American Society of Heating and Ventilating Engineers Guide, 1935
RATE OF EVAPORATION
In problems of air conditioning and drying, as well as in other industrial applications of evaporation, such as cooling towers, it is desirable to determine the rate of evaporation. There are two distinct cases of evaporation. The. first case is that in which the source of heat is primarily from the water itself and in which the air temperature may even be raised.
Table 8. Thermal Properties of Water
Temperature
Deo F
32 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 212 220 240 260 280 300 350 400 450 500 550 600 700
Sat. Press.
Lb per Sq In.
0.0887 0.1217 0.1780 0.2561 0.3628 0.5067 . 0.6980 0.9487 1.274 1.692 2.221 2.887
3.716 4.739 5.990 7.510 9.336 11.525 14.123 14.696 17.188 24.97 35.43 49.20 67.01 134.62
247.25 422.61 681.09 1045.4 1544.6 3096.4
Volume Cu Ft
per Lb
0.01602 0.01602 0.01602 0.01603 0.01605 0.01607 0.01610 0.01613
0.01616 0.01620 0.01625 0.01629 0.01634 0.01639 0.01645 0.01650 0.01656 0.01663 0.01669 0.01670 0.01676 0.01690 0.01706 0.01723 0.01742 0.01797 0.01865 0.0195 0.0205 0.0219 0.0241 0.0394
Weight Lb per
Cu Ft
62.42 62.42 62.42
62.38 62.31 62.23 62.11. 62.00 61.88 61.73 61.54 61.39 61.20 61.01 60.79 60.61 60.39 60.13 59.92 59.88 59.66 59.17 -58.62 58.04 57.41 55.65 53.62 51.3 48.8 45.7 41.5 25.4
Specific
Heat
1.0093 1.0048 1.0015 0.9995 0.9982 0.9975 0.9971 0.9970 0.9971 0.9974 0.9978 0.9984 0.9990 0.9998 1.0007 1.0017 1.0028 1.0039 1.0052 1.0055 1.0068 1.0104 1.0148 1.020 1.026 ' 1.044 1.067 1.095 1.130 1.200 . 1.362
The second is that in which the heat for evaporation is obtained entirely from the air itself, in which case the air is cooled and the temperature of the water remains substantially constant at the wet-bulb temperature. Both cases, however, may be reduced to a common basis of calculation. It has been found that the increase in the rate of evaporation is nearly in direct proportion to the increase in the air velocity, and that it is in direct proportion to the difference in vapor pressure between the vapor pressure of the water and the pressure of the vapor in the air.
26
.
Chapter 1--Fundamentals of Heating and Air Conditioning
The general formula covering the experimental data may be expressed
as follows:
J - (<* + W ( - )
(17)
where
dw rate of evaporation,
di a = the rate of evaporation in still air.
b = the rate of increase with velocity,
e' = the vapor pressure of the liquid, e = the vapor pressure in the atmosphere.
v"= velocity. ------------ ------------------
-
____ _ __
The only difference between case one and case two is that in case one the vapor pressure of the liquid is one of the known or assumed factors, being dependent upon the known temperature of the liquid, while in case two, ' is the vapor pressure corresponding to the wet-bulb tem
perature of the air.
This wet-bulb or evaporation temperature is dependent upon the drybulb temperature and the moisture content, or upon the total heat of'the air as indicated in the previous paragraph.
The effect of air velocity depends upon whether the flow of air is parallel to the surface or perpendicular to the surface elements. For a flow of air parallel to a horizontal surface
w = 0.093 ^ 1 + 2^q ) (' - e) (approximately)
(18)
where
to = pounds evaporated per square,foot per hour.
v -- velocity of atmosphere over surfaces, feet per minute, e' = vapor pressure of the water corresponding to its temperature, e = vapor pressure in the surrounding atmosphere.
For transverse flow, as across a tubular surface, the rate of evaporation
is nearly doubled.
These relationships are indicated graphically on the chart, Fig. 3.
Since the difference in vapor pressures is substantially proportional to the difference between the wet- and dry-bulb temperatures (i.e., the wetbulb depression) the rate of evaporation is also, for case two, substantially proportionate to the wet-bulb depression.
In case fwo, the rate of sensible heat transfer from the air to the liquid to produce evaporation is substantially the same as the rate of heat, transfer with the same type of surface, without moisture being present, but with the same temperature differences. In other words, the rate of heat transfer depends upon the temperature difference only, whether the surface is wet or not. For example, it has been shown that the rate of heat transfer with air flowing across staggered coils (transverse flow) may be represented by the.formula:
_________ 1_ Ut = 0.0447 + 50.66
(19)