or 1124
525
438
875 730
2024 or 2124
575
480
950 792
3024 or 3124
625
522
1025
855
4024 or 4124
650
542
1075
900
1027 or 1127
750
625
1250
1042
2027 or 2127
800
670
1325
1105
3027 or 3127
850
710
1400
1170
4027 or 4127
900
750
1475
1230
1.21 1.21 1.21 1.76 1.76 1.76 2.4 2.4 2.4 2.4 3.14 3.14 3.14 3.14
3-9 3-9 3-9 3-9
40-1/2 44-1/2 48-1/2 43-1/4 47-1/2
51-3/4 44-1/2
49 53-1/2 58-1/8 45-1/2 50-1/4
55 59-9/16 46-3/8 51-5/16 56--1/4 61-3/16
`He highest ratings listed are taken. An allowance for piping has been made on these loads.
20517
8 "IDEAL ARCO ROUND BOILER (1909 - 1924)
Boiler No.
3-19-S or W
3-20-S or W
3-22-S or
3-23-S or W
3-25-S or W
3-28-S or
3-32-S or W
3-34-S or W
4-19-S or
4-20-S or W
4-22-S or W
4-23-S or W
4-25-S or
4-28-S or W
4-31-S or 4-34-S or 5-19-S or 5-20-S or 5-22-S or 5-23-S or 5-25-S or 5-28-S or 5-31-S or 5-34-S or 6-19-S or 6-20-S or 6-22-S or
6-23-S or W
6-25-S or 6-28-S or
6-31-S or W
6-34-S or
Rating
STEAM `Load Inc.
Piping
HOT WATER
`Load Inc.
Rating
Piping
385 450
" 535 610 700 900 1125
1375 410 480
570 650 750 965 1200
1465 430 500 600
685 800
1025
1275 1550
450 520 630
715
835 1070 1330
1615
3OJ0C0ft 418
475 546
705 880 1070 320
375 445 506
585 752
935 1140
336 390 470
535 625 800
995 1210
352 406 492
558 650
835 1040 1260
635 740 880 1000
1155 1485 1860
2270
675 790 940
1065 1240 1590 1980
2415 710
825 990 1130 1320 1690 2100
2555 740 860
1040 1180
1375 1765
2195 2665
495 576
685 780 900 1160
1450
1770
527 615 735 830
965 1240
1540 1880
554 642
770 880 1030 1320 1640
1990
577 670 810 920 1070 1380 1710 2080
`Equipped with Second and Third Pattern Arco Bases
Grate Area Sq. Ft.
1.76 2.23 2.40
2.91 3.14 4.12 4.90 5.94 1.76 2.23 2.40
2.91 3.14 4.12
4.90 5.94 1.76 2.23 2.40
2.91 3-14 4.12 4.90 5.94 1.76 2.23 2.40
2.91 3.14 4.12 4.90 5-94
Water Line Inches
40-7/8^ 41-9/16 42-1/4 41-5/16 42-3/4 44
45-5/8 46-3/8 45-1/2
46-1/8
47 46-5/8 47-7/8 49-1/4
51 52 50 50-3/4 51-1/2
51-3/8 52-1/2 54-1/4 56-1/4 57-1/2
54-5/8 55-5/16 56-1/4 56--1/8
57-5/8 50-1/2 61-5/8 63-1/8
IDEAL DOWNDRAFT SMOKELESS BOILER (1913 - 1920)
364-S or W
374-S or W
384-S or W
394r-S or W
3104-S or W
468-S or 478-S or 488-S or
498-S or W
4108-S or
4118-S or W
4128-S or
670-S or W
680-S or W
690-S or 610O-S or 6110-S or 6120-S or 974-S or 984-S or
994-S or W
9104-S or
9114-S or W
9124-S or W
1500
1800 2100 2400 2700 3000
3500
4000
4500 5000 5500
6000 6300 7200 8100 9000 9900
10,800
8750 10,000 11,250 12,500
13.750 15,000
1250
1505
1755 2005 2260
2505 2920
3340 3760 4180 4600 5000 5260 6000 6760
7500 8260 9000 7300
8350 9400
10,430 11,500 12,520
2450
2950 3450
3950 4450 4800 5600
6400 7200 8000 8800 9600 10,000 11,500 13,000 14,500 16,000
17.500 14,000
16,000 18,000 20,000 22,000 24,000
2050 2460 2880 3300 3720
4000 4680
5350 6000 6700
7350 8000
8350 9600
10,850
12,100
13.370 14,600
11.700
13.370 15,000
16.700
18,400 20,000
54-1/2
54-1/2 54-1/2 54-1/2 54-1/2 61 61 61 61 61 61 61 72 72 72 72 72 72 72 72 72 72 72 72
The highest ratings listed are taken. An allowance for piping has been Bade on these loads.
20518
IDEAL TYPE "A" BOILER U920 - 1925)
9
.ler No.
cr 4Q
or 50
l-K-6 or 60
or 70
_--
or 50 or 60 2-A-7 or 70 or 80 or 90
or 50 or 60 or 70 or 80 or 90 ) or 100 l or 110
Rating
150 600 750 900
STEAM Load Inc. Piping
338 450 562 675
HOT WATER
*Load Inc.
Rating
Piping
O1 KjO*
1000
1250
1500
562
750
935 1125
1100 1400 1700
2000 2300
IDEAL TYPE "A" BOILER (1920 - 1922)
825 1050
1275 1500
1730
1800 2300 2800
3300 3800
1350 1730 2100 2480 2850
26 00
3250 3900
4550 5200 5850 6500
1920 - 1922
1950 2440 2920 3420 3900 4400 4880
4400 5500 6600 7700 8800 9900 11,000
3300 4225
4950 5780 6600 7420 8250
Grate Area Sq. Ft. i*7n 2.5 3.1 3.7
4.0 5.0 6.0 7.0 8.0
8.0 10.0 12.0 14.0 16.0 18.0 20.0
Water Line
Inches
Oyfj* 35 35 35
43 43 43 43 43
49 49 49 49 49 49 49
l-C-4 or 40
l-C-5 or 50 l-C-6 or 60
l-C-7 or 70 l-C-8 or 80
l-C-9 or 90 l-C-10 or 100
675 900 1125
1350
1575 1800
2025
IDEAL TYPE 'C' BOILER (1920)
526 700
875 1050 1230
1400 1580
1050 1400 1750 2100 2450 2800
3150
820 1090
1365 1640 1910 2180
2460
36 36 36 36 36 36 36
IDEAL WATER TUBE BOILER (1922)
S-or W-23-T-5 S-or W-23-T-6 S-or W-23-T-7 S-or W-23-T-8 S-23-T-9 S-23-T-10 S-23-T-ll W-23-T-90 W-23-T-100 W-23-T-110
S-29-T-5 S-29-T-6 S-29-T-7 S-29-T-8 S-29-T-9 S-29-T-10 S-29-T-11
W-29-T-5 W-29-T-6 W-29-T-7 or 70 W-29-T-8 or 80
W-29-T-9 or 90 W-29-T-10 or 100 W-29-T-110
600 750 900 1050 1200 1350 1500
1200 1500 1800 2100 2400 2700 3000
442 552 662 772 882 992 1102
882 1102 1320 1540 1770 1980 2200
975 1200 1425 1650
1875 2100 2325
1920 2400 2880 3360 3840 4320 4800
716 882 1050 1210
1380 1540 1710
1410 1765 2120 2470 2820 3180 3525
2.72
3-36 4.00 4.64 5.28 5.92 6.56 5.28
5.92 6.56
4.84 6.05 7.26 8.47 9.68
10.89 12.10
4.84
6.05 7.26 8.47 9 -68
10.89 12.10
44-1/2 44-1/2 44-1/2 44-1/2 44-1/2 44-1/2 44-1/2
52-3/4 52-3/4 52-3/4 52-3/4 52-3/4 52-3/4 52-3/4
*The highest ratings listed are takeu.
for piping has been Bade on these loads.
20519
10
Boiler No.
S-36-T-5 S-36-T-6 S--36-T-7 S-36-T-8 S-36-T-9 S-36-T-10 S-36-T-11 S-36-T-12 W-36-T-5 W-36-T-6 W-S6-T-7 W-36-T-8 or 80 W-36-T-9 or 90 W-36-T-10 or 100 W-36-T-11 or 110 W-36-T-12 or 120
IDEAL WATER TUBE BOILER (1922)
STEAM
Load Inc.
Rating
Piping
HOT WATER
`Load Inc.
Rating
Piping
1750 2200
2650 3100 3550 4000 4450 4900
1365 1720 2070 2420 2770 3120 3470 3820
2875 3600
4325 5050
5775 6500
7225 7950
2240 2800 3380 3940 4500 5070 5650 6200
Grate Area Sq. Ft.
6.0 7.5 9.0 10.5 12.0 13.5 15.0 16.5 6.0 7.5 9.0 10.5 12.0 13.5 15.0 16.5
Water Line Inches
58 58 58 58 58 58 58 58
S or W-79-T-7 S or W-79-T-8
S or W-79-T-9 S or W-79-T-10 S or W-79-T-11 S or W-79-T-12
S or W-79-T-13 S or W-79-T-14
S or W-79-T-15 S or W-79-T-16
S or W-79-T-17
8400 9600 10,800 12,000 13,200 14,400 15,600 16,800 18,000 19,200 20,400
IDEAL WATER TUBE BOILER (1922)
7020 8010 9000
10,000 11,000 12,000 13,000 14,000 15,000 16,000 17,000
13,440 15.360 17,280 19,200 21,120 23,040 24,960 26,880 28,800 30,720 32,640
11,200 12,810 14,400 16,000 17,600 19,300 20,800 22,420 24,020 25,600 27,200
22.96 26.24
29.52 32.80
27.88 31.16 31.16 34.44 34.44 37.72 37.72
67 67 67 67 67 67 67 67 67 67 67
S or W-1724 S or W-1744 S or W-1924 S or W-1944 S or W-2024 S or W-2044 S or W-2224 S or W-2244 S or W-2524 S or W-2544 S or W-2824 S or W-2844 S or W-3104 S or W-3124 S or W-3144
S or W-3105 S or W-3106
IDEAL ARCO ROUND BOILER (1925 - 1929)
400 450
550 600
675 725 825
875 1025 1100 1300 1400 1500 1600 1700 1600
1700
200 675 338
225 750 375
275 925 300 1000
463 500
330 1125 362 1200
562 600
412 1375
688
437 1450
725
512 1700
850
550 1825
912
650 2150 1075
700 2350 1175
750 2475 1240
800 2650 1325
850 2825 1413
800 2650 1325
850 2825 1413
1.4 48-1/2 1.4 50
1.9 46-1/2 1.9 48 2.2 47-1/2
2.2 49 2.6 48-1/2 2.6 50
3-5 49-1/2
3-.5 51 4.4 50-1/2
4.4 52
5-3 51 5.3 52-1/2 5-3 54 5-3 56 5-3 62
`The highest ratings listed are taken. An allowance for piping has been *ade on these loads
20520
IDEAL TTPE 'A' BOILER (1925)
11
Boiler No.
S or W-2205-A~ S or W-2206-A S or VT--2207--A S or W-2208-A S or W-2209-A S or W-3205-A S or W-3206-A S or W-3207-A S or W-3208-A S or W-3209-A S or W-3210-A S or W-3211-A S or N-3212-A
~
STEAM
`Load Inc.
Rating
Piping
HOT WATER
`Load Inc.
Rating
Piping
1GG0
1250 1500
1750 2000 2250 2500 3000 3500 4000
4500 5000 5500 6000
625 780
935 1095 1250 1410 1516 1870
2185 2500
2810 3120 3400
3750
1600 2000 2400 2800 3200 3600 4000 4800 5600 6400 7200 8000 8800 9600
1000 1250 1500
1750 2000 2250 2500 3000
3500
4000
4500 5000
5500
6000
IDEAL YONDA SECTIONAL BOILER (1925)
Grate Area Sq. Ft.
2.76 3.68 4.60 5.52 6.44 7.36 6.22 7.77 9.32 10.87 12.42 13.97 1552 17.07
Water Line Inches
5tf 0v 50 5J 0w 50 50 50 56-3/4 56-3/4 56-3/4 56-3/4 56-3/4 56-3/4 56-3/4 56-3/4
S or W--1814 S or W-1824 S or W-1834 S or W-1844 S or W-1815
S or Vf--1825 S or tf-1835 S or W-1845 S or W-1816 S or W-1826 S or W-1836 S or W-1846 S or W-1817 S or W-1827 S or W--1837 S or W-1847 S or W-1818 S or W-1828 S or W-1838 S or W-1848
S or W-1815-S S or W-1825-S S or tf-1835-S S or W-1845-S S or W-1816-S S or W-1826-S S or W-I836-S S or W-1846-S S or W-1817-S S or W-1827-S S or W-1837-S S or W-1847-S S or W-1818-S S or W-1828-S S or W-1838-S S or W-1848-S S or W-1819-S S or W-1829-S S or W--1839--S S or W-1849-S S or W--1810--S S or W-1820-S S or W-1830-S S or W-1840-S
540 600 660 720 780 840 900 960 1020 1080 1140 1200 1260 1320 1380 1440 1500 1560 1620 1680
780 840 900 960 1020 1080 1140 1200 1260 1320 1380 1440 1500 1560 1620 1680 1740 1800 1860 1920 1980 2040 2100 2160
306 900 510
340 1000 566
374 1100 623
407 1200 680
442 1300 735
475 1400 791
510 1500 850
545 1600 905
576
1700
965
611
1800
1020
645
1900
1075
680
2000
1132
715
2100
1190
748
2200
1248
782
2300
1300
815
2400
1360
850
2500
1415
885
26 00
1470
916
2700
1530
952
2800
1590
IDEAL YONDA SMOKELESS BOILER (1925)
442
475 510
545 576 611
645 680
715 748 782
815 850
885 916
952 990 1020 1052 1088 1120 1156 1190
1225
1300 1400 1500
1600 1700
1800 1900 2000 2100 2200 2300
2400 2500 26 00 2700
2800 2900 3000 3100 3200
3300
3400
3500 3600
735 791 850
905
965 1020
1075 1132 1190
1248 1300 1360
1415 1470
1530 1590 1640 1700 1760 1810
1870
1930 1980 2040
1.94 2.12
2.3 2.47 2.65 2.83 3.01 3.18 3-36 3.54 3.71 3.89 4.07 4.24 4.42 4.60
4.77 4.95 5.13 5.31
2.65 2.83 3.01 3.18 3-36 3-54 3.71 3.89 4.07 4.24 4.42 4.6 4.77 4.95 5.13 5.31 5.49 5.67 5.85 6.02 6.20 6.37 6.55 6.73
48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48
48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48
`The highest ratings listed are taken. An allowance for piping has been nade on these loads.
20521
12 IDEAL ASSEMBLED SECTIONAL BOILER (1924)
Boiler No. S or W-1204 S or W-1205 S or W-1206 S or W-1207 S or W-1208
oocn
/Recommended Load-Sq. Ft.
E.D.R. Steam Water
225 375
375 625 450 750 525 875
OO
Grate Area Sq. Ft.
.81
1.08
1.35 1.62
1.89
Floor Area Occupied Inches
17 x 13-1/2
17 x 17
17 x 20-1/2
17 x 24
17 x 27-1/2
Water Line Ins.
39-1/4
39-1/4
39-1/4
39-1/4
39-1/4
Base Height Inches
None It
M
It
It
Chimney
Size
Height
Inches
Feet
8x8 8x8 8x8 8x8
25 25 30 30
8x8
35
/RecommendedlLoad represents attached load - including piping - which may be placed on boiler in accordance with accepted installation standards for economical operation.
Boiler No.
S or W-1814 S or W-1824 S or W-1834 S or W-1844 S or W-1815 S or W-1825 S or W-1835 S or W-1845 S or W-1816 S or W-1826 S or W-1836 S or W-1846 S or W-1817 S or W-1827 S or W-1837 S or W-1847 S or W-1818 S or W-1828 S or W-1838 S or W-1848
IDEAL ARCO SECTIONAL BOILER (1923 - 1924)
*`Installed Radiation Sq. Ft.
Steam Water
Grate
Area Sq. Ft.
Floor Area Occupied Inches
Water Line Inches
Base Height Inches
480 540 600 660 720
780 840 900 960 1020 1080 1140 1200
1260 1320 1380 1440 1500 1560 1620
800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
2200 2300 2400 2500 2600 2700
1.77 1.94 2.12 2.30
2.47 2.65
2.83 3.01 3.18
3-36 3.54 3.71 3-89 4.07 4.24 4.42 4.60
4.77 4.95 5.13
27-1/2 x 21-3/4 27-1/2 x 23-1/4 27-1/2 x 24-3/4 27-1/2 x 26-1/4 27-1/2 x 27-3/4 27-1/2 x 29-1/4 27-1/2 x 30-3/4 27-1/2 x 32-1/4 27-1/2 x 33-3/4 27-1/2 x 35-1/4 27-1/2 x 36-3/4 27-1/2 x 38-1/4 27-1/2 x 39-3/4 27-1/2 x 41-1/4 27-1/2 x 42-3/4 27-1/2 x 44-1/4 27-1/2 x 45-3/4 27-1/2 x 47-1/4 27-1/2 x 48-3/4 27-1/2 x 50-1/4
43 43 43 43 43
43 43
if
43 43 43 43 43 43 43
43 43 43 43 43
None 11 II II II
II II
H II It II It II
n 11
it
it .H
II 11
Chimne V
Size
H[eight
Inches
Feet
8x8 8x8 8x8 8x8 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 12 x 12 12 x 12 12 x 12 12 x 12 12 x 12 12 x 12 12 x 12
35
35 . 35 35 35
35 35
35
35 35
40 40 40
40
45 45 45 45 45 45
IDEAL ARCOFLASH BOILER (1928 - 1932)
Boiler No.
"Installed Radiation So. Ft.
Steam Water
Grate Area Sq. Ft.
Floor Area Occupied
Inches
Water Line Inches
Base Height
Inches
Chimne)r
Height
tteight
Inches
Feet
S or W-18 S or W-20 S or W-22
S or W-24
250 400 300 480 350 560 450 720
1.77 2.18
2.65 3.14
26-1/2 Dia. 28-1/2 " 31-1/4 " 33-1/4 "
38-5/8
38-5/8 38-5/8 38-5/8
11-1/2 11-1/2 11-1/2 11-1/2
8x8 8x8 8x8 8x8
30 30
35 35
"These ratings represent the maximum net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot water) that may be connected to the boiler. Allowances have been made in these ratings for normal piping (covered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75
gallons in 24 hours.
20522
NO. 23 (23 INCH) IDEAL WATER TUBE BOILER (1923 - 1947}
13
Boiler No.
S or W-23-T-5 S or W-23-T-6 S or W-23-T-7 S or W-23-T-8 S or W-23-T-9
"Installed Radiation Sq. Ft. Steam-Whter
Grate Area Sq.ft.
Firing Firing Rate Rite Lfs. Lbs.Per Per Hour Hour
Floor Area
Occupied Inches
Fire Box Dimensions
Indies Width length
Height
Floor to
Center
Water Rise of Crown Chimney
Line Height Siept S7A Hnirvl
Ins. Ins.
Ins. Indies Fee
400 640 500 800 600 960 700 1120 800 1280
2.72
3-36 4.00 4.64 5.28
"T TVpe - Lithrncite tml flland Fired)
31-3/4 x 21 31-3/4 x 25 31-3/4 x 29 3l-3/4 x 23 31-3/4 x 37
23 x 16-1/2 23 x 20-1/2 23 x 24-1/2 23 x 56-1/2 23 x 32-1/2
44-1/2 44-1/2 44-1/2 44-1/2 44-1/2
Non11e ft It 11
30 8x8 30
30 8 x 12 30 30 8 x 12 35 30 8 x 12 35 30 i12 x 12 40
Sor W-2305 S or W-2306
S or W-2307 S or W-2308 S or W-2309 S or W-2310
400 640 500 800 600 960 700 1120 800 1280 900 1440
2.72
3-36 4.00 4.64 5.28 5.92
Coal (Ifcuid Fired)
31-3/4 X 21
31-3/4 X 25 31-3/4 X 29 31-3/4 X 33 31-3/4 x 37 31-3/4 X 41
23 x 16-1/2 23 x 20-1/2
23 x 24-1/2 23 x 56-1/2 2j x 32-1/2 23 x 36-1/2
44-1/2 44-1/2 44-1/2 44-1/2 44-1/2 44-1/2
ft M If If II If
30 8 x 12 30
30 8 x 12 35 30 8 x 12 35 30 8 x 12 35 30 8 x 12 40
30 12 x 12 40
S or W-O623 S or W-0723 SorW-0623 S or W-0923 S or W-1023
650 770 910 1050 nyo
10-10 1230 1450 1680 1905
16.5
19.3 22.9 25.8 58.6
Oil Fired
3I-3/4 x *5 31-3/4 X 29
31-3/4 x 33 31-3/4 x 37 31-3/1 x 41
2j x 20-1/2 23 x 24-1/2
23 x 56-1/2 23 x '{2-1/2 23 x 36-1/2
44-1/2 44-1/2 44-1/2
14-1/2 44-1/2
II II II II II
30 30
30 30 30
`Minimum Rimer Oapacity-Lbs. Oil Per Hour, based on oil of 19,700 Btu per pound.
8x8 30
8x8 30 8 x 12 30 H x 12 . .35 8x12 35
SC or MZ-23-T-6
SC or MT-23-T-7 SC or WC-23-T-8 SC or WC-23-T-9 SC or WO-23-T-10 SC or WC-23-T-U
650 770 910 1050 1190
1330
1040 1230 1455
1680
1905 2130
Stoker Fiied
26 31-3/4 x 25 23 X 20-1/2 44-1/2 30 31-3/4 X 29 23 X 24-1/2 44-1/2 33 31-3/4 x 33 23 X 28-1/2 44-1/2 41 31-3/4 x 37 23 X 32-1/2 44-1/2 46 31-3/4 x 41 23 X 3&-1/2 44-1/2 51 31-3/4 X 45 23 X 40-1/2 44-1/2
30 8x8 30 30 8x8 30 30 8 x 12 30
30 8 x 12 35 30 8 x 12 35 30 12 x 12 35
S or W-29-T-5 S or W-29-T-6
S or W-29-T-7 S or W-29-T-8
NO. 29 ( 29 INCH) HEAL WATER TUBE DDILER (1923 - 1947)
"T" TVpe - Anthracite Coal (Hand Fired)
800 1000 1200 1400
1280 1600 1920
2240
4.84 6.05 7.26 8.47
38-1/2 x 30 38-V2 x 36 38-1/2 x 42 38-1/2 x 48
5J) x 23-1/2 29 x 29-1/2 29 x 35-1/2 29 x 41-1/2
52-3/4 52-3/4 52-3/4 52-3/4
II H II It
33 12 x 12 35 33 12 x 12 35 33 12 x 16 40
33 12 x 16 45
S or W-2905 S or W-2906 S or W-2907 S or W-2908 Sor W-2909 S or W-2910
S or W-2911
800 1000 1200 1400 1600 1800 2000
1280 1600 1920 2240 2950 2880 3200
4.84 6.05 7.26 8.47 9.68
10.89 12.10
Coal (Hand Fired)
38-1/2 x 30 38-1/2 x 36 38-1/2 x 42 38-1/2 x 48 38-1/2 x 54 38-1/2 x 60 38-1/2 x 66
29 x 23-1/2 29 X 29-1/2 29 X 35-1/2 29 x 41-1/2 29 x 47-1/2 29 x 53-1/2 29 x 59-1/2
52-3/4
52-3/4 52-3/4
52-3/4 52-3/4 52-3/4 52-3/4
II M
II II II 11
33 12 x 16 35 33 12 x 16 40 33 16 x 16 40 33 16 x 16 45
33 16 x 20 50 33 16 x 20 55 33 20 x 20 60
"These ratings represent the maximum net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot water) that mav be connected to the boiler. Allowances he.ve been made in these ratings for normal piping (covered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
20523
14 NO. 36 (36 INCH) IDEAL WATER TUBE BOILER (1923 - 1947)
Boiler No.
S or W-36-T-6 S or W-3S-T-7 S or W-36-T-8 S or W-36-T-9 S or W-36-T-10 S or W-36-T-11 S or W-36-T-12 S or W-36-T-13
S or W-3506 S or W-36U7 S or W-36CB S or W-3609 S or W-3610 S or W-36II S or W-3612 S or W-3613 S or W-3614 S or W-3615
"Installed fediation bq. Ft. SteanJfeter
Grate Area Sq.Ft.
Floor Area Occupied Inches
Fire Box
Dimensions Inches
Width Length
Witer Base Line Heioht,
Ins. Ins.
Height Floor to
Center of Crowe Sieet
Inches
"T" Type - Anthracite Gcal (Hand Fired)
Oiinwwiv
Si TO
Hoi r4>+
Inches Feet
1600 2560 7.50 50-1/4 x 36 36 x 29-1/2 57 12-1/4 38-1/2 2000 3200 9.00 50-1/4 x 42 36 x 35-1/2 57 12-1/4 33-1/2 2400 3840 10.50 50-1/4 x 48 36 x 41-1/2 57 12-1/4 38-1/2 2800 4480 12.00 50-1/4 x 54 36 x 47-1/2 57 12-1/4 33-1/2 3200 5120 13.50 50-1/4 x 60 36 X 53-1/2 57 12-V4 38-1/2 3600 5760 15.00 50-1/4 x 66 36 X 50-1/2 57 12-1/4 38-1/2 4000 6400 16.50 50-1/4 x 72 36 X 65-1/2 57 12-1/4 38-1/2 4400 7040 18.00 50-1/4 x 78 36 X 71-1/2 57 12-1/4 33-1/2
Coal (Hand Fired)
16 x 20 16 x 20 20 x 20 20x 20 20 x 20 20 x 20 20 x 24 20 x 24
45 50 50
55 55 60 60
65
1600 2560 7.50 50-1/4 x 36 36 x 29-1/2 57 12-1/4 33-V2 2000 3200 9.00 50-1/4 x 42 36 x 35-1/2 57 12-1/4 33-1/2
2400 3840 10.50 50-1/4 x 48 36 X 41-1/2 57 12-1/4 38-1/2 2809 4480 12.00 50-1/4 x 54 36 x 47-1/2 57 12-1/4 38-1/2 3200 5120 13.50 50-1/4 x 60 36 X 53-1/2 57 12-1/4 38-1/2 3600 5760 15.00 50-1/4 x 66 36 x 50-1/2 57 12-1/4 38-1/2
4000 6400 16.50 50-1/4 x 72 36 x 65-1/2 57 12-1/4 38-1/2 4400 7040 18.00 50-1/4 x 78 36 x 71-1/2 57 12-1/4 38-1/2 4800 7680 19.50 50-1/4 x 84 36 x 77-1/2 57 12-1/4 33-1/2 5200 8320 21.00 50-1/4 x 90 36 x 83-1/2 57 12-1/4 38-1/2
16 x 20 16 x 20 20 x 20 20 x 20 20 x 20 20 x 20 20 x 24 20x24 20 x 21 24 x 24
45 50 50
55 55 60 60
65 70
75
Boiler No.
NO. 36 WATER TUBE BOILER (1923 - 1956)
** Installed Radiation
Sq. Ft. Steam Water
Floor Area
Occupied Inches
Firing Rate
Lbs. Coal or Gals. Oil
Per Hour
Water Line Inches
Base Height Inches
Height Floor to Center of Crown Sieet Inches
Chimney Size Height Inches Feet
S or W-0736 S or W-0836 S or W-0936 S or W-1036 S or W-1136 S or W-1236
2350 2800 3250 3700 4150 4600
3915 4600 5280
5945 6640 7360
50 x 42
50 x 48
50 x 54 50 x 60 50 x 66
50 x 72
SC or WC-36-T-6 SC or WC-36-T-7 SC or WO36-T-8 SC or WC-36-T-9 SC or WC-36-T-10 SC or WC-36-T-11
SC or WC-36-T-12
1900
2350 2800 3250 3700 4150 4600
3210
3915 4600 5280
5945 6640 7360
50 *x 36
50 x 42 50 x 48 50 x 54 50 x 60 50 x 66 50 x 72
Oil Fired
7.6
8.9 10.2 11.4 12.6 13.8
57 57 57 57
57
57
Stoker Fired
71 57 86 57 101 57 116 57 131 57 145 57 160 57
12-3/8 12-3/8 12-3/8 12-3/8 12-3/8 12-3/8
12-3/8 12-3/8 12-3/8 12-3/8 12-3/8 12-3/8 12-3/8
38-1/2 38-1/2 3&-1/2 38-1/2 38-1/2 38-1/2
16 x 16 16 x 16 16 x 20 16 x 20 16 x 20 20 x 20
30 35
40
50 55 6u
38-1/2 38-1/2 38-1/2 38-1/2 38-1/2 38-1/2 38-1/2
12 x 16 16 x 16 16 x 16 16 x 20 16 x 20 16 x 20 20 x 20
25 30 35 40
50
55 60
`For Smoke Hood add 11-1/2". "These ratings represent the maximum net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot water) that may be connected to the boi ler. Allowances have been made in these ratings for normal piping (covered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
20524
NO. 48 (48 INCH) HEAL WATER TUBE BOILER (1923 - 1945)
15
Boiler No.
"Installed th.hr.tiCu - Sin Ft.
Steam Vfeter
Firing uTac<ac rale Area lbs.Per Sq.Ft. Hour
Firing fete Lbs.Per Hour
Floor Area Occupied
Indies
Heig&t
Floor to
Fire Box
Center
Dimensions Water Base of Crown1
Indies line Height Sieet
Width Length Ins. Ins. Inches
(Limey Size Height Indies Fat
Goal (fend Fired)
SorW-4807 S or W-4808 S or W-4809 S or W-4810
S or W-48U S or VM812 S or W-4813 SorW-4814
6000 9600 21.60 7000 11200 25.20 7600 12160 25.20
8400 13440 28.80
9000 14400 28.80 9600 15360 28.80 10400 16640 32.40 11000 17600 32.40
58-3/8 x 68-1/2 48 x 64
69 14-1/2 37-3/4 24x 24
58-3/8 x 79-1/4 48 x 74-3/4 69 14-1/2 37-3/4 24 x 94
58-3/8 x 90
48 x 85-1/2 69 14-1/2 37-3/4 24x 28
58-3/8 x 100-3/4 48 x 96-1/4 69 14-1/2 37-3/4 24x28
58-3/8 x 111-1/2 48 x 107
69 14-1/2 37-3/4 28x 28
58-3/8 x 122-1/4 48 x 117-3/4 69 14-1/2 37-3/4 28x28
58-3/8 x 1
48 x 128-1/2 69 14-1/2 37-3/4 28x32
58-3/8 x 143-3/4 48 x 139-1/4 69 14-1/2 37-3/4 28x32
70
75 80
85
95 100 105
no
S or VM808-0
S or VM8Q9-0 S or W-4810-0 S or W-4811-0 S or W-4B12-0 S or W-4813-0 S or VM&L4-Q
4965 7945
5645 9035 6330 10130 7020 11230 7700 12320 90 13410
9060 14530
*
119.1 135.0 152.0 169.0 185.0 201.5 218.4
Oil Fired
58-3/8 x 79-1/4 48 x 74-3/4 69 14-1/2 37-3/4 20 x 24
50-3/8 x 90
48 x 85-1/2 69 14-1/2 37-3/4 20 x 24
58-3/8 x 100-3/4 48 x 96-1/4 69 14-1/2 37-3/4 24 x 24
58-3/8 x 111-1/2 48 x 107
69 14-1/2 37-3/4 24 x 24
58-3/8 x 122-1/4 48 x 117-3/4 69 14-1/2 37-3/4 24 x 24
58-3/8 x I
46 x 128-1/2 69 14-1/2 37-3/4 24x 28
58-3/8 x 143-3/4 48 x 139-1/4 69 14-1/2 37-3/4 24 x 28
60
65 70
75 80
85 90
Stoker Fired
or VC-4807 or VC-4808 or VC-4809 or W3-4810 or VC-48U or VC-4812 or VC-4813 or VC-4814
4000 6400
4965 7945 5645 9035 6330 10130 7020 11230 7700 12320 8380 13410
9060 14530
158 58-3/8 x 68-1/2 48 x 64
69 14-1/2 37-3/4 20 x 24
196 58-3/8 x 79-1/4 48 x 74-3/4 69 14-1/2 37-3/4 20 x 24
223 58-3/8 x 90
48 x 85-1/2 69 14t-1/2 37-3/4 20x 24
250 58-3/6 x 100-3/4 48 x 96-1/4 69 14-1/2 37-3/4 A x 21
w 58-3/8 x 111-1/2 48 x 107
69 14-1/2 37-3/4 24 x 24
306 58-3/8 x 122-1/4 48 x U7-3/4 69 14-1/2 37-3/4 24 x 24
331 58-3/8 x 133
48 x 128-1/2 69 14-1/2 37-3/4 24 x 28
359 58-3/8 x 143-3/4 48 x 139-1/4 69 14-1/2 37-3/4 24 x 28
60
60
65
70
75
80
85
90
v Boiler No.
NO. 79 (79 INCH) IDEAL WATER TUBE BOILER (1923 - 1942)
"Installed
Firing Firing
Radiation Grate Rate Rate Floor Area
Sq.Ft. Area Lbs.Per Lbs.Bar Occupied
Steen Vfater Sq.Ft. Hour Hour
Indies
Fire Box Dimensions
Indies Width Length
Height Floor to Genter Water Base of Crowi Qiimiey
Line Height Sieet Size Height Ins. Ins. Inches Indies Feet
Sor W-7909 S or W-7910 S or W-7911 S or W-7912 S or W-7913 S or W-7914
S or W-7915 S or W-7916 S or W-7917
7000 11200 21.9
8500 13600 24.9 9500 15200 28.0
nooo 17600 31.1
12000 19200 34.2
13000 20800 37.3
14000 22400 34.2
15000 25600 34.2
16000 25600 37.3
Coal (Hand Fired)
98-1/2 x 60 98-1/2 x 66 98-1/2 x 72 98-1/2 x 78 98-1/2 x 84 98-1/2 x 90 98-1/2 x 96 98-1/2 x 102 98-1/2 x 108
78-3/4 x 53-1/2 78-3/4 x 59-1/2 78-3/4 x 65-1/2 78-3/4 x 71-1/2 78-3/4 x 77-1/2 78-3/4 x 83-1/2 78-3/4 x 89-1/2
78-3/4 x 95-1/2 78-3/4 x 101-1/2
67 67 67 67 67 67 67 67 67
None II It II H II II II II
41 24 x 28 85 41 24 x 28 90
41 24 x 28 95 41 28 x 28 100
41 30 x 30 105 41 30 x 36 no
41 30 x 36 U5 41 36 x 36 120 41 36 x 36 125
`These ratings represent the mucuiun net loads (240 Btu per sq. ft. steam and 150 per sq. ft. hot water) that, may be connected to the boiler. Allowances have been node in tliese rating for normal piping (covered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served or if the use of domestic hot water does not exceed 75 gallons in 24 hairs.
Minimm Goal Burning Capacity - Lbs. Per Hour, based on coal of 12,500 Btu per pound.
`"Minimm Burner Capacity - Lbs. Oil Per Hour, based on oil of 19.700 Btu per pcwnd.
20525
16 NO. 79 (79 INCH) IDEAL WATER TUBE BOILER (1923 - 1942) - CONTINUED
Boiler No.
"Installed
Firing Firing
fediatioo Grate fete fete
Sq.Ft-- -Area Lbs.Per Lbs.Per Steam Water Sq.Ft. Hour Hour
Floor Area Occupied
Inches
Fire Box Dimensions
Inches Width Length
lleirfit
Floor to
Center hater Base of Crown QiLimey Line Height Sieet Size ur; j,* Ins. Ins. Inches Indies Feet
***
S or W-7909-0 S or W-7910-0 S or W-7911-0 S or W-7913-0
S or W-7913-0 S or W-7914-0 S or W-7915-0 S or W-7916-0 S or W-7917-0
7295 11675 8115 12985 8935 14295 9765 15625
10585 16935 11415 18265
12235 19575 13065 20905 13&85 22215
*
175.0 195.0 214.0 234.0 254.0 274.6 294.0
313.0 334.0
Oil or Stoker Fired 99
288 98-1/2 x 60 78-3/4 x 53-1/2 321 98-1/2 x 66 78-3/4 x 59-1/2 352 98-1/2 x 72 78-3/4 x 65-1/2 386 98-1/2 x 78 78-3/4 x 71-1/2 418 98-1/2 x 84 78-3/4 x 77-1/2 482 98-1/2 x 90 78-3/4 x 83-1/2
507 98-1/2 x 96 T&-3/4 x 89-1/2 516 98-1/2 x 102 78-3/4 x 95-1/2 543 98-1/2 x 108 78-3/4 x 101-1/2
67 67 67 67 67 67 67 67 67
Nooe II II II II II II II It
41 24 x 24 80 41 24 x 24 85 41 24 x 28 90 41 24 x 28 95 41 24 x 28 100 41 24 x 28 105 41 28 x 28 110 41 28 x 28 115 41 28 x SB 120-
***For Stoker Fired use Prefix ' SC" or "WC" and emit Suffix ,"0".
NO. 1 IDEAL REDFLASH BOILER (1926 - 1946)
Boiler No.
"Instailed
Radiation Sq Ft."
Steam feter
Firing Firing Grate fete fete Area Lbs. Per Lbs.Per Sq.Ft. Hour Hour
Floor Area Occupied
inches
Heidit
Floor to
Fire Box
Center
Dimensions feter fese of Crown Chinriey indies Line lleipht Sieet Size Heidit
Width Length Ins. Ins. Inches Inches Feet
1--S or W-4 1-S or W-5 1--S or W-6
1-S or W-7 1-S or W-8 1-S or K-9 1-S or W-10 1-S or W-ll
200 320
290 465
3/0 590 450 720 530 850 610 975 690 1105 700 1130
1-33 1.79 2.25
2.71
3.17 3.63 4.09
4.55
Coal (Hand Fired)
26-3/4 x 16-5/16 18 x 11-1/2 45 10
26-3/4 x 20-5/16 18 x 15-1/2 45 10 26-3/4 x 24-5/26 18 x 19-1/2 45 10
26-3/4 x 28-5/16 18 x 23-1/2 45 10 26-3/4 x 32-5/16 18 x 27-1/2 45 10 26-3/4 x 36-5/16 18 x 31-1/2 45 10 26-3/4 x 40-5/16 18 x 35-V2 45 10 26-3/4 x 44-5/16 18 x 39-1/2 45 10
Stoker Fired
32 8x8 25 32 8x8 30
32 8 x 8 30
32 8 x 12 35
32 8 x 12 35 32 8 x 12 35 32 12 x 12 35 32 12 x 12 35
1-SC or MC-5 1-3C or ViC-6
1-SC or M>7 1-SC or WC-8 1-SC or W>9 1-SC or WC-10 1-SC or VrC-UL
280 450
340 545 400 640
460 735 520 830
580 930 640 1025
1-S or W-5-0 265 425 1-S or W-6-0 305 490 1-S or W-7-0 360 575 1-S or W-8-0 400 640
1-S or W-9-0 455 730 1-S or W-10-0 495 790 1-S or W-11-0 550 880
6.2
7.1 8.4 9.4 10.7 11.7 13.0
11 26-3/4 x 20-5/16 18 x 15-1/2 45 10 13 26-3/4 x 24-5/16 18 x 19-1/2 45 10 15 26-3/4 x 28-5/16 18 x 23-1/2 45 10 17 26-3/4 x 32-5/16 18 x 27-1/2 45 10 19 26-3/4 x 36-5/16 18 x 31-V2 45 10 21 26-3^4 x 40-5/16 18 x 35-1/2 45 10 23 26-3/4 x 44-5/16 18 x 39-1/2 45 10
Oil Fired
26-3/4 x 20-5/16 18 x 15-1/2 45 10 26-3/4 x 24--5/16 18 x 19-1/2 45 10 26-3/4 x 28-5/16 18 x 23-1/2 45 10 26-3/4 x 32-5/16 18 x 27-1/2 45 10 26-3/4 x 36-5/16 18x31-1/2 45 10 26-3/4 x 40-5/16 18 x 35-1/2 45 10 26-3/4 x 44-5/16 18 x 39-1/2 45 10
32 8x8 30 32 8x8 30 32 8x8 30 32 8x8 30 32 8 x 12 30 32 8 x 12 35 32 8 x 12 35
32 8x8 30 32 8x8 30 32 8x8 30 32 8x8 30 32 8 x 12 30 32 8 x 12 35 32 8 x 12 35
frtirnmitti Burner Capacity - Lbs. Oil Per Hour - based oa oil ot 19,700 Btu per paind.
^tinimn Coal Riming Capacity - Lbs. Coal Per Hour - based on coal of 12,500 Btu per pound.
**Ihese ratings represent the maxhtum net loads (240 Btu per sq. ft steam and 150 Btu per sq. ft. hot water) that may be connected to the boiler. Allowances have been unde in these ratings for normal piping (oovered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
20526
Boiler No.
** Installed Radiation
3g. Ft. Steam Water
NO. 3 RFDFLASH BOILER (1927 - 1956) (10 through 14 sections only)
Floor Area Occupied Inches
Firing Rate
Lbs. Coal or Gais. Oil
Per Hour
Water Line Inches
..Base Height Inches
Height FLoor to Center of Crown 55ieet Inches
Chimney
Size iieight
Inches
Feet
3-S or W-10-0 3-S or W-11-0 3-S or W-12-0 3-S or W-13-0 3-S or W-14-0
2700 3000 3300 3600 3900
4450
4905 5355 5800 6240
*
45-5/8 x 60 45-5/8 x 66 45-5/8 x 72 45-5/8 x 78 45*5/8 x 84
3-SC or WC-10 3-SC or WD-11 3-SC or WC-12 3-SC or WC-13 3-SC or WC-14
2700 3000 3300 3600
3900
4450 4905
5355 5800 6240
*
45-5/8 x 60 45-5/8 x 66 45-5/8 x 72 45-5/8 x 78 45-5/8 x 84
3-S or VH0
3-S or VPll 3-S or W-12 3-S or W-13
2700 3000 3300
3600
4320 4800 5280 5760
*
45-5/8 x 60 45-5/8 x 66 45-5/8 x 72 45-5/8 x 78
Oil Fired
8.8 9.6 10.2 11.0*
11.8
53-1/2 53-1/2 53-1/2 53-1/2 53-1/2
Stoker Fired
98 53-1/2 108 53-1/2 118 53-1/2 128 53-1/2 137 53-1/2
Hand Fired
53-1/2 53-1/2 53-1/2 53-1/2
12 12 12 12 12
12 12 12 12 12
12 12 12 12
35 16 x 16 35 35 16 x 20 40 35 16 x 20 40 35 16 x 20 45 35 20 x 20 45
35 16 X 16 35 35 16 x 20 40 35 16 x 20 40 35 16 x 20 45 35 20 x 20 45
35 16 x 20 35 16 x 20 60 35 20 x 20 65 35 20 x 20 65
*On Hand Fired add 21" to length for Smoke Hood. On Oil and Stoker Fired add 3-1/4" for Snoke Col lar.
Boiler No.
NO. 4 REDFLASH BOILER (1928 - 1956)
** Installed Radiation
Sq. Ft. Steam Water
Floor Area Occupied Inches
Firing Rate
Lbs. Coal or Gals. Oil
Per Hour
Water Base Line Height Inches Inches
Height Floor to Center of Crown Sheet Inches
Chimney Size Heigh Inches Feet
Oil Fired
4-S or W-10-0 4-S or VH1-0 4-S or W-12-0 4-S or W-13-0 4-S or W-14-0
2750 3100 3450 3800
4150
4525
5055
5575 6090
6640
54-3/4 x 70
54-3/4 x 77 54-3/4 x 84 54-3/4 x 91 54r3/4 x 98
9.1 10.1 11.0
11.9 12.9
55-1/2 55-1/2 55-1/2 55-1/2 55-1/2
12 12 12 12 12
34 16 x 16 30 34 16 x 16 35 34 16 x 20 40 34 16 x 2(1 10
34 16 x 20 45
4-SC or WC-10 4-SC or WC-11 4-SC or WC-12 4-SC or WC-13 4-SC or WC-14
3200 3600
4000 4400 4800
5205 5800 6400
7040 7680
*
54-3/4 X 70
54-3/4 X 77 51-3/4 x 84 54-3/4 x 91 54-3/4 x 98
Stoker Fired
115 55-1/2 128 55-1/2 141 55-1/2 153 55-1/2 166 55-1/2
12 12 12 12 12
34 16 x 16 30 34 16 x 20 35 31 16 x 20 40 34 16 x 20 45 34 20 x 20 50
*0n Hand Fired add 24" to length for Snoke Hood. On Oil and Stoker Fired add 3-1/4" for Smoke Collar.
"These ratings represent the maximum net londs (210 Dtu per sq. ft. steam and 150 Rtu per sq. ft. lint water) that may be connected to the boiler. Allowances have been made in these ratings for normal piping
(covered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be
served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
20527
is NO. 4 REDFLAffl BOILER (1929 - 1956) (Coat'd.)
Boiler No.
** Installed Radiation
Sq. Ft. Steam Water
Floor Area Occupied Inches
Firing Rate
Lbs. Coal
or Gals. Oil Per Hour
Water Line Inches
Base Height Inches
Height Floor to Center of Crown Sheet Inches
Oumney
Si H /vl
TnmKfii-
1 X-C,
Hand Fired
4-S or W-7 4-S or W-8 4rS or W-9 4r-S or W-10
4rS or w-ll
4-S or W-12
4-S or V-13
3000 3575 4150 4725 5300
5875 6450
4800 5720 6640 7560 8480 9400 10320
54-3/4 x 49 54-3/4 x 56 54-3/4 x 63 54-3/4 x 70
54-3/4 x 77 54-3/4 x 84 54-3/4 x 91
55-1/2 55-1/2 55-1/2 55-1/2 55-1/2 55-1/2
55-1/2
12 12 12 12 12 12 12
34 16 x 20 45 34 20 x 20 50 34 20 x 20 55 34 20 x 20 60
34 20 x 24 65
34 20 x 24 70
34 20 x 24 75
*0n Hand Fired add 24" to length for Snoke Hood. On Oil and Stoker Fired add 3-1/4" for Smoke Collar.
NO. 5 REDFLASH BOILER (1928 - 1956)
Boiler No.
**
Installed Radiation
Sq. Ft. Steam Water
Floor Area Occupied Inches
Firing Rate
Lbs. Coal or Gals. Oil
Per Hour
Water Line Inches
Base Height
Inches
Height Floor to Center of Crown Sheet
Inches
Chimney Size Height Inches Feet
Oil Fired
5-S or W-10-0 5-S or W-11-0 5-S or W-12-0 5-S or W-13-0 5-S or W-14-0 5-S or W-15-0 5-S or W-16-0 5-S or W-17-0
3900 4400 4900 5400 5900 6400 6900 7400
6240 7040 7840 8640 9440 10240 11040 11840
64-1/8 x 80 64-1/8 x 88 64-1/8 x 96 64-1/8 x 104 64-1/8 x 112 64-1/8 x 120 64-1/8 x 128 64-1/8 x 136
12.4
59-1/2
13-7
59-1/2
15.0
59-1/2
16.3 17.6
59-1/2 59-1/2
19.0
59-1/2
20.4 ` 59-1/2
21.8
59-1/2
12 12 12 12 12 12 12 12
33-1/2 33-1/2 33-1/2 33-1/2 33-1/2
33-1/2 33-1/2 33-1/2
16 x 20 20 x 20 2U x 20 20 x 20 20 x 24
20 x 24 20 x 24
20 x 24
30
35 35 40
45 50
55 60
S8*
O
$
>-*O
5-SC or WD-11 5-SC or WC-12 5-SC or WC-13 5-SC or WC-14 5-SC or WC-15 5-SC or WC-16 5-SC or WC-17
4500 5100
5700 6300 6900
7500 8100
8700
7200
8160 9120 10080
11040 12000 12960 13920
*
64rl/8 x 80 64-1/8 x 88 64-1/8 x 96 64-1/8 x 104 64-1/8 x 112 64-1/8 x 120 64-1/8 x 128 64-1/8 x 136
Stoker Fired
156 59-1/2 175 59-1/2 194 59-1/2 214 59-1/2 234 59-1/2 255 59-1/2 275 59-1/2 296 59-1/2
12 12
12 12 12 12 12 12
33-1/2 33-1/2
33-1/2 33-1/2
33-1/2 33-1/2 33-1/2 33-1/2
20 x 20 20 x 20 20 x 20 20 x 24
20 x 24 20 x 24 20 x 24 24 x 24
35 35 40
45 50
55 60
65
5-S or W-8 5-S or 14-9 5-S or W-10 5-S or W-ll 5-S or W-12 5-S or W-13 5-S or W-14 5-S or W-15
5000 5700 6400
7100 7800 8500 9200 9900
8000
9120 10240 11360 12480 13600 14720 15840'
*
64-1/8 x 64 64-1/8 x 72 64-1/8 x 80 64-1/8 x 88 64-1/8 x 96 64-1/8 x 104 64-1/8 x 112 64-1/8 x 120
Hand Fired
59-1/2 59-1/2 59-1/2 59-1/2 59-1/2 59-1/2 59-1/2 59-1/2
12 12 12 12 12 12 12 12
33-1/2 33-1/2
33-1/2 33-1/2
33-1/2 33-1/2
33-1/2 33-1/2
20 x 24 20 x 24 24 x 24 24 x 24 24 x 28 24 x 28 24 x 28 28 x 28
60
65 70
75 80
85
yo yo
*On Hand Fired add 28" to length for Smoke Hood. On Oil and Stoker Fired add 3-1/1" for Smoke Collar. **These ratings represent the maximum net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot water) that mqy be connected to the boiler. Allowances have been made in these ratings for normal piping (covered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
20528
NO. 12 IDEAL OIL BOILER (JACKETED) (1931 - 1942)
19
Boiler No.
``Installed
Firing Firing
fedimticQ Grate Rite fete Lbs.Fer Lbs. Per
iter Sq.Ft. Hour
Hour
Floor Area Obcupied Indies
Fire Box Dimensions Water
Indies Line Width Length Ins.
Heif^it
Floor to
Center
Ehse of Crown
Qdimey
Height 3ieet Size Height
Ins. Indies Inches Feet
S or W-0412 S or W-0512 S or W-0612 S or W-0712
510 815
660 1055 810 1295 960 1535
9
10.8 13.8
16.9 20.0
H-
32-5/8 x 34 32-5/8x42
32-5/8 x 50 32-5/8 x 58
23 x 23 x 23 x 2J x
22-1/450-3/8 32-3/4 32-3/4 30-1/450-3/8 12-1/2 32-3/4 38-1/450-3/8 12-1/2 32-3/4 46-1/450-3/8 12-1/2 32-3/4
8x8 8x8 8 x 12 8 x 12
30 30 30 35
3bsed on oil of 19,700 Btu per lb. //Dimensions apply to flush jacket. For extended jacket add 21" to last figure.
NO. 21 IDEAL STOKER BOILER (1932 - 1942)
SC or MC-421 SC or VC-521 SC or WC-621 SC or KO-721
510 710 910
mo
815 1136 1456 1776
*9
20 27
34 42
*Based co Goal of 12,500 Btu per lb.
34x34 34 x 42
34 x 50
34x58
53 x 22-1/4 55-3/8 23 x 30-1/4 55-3/8 23 x 33-1/4 55-3/8 23 x 46-1/4 55-3/8
7-1/8 7-1/8 7-1/8 7-1/8
37-3/4 37-3/4
37-y4
37-3/4
8x8 8x8 8x 12 8x 12
30 30
35 40
IDEAL AR00 ROUND BOILER (1929 - 1942)
S or W-1704 S or W-1904 S or W-2Q04 Sor W-2204 S or W-2504 Sor W-2804
No. 4 Ssries: Base, Fi repot, Single Section and Dome
200 320 1.4
24-3/4 Dia. 15 Dia. 47-3/8 13
275 440 1.88
26-1/2
17-1/2 44-1/4 12
330 530 2.23
28-1/2
19
45-3/4 12
380 610 2.62
32-1/8
21
45-1/8 12
500 800 3.53
34-7/8
23-V2 47-1/8 12
600 960 4.36
38-7/8
27
48-1/2 12
39-1/4 36-1/2 36-1/2 38-1/2
39 39-1/2
8x8 8x8 8x8 8 x 12 8x 12 8x 12
30 30 30
35 35 35
S or W-1705
S or W-1905 S or W-2005
S or W-2205 S or W-2505 SorW-2805
220 350 300 480
360 575
440 705 580 930 750 1200
No. 5 Series:
1.4 1.88 2.23 2.62
3-53 4.36
Base, Fi repot, Double Section and Done
24-3/4 Dia.
. 26-1/2 28-1/2 32-1/8 34-7/8 38-7/8
15 17-1/2
19 21 SJ-1/2
27
51-7/8 49-1/4 50-5/8
51 52-l/B
53-1/8
13 12 12
12 12 12
39-1/4 36-1/2 36-1/2 38-1/2
39 39-1/2
8x8 8x8 8x8 8 x 12 8 x 12 12 x 12
30
35 35 35 40 45
S or W-1706 S or W-1906 Sor W-2006 Sor W-2206 S or W-2506 S or W-2806
No. 6 Series: Base,, Firepot, Dbuhle Section, Single Section and Dome
240 335 325 520 330 610
460 735 625 1000
800 1280
1.4 1.88 2.23 2.62
3-53 4.36
24-3/4 Dia. 26-1/2 5B-1/2 32-1/8 34-7/8
3B-7/8
15 17-1/2
19 21 23-1/2
27
56-3/8 13 39-1/4 54-1/8 12 36-1/2 54-3/4 12 36-1/2
53-1/8 12 38-1/2 57-V8 12 39 58 12 39-1/2
8x8 8x8 8 x 12 8 x 12 8 x 12
12x 12
35 35 35 40 40
45
"These ratings represent the mexuuun net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot witer) that ray be connected to the boiler. Allowances hare been made in these ratings for normal piping (covered) and pick-up loads and for heating domestic hot water when not more (Inn two tnthrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
20529
20 IDEAL ARQOLA WATER BOILER (I932 - 1947) Coal Fired
Boiler No.
4-A, A) or A1 5-A, AJ or AI 6-A, AJ or AI 7-A, AJ or AI 8rA, AJ or AI 9-A* AJ or AI 10-A, AJ or AI
Installed fediatics
mater
120 170 220 270 320 370 420
AJ-0 or AI-0 6-A-O, AJ-0 or AI-0 7-A-O, AJ-0 or AI-0
8-A-O, AJ-0 or AI-0 9-A-0, AJ-0 or AI-0 10-A-0, AJ-0 or AI-0
150 200 250 300
350 400
Qrote Anno Sq.Ft!
0.67 0.90 1.13 1.36 1.59 1.82 2.05
Floor Area Occupied
Inches
Fire Box
Dimmsion
Inches Width Length
17 x 12 17 x 15 17 x 18 17 x 21 17 x 24 17x27
17 x30
12JJ/8
12-5/8 12-5/8 12-5/8 12-5/8 12-5/8 12-5/8
8-3/4 U-3/4 14-3/4 17-3/4 20-3/4 23-^4
26-3/4
Oil Fired
17 x 15 12-5/8
17 x 18 12-5/8
17 x 21 12-5/8
17 x 24 17 x 27 17 x 30
12-5/8 12-5/8 12-5/8
11-3/4 14-3/4
17-3/4 20-3/4 23-3/4 26-3/4
Base Height
Ins.
5 5 5 5 5 5 5
Height Floor to Center Of Crown Sheet Inches
36-3/8 36-3/8 36-3/3 36-3/8 36-3/8 36-3/8 36-3/8
5 36-3/8 5 36-3/8 5 36-3/8 5 36-3/8 5 36-3/8 5 3&-3/8r
ARCOLA WATER HEATER FOR HOT WATER SUPPLY (1942 - 1947)
Heater Number
1004-A 1005-A 1006-A 1007-A 100S-A 1009-A 1010-A
Number of Sections
4 5 6 7 8 9 10
Nominal
Capacity
Gallons
Coal
Oil
240 320 200 400 260 480 320 560 380 620 440 68Q 500
Length Inches
12 15 18 21 24 27 30
TAPPINGS
inlets Inches
thtlets Inches
1-2 1/2 1-2 1/2 1-2 1/2 1-2 1/2 1-2 1/2 1-2 1/2 1-2 1/2
2-2 2-2 2-2 2-2 2-2 2-2 2-2
Chirmev Size Height Inches Feet
8x8 8x8 8x8 8x8 8x8 8x8 8x8
30 30 30 30 30 30
30
8x8 8x8 8x8 8x8 8x8 8x8
30 30 30
30 30 30
Size of Smoke pipe
laches
6 6 6 6 6 6 6
NEW IDEAL ARCO ROUND BOILER (JACKETED) (1934 to 1939)
Boiler No.
S orW-181 S or W-201 S or W-221 SorW-222 SorW-223 S or l<M!52 S or W-253 S or W-282 Sor W-283
Height
`^Installed
Firing Firing Floor
foliation Grate Rate fete Area
Sq.Ft.
Area Ihs.Pbr Lbs.fer Occupied
Steam /
Watter
Sq.Ft*
Hour
Hour
Inches
Fire Box Dimensions Water
Inches Line Width Length Ins.
300 480 1.77 350 560 2.18 400 640 2.65 450 720 2.62 500 800 2.62
600 960 3.53 650 1040 3.53 750 1200 4.36
800 1280 4.36
26-1/2 Dia. 18 Dia.
28-1/2
20
31-1/4
22
32-1/4
22
32-1/4
22
35 25
35 25 39 28 39 a
38-5/8 38-5/8 33-5/8
47 51-3/4 48-1/2
53-1/2 50-3/8 55-1/2
Center Base of Crown
Height Sheet Ins. Ins.
Qiinney Size Hei^it Indies Feet
14 - 34-1/4 14 34-7/8 14-1/2 34 14-1/2 37-5/8 14-1/2 37-5/8
15-1/4 38 15--1/4 38 15-1/4 36 15-1/4 36
8x8 8x8 8x8 8x 12 8x 12 8 x 12
8 x 12 8 x 12 12 x 12
30 30
35 35 35 35 40
35 40
*(fcfBcities based cn water temperature rise of 25 F. per hour. 1
**Diese ratings represent the maxima net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot *ter) that may be connected to the boiler. Allowances have been mnde in these ratings for noreal piping (covered) and pick-up loads and for heating domestic hot water when not more Umn two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gpllons in 24 hours.
/Reooomended load sq. ft. E.D.R. Represents attached load - including piping - which may be placed on Boiler in accordance with accepted installation standards for economical operation.
20530
IDEAL MAGAZINE BOILER NO. 15 (1933 - 1937)
21
Boiler No.
Installed
Firing Firing Floor
radiation Grate fate fate
Area
Sq.Ft.
Area Lbs.Per Lbs.Per Occupied
-Steam Wtter Sq.Ft. Hour Hour
/4
Inches
Fire Box Dimensions Water
Inches line Width Length Ins.
Heij^t Floor to
Center Base of Grown Height Sieet Ins. Ins.
Chiuney Size Height Indies Feet
15-Sor #-04
15-S or W-05 15-S or 14-06 15-Sor #-07 15-S or #-06
400 550 700 850 1000
640 880 1120
m1350
1.82 2.60
3-33 4.16 4.94
33-3/4 x 27 33-3/4x33 33-3/4x39 33-3/4 x 45 33-3/4 x 51
40-5/8 40-5/8 40-5/8 40-5/8
40-5/8
None n it it ti
8x8 8 x 12 8 x 12 8 x 12 12x 12
35 35
40 40
45
25-Sor W-05 25-Sor VMS
25-5 or #-07 25-Sor W-06 25-S or Vf-09 25-Sor #-10
IDEAL MAGAZINE BOILER NO. 25 (1933 - 1937)
750 900 1200 1500 1800 2100
1200 1440 1920 2400 2880 3360
3-35
4.3 5.25
6.2
7.15 8.1
42-1/2 x 29-1/4 42-1/2 x 35-1/4 42-1/2 x 41-1/4 42-1/2 x 47-1/4
42-1/2 x 53-1/4 42-1/2 x 59-1/4
43-1/4 43-1/4 43-1/4 43-1/4 43*1/4 43*1/4
None
n
it
n
II
ii
8 x 12 8x 12 12x 12 12 x 12 12x 12 12x 16
35 35 35
40 40
45
S or #-98-7 S or #-92-8 S or W-92-9 S or #-92-10 S or W-92-11 S or W-92-12
1450 168C 1900 2130 2370
2600
2320 2690 3040 3410 3790 4260
NO. 92 IDEAL OIL BOILER (JACKETED) (1935 - 1942)
35-5 40.6 45.8 51.0 56.2
61.3
42-3/4 x ?7 42-3/4 x 63 42-3/4 x 69
42-3/4 x 75 42-3/4 x 81 42-3/4 x 87
29 x 35-1/2 29 x 41-1/2 29 x 47-1/2 29 x 53-V2 29 x 59-1/2 59 x 65-V2
52-3/4
52-3/4 52-3/4 52-3/4 52-3/4 52-3/4
None 11 M ri n M
33 33 33 33 33 33
4fesed on Ccal of 19 >700 Btu per lb.
12x 12 12x 12 12 x 16 12x 16 12x 16 12x 16
35 35 40 40
45 45
SC or VC-92-7 SC or VC-92-8
SC or VC-92-9 SC or VC-92-10 SC or VC-92-11 SC or VC-92-12
1450 1680 1900 a.30
2370 2600
NO.
2320 2690 3040 3410 3790 4160
92 IDEAL STOKER BOILER (JACKETED) (1935 - 1942) ea
55
62
71 80 88 97
42-3/4x57 42-3/4 x 63 42-3/4 x 69 42-3/4 x 75 42-3/4x81 42-3/4x87
29 x 35-1/2 29 x 41-1/2 29 x 47-1/2 29 x 53-1/2 29 x 59-1/2 29 x 65-1/2
52-3/4 52-3/4 52-3/4 52-3/4 52-3/4 52-3/4
None n M n if it
33 33 33 33 33 33
12 x 12 12x 12 12 x 16 12x 16 12x 16 12x 16
35
35
40 40
45 45
33ased oa Coal of 13,000 Btu per lb.
These ratings represent the neudinun net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot water) that any be connected to the boiler. Allowances have been trade in these ratings for noimi piping (cowred) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
/Recoomaided load sq. ft. E.D.R. Represents attached load - including piping - which tray be placed on Boiler in accordance with accepted installation standards for economical operation.
20531
22 NO. 7 IDEAL BOILER (1937 - 1941)
Boiler No.
Installed
Firing Firing
Radiation Orate Rate Rate
Su*Py*
An* f )w i Par* fKe Par*
Stew Ifeter-fiq.Ft. Hour* Hour*
Floor
Area
<y|
TnA^T
Height
Fire Box
Floor to Center
Dimensions Vfeter Base of Crwn
Incheg lane Uei^-.t Steel
Width Imgtli Ins. Ins. Ins.
(Hmey
SI "eight Indies Feet
Sor W-711 S or N-715 SorW-719 Sor W-723 Sor W-727 SorW-731 S or W-735 SorW-739
220 350 1.68 320 510 2.15
410 655 2.62 500 800 3.09 590 945 3-56 670 1070 4.Q3 750 1200 4.50
820 1310 4.97
Coal (Hand Fired)
29-1/2 X 18-1/8 29-1/2 x 21-5/8 29-1/2 x 25-1/8 29-1/2 x 28-5/8 29-1/2 x 32-1/9 29-1/2 x 35-5/8 29-1/2 x 39-1/8
29-1/2 x 42-5/8
18 x 11-5/8 46-3/4
18 x 15
46-3/4
18 x 18-7/16 46-3/4
18 x 22
46-3/4
18 x 25-7/16 46-3/4
18 x 29
46-3/4
18 x 32-7/16 46-3/4
18 x 36
46-3/4
12-1/4 32-1/4 8x8 12-1/4 32-1/4 8 x8 12- 1/4 32-1/4 8x8 13- 1/4 32-1/4 8x 12 12-1/4 32-1/4 8x 12 12-1/4 32-1/4 8 x 12 12-1/4 32-1/4 12 x 12 12-1/4 32-1/4 12x12
30
30
35 35 35 35 35
40
S or W-715-0 Sor W-719-0 Sor W-723-0 S or W-7J7-0 S or W-731-Q Sor W-735-0 S or W.739-0
340 410 480 550 620
690 760
545 655 770 880 990
1105 1215
8.0
9.5 10.5 12.0
13.5 14.5 16.0
"Based an oil of 19.700 Btu per Lb.
Oil Fired
29-1/2 x 21-5/8 29-1/2 x 25-1/2 29-1/2 x 28-5/8 29-1/2 x 32-1/8 29-1/2 x 35-5/8
29-1/2 x 39-1/8 29-1/2 x 42-5/8
18 x 15
46-3/4
18 x 18-7/16 46-3/4
18 x 22
46-3/4
18 x 25-7/16 46-3/4
18 x 29
46-3/4
18 x 32-7/16 46-3/4
18 x 36
46-3/4
12-1/4 12-1/4 12-1/4 12-1/4 12-1/4 12-1/4 12-1/4
32-1/4 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4
8x8 8x8 8x8 8 x 12 8 x 12 8x 12 8 x 12
30
30 30
30 30
35 35
SC or VC-919 SC or VC-923 SC or VC-927 SC or VC-931 SC or VC-935 SC or VC-939
410 490 570 650
730 810
655 W5
910 1040
1170
1295
cm
17.0
20.0 22.0 25.0 17.0 30.0
"Based an Coal of 12,500 Btu per Lb.
Stoker Fired
29-1/2 x 25-1/2 29-1/2 x 28-5/8 29-1/2 x 354-1/8 29-1/2 x 35-5/8 5&-1/2 x 39-1/8 29--1/2 x 42-5/8
18 x 18-7/16 46-3/4
18 x 22
46-3/4
18 x 25-7/16 46-3/4
18 x 29
46-3/4
18 x 32-7/16 46-3/4
18 x 36
46-3/4
12-1/4 12-1/4 12-1/4 12-1/4 12-1/4 12-1/4
32-1/4 32-1/4 32-1/4 32-1/4 32-1/4 32-1/4
8x8 8x8 8 x 12 8 x 12 8 x 12 8 x 12
30 30
30
30
35 35
Sor tf-Mll 390 625 S or W-0511 480 770
Sor W-0611 560 895 S or W-0711 640 1025 SorVWBll 730 1170 SorW-0911 810 1295
NO. 11 IDEAL OIL B0ILR (JACKETED) (1938 - 1942)
8.5 10.3
12.1
13.5 14.9 16.3
U
29-3/4 x 21 29-3/4 x 27-1/2 29-3/4 x 31 29-3/4 X 34-1/2
29-3/4 x 38 29-3/4 x 41-1/2
2
1
X
3
18 x 15
47-1/4
18 x 18-7/16 47-1/4
18 x 22
47-1/4
18 x 25-7/16 47-1/4
18 x 29
47-1/4
12-1/4 32-1/4 12-1/4 32-1/4 12-1/4 32-1/4 12-1/4 32-1/4 12-1/4 32-1/4 12-1/4 32-1/4
8x8 8x8 8x8 8x 12 8x 12 8x 12
30 30 30
35 35 35
4fesed ca oil of 19.700 Btu per lb.
//Dimensions apply to flush jacket. Fbr extended jacket add 23-3/4" to last figire.
"These ratings represent the gurigum net leads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. bot water)
that ny be occnacted to the boiler. Allaences have been nade in these ratings for nornal piping (covered) and
pick-up trads and for heating domestic hot water vdien not more then two bathrooms are to be served, or if the use of
domestic hot veter does not exceed 75 gallons in 24 hours.
O.
20532
NO. 24 IDEAL ARCOFIRE STOKER BOILER (1938 - 1942)
4
Boiler No.
SC or WC-824 SC or VC-924 SC or VC-1024 SC or 1C-1124 SC or VC-1224 SC or VC-1324
^Installed
Firing
tediation Grate fete
,, Sq.Ft. Area Lbs.Per Steam Vfater Sq.Ft. Hour
900 1440
1075 1720 1250 2000 1425 2280 1600 2560
1775 2840
Firing Floor
fete
Area
Lbs.Per Occupied
Hour
M
Indies
34 42-3/4 x 57
41 42-3/4 x 63
47 42-3/4 x 69
53 42-3/4 x 75
60 42-3/4 x 81
66 42-3/4 x 87
Fire Box
Dimensions Water
Indies
line
Width Lmgth Ins.
@
24 x 19-1/2 50-3/4
24 x 24-1/2 50-3/4
24 x 24-1/2 50-3/4
24 x 29-1/2 50-3/4
24 x 24-1/2 50-3/4
24 x 29-1/2 50-3/4
fese
Height
Ins.
m
12-1/2 12-1/2
12-1/2
12-1/2
12-1/2
12-1/2
Height Floor to
Center
of Crown
Qumey
Sieet Size Heioiif
tIns. Inches Feet
23 12x 12 40
4 12x 12 40 4 12x 16 45 4 12x 16 45 4 12 x 16 45
23 12 x 16 50
Minimum Hei^it ranges to 57-3/4" depending on Base Hei^it. @@ Minima tenges to 19-1/2".
S* Distance frcm Bottom Water Leg to Crow Sieet. * Based on Coal of 13,000 Btu per Lb.
S or W-64 S or W-65
300 480 375 600
NO. 6 IDEAL OIL BOIIfR TUXEDO OIL BOIlfR (1940 - 1942)
K
44-5/8 x 24-3/4 11-1/8 x 10 43 52-5/8 x 24-3/4 14-1/8 x 10 42
Dimensions of Refractory Brick Chamber
8x8 8x8
25 25
** These ratings represent the oaxinun net loads (240 Btu per sq. ft. steam and 150 Btu per sq. ft. hot water) that my be connected to the boiler. Allowances have been rade in these ratings for norml piping (covered) and pick-up loads and for heating domestic hot water when not more than two bathrooms are to be served, or if the use of domestic hot water does not exceed 75 gallons in 24 hours.
NO. 1-G STANDARD GAS BOILER (1928 - 1955)
Boiler No.
Installed Radiation Sq. Ft. Steam Water
1-G-S or Vf-4 1-G-S or W-5 1-G-S or W-6 1_G_S or W-7 1-G-S or W-8 1-G-S or Vf-9 1-G-S or W-10
395 530 670 810
950 1095 1240
715 960 1200 1440
1675
1915 2160
Note: Ratings shown are for insta
Floor Area Occupied Inches
19 x 25 23 x 25 27 x 25 31 x 25 35 X 25 39 x 25 43 x 25
A.G.A. Input MB!
180 240 300 360 420 480 540
Water Line Inches
30 30 30 30 30 30 30
Qiinrey
Diameter Height
Inches
Feet
6 20
7 20 8 20
8 20
9 20 9 20 9 20
20533
24
NO. 4-0 STANDARD GAS B0IIR (1928 - 1955)
Boiler No.
Installed Radiation
Sq. Ft. Steam Water
Floor Area Occupied Inches
A.G.A. Input MQI
Water Line Inches
Chi mey
Diameter Inches
Hnret,sige. ht t
4-G-S or W-6 4-G-S or W-7 4-G-S or W-8 4-G-S or W-9 4-G-S or W-10 4-G-S or #-11
1390 1690
1995 2300 2610
2935
2400 2880
3355 3835 4315 4795
27 x 41-1/2 31 x 41-1/2 35 x 41-1/2 39 x 41-1/2 43 x 41-1/2 47 x 41-1/2
600 720 840 960 1080 1200
43 43 43 43 43 43
9 20 10 20 11 20 11 20 12 20 12 20
4-G-S or W-13 4-G-S or W-15 4-G-S or #-17 4-G-S or W-19 4rG-S or #-21 4-G-S or W-22
3570 4230 4895 5565 6205 6520
5760 6765 7825 8895 9920
10435
61-1/4 x 41-1/2 69-1/4 x 41-1/2 77-1/4 x 41-1/2 85-1/4 x 41-1/2
93-1/4 x 41-1/2 103-1/2 x 41-1/2
1440 1680 1920
2160 2400 2520
43 43 43 43 43 43
13 20 14 20 15 20 16 20
17 20 17 20
4-G-S or W-25 4-G-S or W-28 4-G-S or W-31 4-G-S or W^33 4-G-S or #-37 4-G-S or #-41
7455
8385 9315 9940
11180 12420
11905 13405 14880
15875 17840 19840
115-1/2 x 41-1/2 127-1/2 x 41-1/2 139-1/2 x 41-1/2 153-3/4 x 41-1/2 169-3/4 x 41-1/2
185-3/4 x 41-1/2
2880 3240 3600 3840 4320 4800
43 43 43 43 43 43
18 20 19 20 20 20 20 20 22 20 24 20
Note: Ratings shown are for installations at elevations up to 2000 ft. All ratings are for Natural, Manufactured, Mixed, IA* and LP-Air gases.
A
Radiator Height Inches
15"
18"
20"
22"
PEERLESS COLUMN RADIATOR
(1901 - 1925)
1 Column Width 5-3/8"
Centers1-1/2"
2 Column Width 8-1/4" Centers 2-1/2"
3 Column
Width 9-3/4" Centers 2-1/2"
1-1/2" Sq. Ft.
per section 0.6 Sq. Ft. per lineal inch
2-1/4 Sq. Ft. per section
0.9 Sq. Ft. per lineal inch
1-1/2 Sq. Ft. per section 0.600 Sq. Ft. per lineal inch
2 Sq. Ft. pep section 0.800 Sq. Ft. per lineal inch
3 Sq. Ft. per section 1.2 Sq. Ft. per
lineal inch
4 Column Width 11-1/4"
Centers 3"
3 Sq. Ft. per section 1.0 Sq. Ft. per lineal inch
4 Sq. Ft. per section 1.333 Sq. Ft. per linehl inch
<1
20534
Radiator Height laches
1 Column
Wid.th_5-3/8" Centers 1-1/2"
PEERLESS COLUMN RADIATOR
(1901 - 1925)
2 Column
Width 8-1/4" Centers 2-1/2"
3 Column
Width 9-3/4" Centers 2-1/2"
25
4 Column Width 11-1/4"
Centers 3"
23"
1-2/3 Sq Ft.
2-1/3 Sq. Ft.
per section
per section
0.667 Sq. Ft. per
0.933 Sq. Ft. per
lineal inch
lineal inch
26" 2 Sq. Ft.
2-2/3 Sq. Ft.
3-3/4 Sq. Ft.
5 Sq. Ft.
per section
per section
per section
per section
.800 Sq. Ft. per
1.067 Sq. Ft. per
1.5 Sq. Ft. per
1.667 Sq. Ft. per
lineal inch
lineal inch
lineal inch
lineal inch
32"
2-1/2 Sq. Ft.
3-1/3 Sq. Ft.
4-1/2 Sq. Ft.
6-1/2 Sq. Ft.
per section
per section
per section
per section
1 Sq. Ft. per
1.333 Sq. Ft. per
1.8 Sq. Ft. per
2.167 Sq. Ft.
lineal inch
lineal inch
lineal inch
lineal inch
38" 3 Sq. Ft.
4 Sq. Ft.
5 Sq. Ft.
8 Sq. Ft.
per section
per section
per section
per section
1.2 Sq. Ft. per
1.6 Sq. Ft. per
2.0 Sq. Ft. per
2.667 Sq. Ft.
lineal inch
lineal inch
lineal inch
lineal inch
45"
5 Sq. Ft.
6 Sq. Ft.
10 Sq. Ft.
per section
per section
per section
2 Sq. Ft per
2.4 Sq. Ft. per
3.333 Sq. Ft.
lineal inch
lineal inch
lineal inch
Height Inches
13-5/16 13-5/16 13-5/16
PEERLESS WALL RADIATOR (1920 - 1953) TYPE A
Length or Width Inches
16-5/8 21-7/8 29-1/16
Thickness Inches
2-7/8 2-7/8 2-7/8
Heating Surface Square Feet
6 8 11
Height Inches
8
PEERLESS BATHROOM RADIATOR (1920 - 1948)
Length Inches
20-1/2
i |!
Thickness Inches
1-1/2
Heating Surface Square Feet
4-1/2
20535
26
CORTO RADIATORS (1927 - 1942)
Radiator Height T neb**
3 Tube
Width 4-5/8" Center* 2-1/2"
4 Tube
Width 6-5/16"' Centers 2-1/2"
5 Tube
Width 8" Centers 2-1/2"
6 Tube
Width 9-11/16" Centers 2-1/2"
7 Tube (Window)
Width 11-3/8" Centers 2-1/2"
20"
1-3/4 Sq. Ft.
2-1/4 Sq. Ft.
2-2/3 Sq. Ft.
3 Sq. Ft.
3-2/3 Sq. Ft.
per section
per section
per section
per section
per section
0.7 Sq. Ft. per 0.9 Sq. Ft. per 1.178 Sq. Ft. per 1.2 Sq. Ft. per 1.467 Sq. Ft. per
lineal inch
lineal inch
lineal inch
lineal inch
lineal inch
23" 2 Sq. Ft.
2-1/2 Sq. Ft.
3 Sq. Ft.
3-1/2 Sq. Ft.
per section
per section
per section
per section
0.8 Sq. Ft. per 1.0 Sq. Ft. per 1.2 Sq. Ft. per
1.4 Sq. Ft. per
lineal inch
lineal inch
lineal inch
lineal inch
26"
2-1/3 Sq. Ft.
2-3/4 Sq. Ft.
3-1/2 Sq. Ft.
4 Sq. Ft.
per section
per section
per section
per section
0.933 Sq. Ft. per 1.1 Sq. Ft. per 1.4 Sq. Ft. per
1.6 Sq. Ft. per
lineal inch
lineal inch
lineal inch
lineal inch
32" 3 Sq. Ft.
3-1/2 Sq. Ft.
4-1/3 Sq. Ft.
5 Sq. Ft.
per section
per section
per section
per section
1.2 Sq. Ft. per 1.4 Sq. Ft. per 1.733 Sq. Ft. per 2.0 Sq. Ft. per
lineal inch
lineal inch
lineal inch
lineal inch
38"
3-1/2 Sq. Ft.
4-1/4 Sq. Ft.
5 Sq. Ft.
6 Sq. Ft.
per section
per section .
per section
per section
1.4 Sq. Ft. per 1.7 Sq. Ft. per 2.0 Sq. Ft. per
2.4 Sq. Ft. per
line&l inch
lineal inch
lineal inch
lineal inch
14" 2-1/2 Sq. Ft. per section
1.0 Sq. Ft. per
lineal inch
17" 3 Sq. Ft. per section 1.2 Sq. Ft. per lineal inch
Radiator Height Inches
20"
23"
CORTO HOSPITAL RADIATOR (1927 - 1942)
3 Tube
Width 4-5/8 M Centers 3"
1-3/4! Sq. Ft. per section 0.583i Sq. Ft. per lineal inch
2 Sq.: Ft. per section .667 Sq. Ft. per lineal inch
5 Tube
Width 8" Center 3"
2-2/3 Sq. Ft. per section 0.889 Sq. Ft. per lineal inch
3 Sq. Ft. per section 1.0 Sq. Ft. per lineal inch
20536
o
OORTO HOSPITAL RADIATOR (192? - 1942) (Cont'd.)
Radiator Height -- -- Inches
26"
32"
38"
3 Tube
Width 4-5/8" Centers 3"
2-1/3 Sq. Ft. per section 0.778 Sq. Ft. per lineal inch
3 Sq. Ft. per section 1.0 Sq. Ft. per lineal inch
3-1/2 Sq. Ft. per section 1.167 Sq. Ft. per lineal inch
'j Tube
Width 8" Center 3"
3-1/2 Sq. Ft. per section 1.167 Sq. Ft. per lineal inch
4-1/3 Sq. Ft. per section 1.444 Sq. Ft. per lineal inch
5 Sq, Ft. per section 1.667 Sq. Ft. per lineal inch
27
ARCO RADIATOR U-l/2" Center) (1930 - 1939)
I
Radiator
3 Tube
4 Tube
6 Tube
Height
Inches
Width 3-1/2"
Width 4r-3/4"
Width 7-7/8"
19" 1.1 Sq. Ft.
1.6 Sq. Ft.
2.3 Sq. Ft.
per section
per section
per section
0.733 Sq. Ft. per
1.067 Sq. Ft. per
1.467 Sq. Ft. per
lineal inch
lineal inch
lineal inch
22" 1.3 Sq. Ft.
1.8 Sq. Ft.
per section
per section
0.867 Sq. Ft. per
1.2 Sq. Ft. per
lineal inch
lineal inch
25" 1.6 Sq. Ft.
2.0 Sq. Ft.
3*0 Sq. Ft.
per section
per section
per section
1.067 Sq. Ft- per
1*333 Sq. Ft. per
2.0 Sq. Ft. per
lineal inch
lineal inch
lineal inch
32" 3-7 Sq. Ft. per section
2.467 Sq. Ft. per lineal inch
AR00 SUNRAD (1938 - 1950) 2" Centers
cDepth |
5 7-1/2
Height
10 23
Heat Emission Sq. Ft. per section
2i 34
BASEBOARD RADIANT PANEL (1947 - 195D TYPE R
Depth 2-1/8"
Height 8"
Heat Emission Sq. Ft. per Lineal Foot
1.25
20537
AwERiCAN-c^tandapd PLUMBING AND HEATING DIVISION
AMERICAN RADIATOR & STANDARD SANITARY CORPORATION NEW YORK I B. NEW YORK
4
form No. 706*2
20538
lifho tn U S A