Document k4QExZmrmBzjbxe2868Zj9p0

Monsanto Monsanto Company 800 N. Lindbsroh Boulevard St. Louis. Missouri 83166 Phone: (314) 684-1000 ORGANIC CHEMICALS DIVISION February 18, 1971 Subject: Capacitor Aroclor 1242 vs. MCS 1016 On August 6, 1970 we sent to you the proposed specifications for MCS 1016 along with copy of our specifications for Aro clor 1242, so that the typical properties of these fluids could be compared conveniently. The two fluids appear very similar. You will recall that the purpose of MCS 1016 is to provide essentially the same characteristics as Aroclor 1242, except that higher chlorinated biphenyls have been removed, to help alleviate the PCB pollution problem. Our goal remains to be in large scale production of MCS 1016 by July 1, 1971. Pursuant to changing to MCS 1016, we sent a drum of it to you for examination and capacitor life test ing. Additional sample amounts can be made available, if needed. Our laboratory has completed a capacitor life test study of these fluids, extending over a period of 3,200 hours and in cluding exposure to voltage levels and temperatures consider ably in excess of the conditions prescribed in the commercial acceptance tests for the fluorescent lamp ballast type capa citors used in our study. These capacitors were 2.0 microfarad units of the type rated at 580 volts AC, and required to with stand 1.5x580 = 870 volts at 70C for 750 hours, . The severity of our test conditions is defined in the attached data. The results are essentially the same for both of the fluids and reflect excellent stability and capacitor life. While the number of capacitors tested was small (six Aroclor 1242 and five MCS 1016), the work was done under very carefully r 2- - ' . controlled conditions in our Research Laboratory. We have an extensive research program on materials for use in capacitor dielectric systems. We would be most pleased to have you visit our laboratory to review not only MCS 1016 but also other work assigned to serve our mutual interests in capacitor dielectrios. Our rather extensive new commercial facilities to produce MCS 1016 are being installed. As we are committed to the July 1, 1971 production date, please give us your findings and views from your testing work, at the earliest appropriate time. Believing that you may like another copy of the specifications for MCS 1016 and Aroclor 1242, we are pleased to enclose them. Best regards, cs Enclosures (f. tV- tfd-tnr?st`q 77 P. G. Benignus /f Market Manager* Dielectric Fluids 3 $ I. MCL000800 LIFE TEST DATA - PAPER CAPACITORS Te3t Conditions, Tan 6 , Capacitance, Failure Times Started 9-16-70 Temp. C Voltage Time, hrs. " Aroclor 1242 70 70 70 70 70 70 80 90 100 870 900 900 930 965 1000 1000 1000 1000 0 750 168 1274 336 168 168 168 168 168 *a .00338 1.979 ufd a .00344 a .00348 b .00360 b ,00303 b .00304 bb .00301 .00309 112 hr. bb .00341 .00472 12.75 hr 79.5 136.0 2 OK MCS 1016 .00348 1.996 ufd .00342 .00345 .00358 ,00318 .00320 hooiO *.00316 .00350 .00434 8.5 hr. 15.0 126.16 2 OK a) Measured at 600V, room temp, h) Measured at test voltage and temp. * line fuse blew, measured time was 148 hrs. MCL000801 CAPACITOR DIELECTRIC MCS 1016 (Similar to Aroclor 124k!, except that some of the more' highly chlorinated biphenyls Have been removed.) PROPERTY Appearance Color, APHA Acidity (ASTM D974, D664) Water (ASTM D1533-60) Inorganic Chlorides (ASTM D1821) Specific Gravity 25/15.5*0 (ASTM Dl8lO) Viscosity 37.8C (ASTM D88-56) Refractive Index 26C (ASTM DI807) Dielectric Strength (ASTM D877) Pour Point, PC (ASTM D97-57) Hydrolyzable Chlorine Compounds, (ASTM D1820-65) Hydrolyzable Chlorine Compounds, by Refluxing (ASTM D2441-65T) Thermal Stability (ASTM D1936-64) Distillation Range (ASTM D20-56) Resistivity, 100*C 500 volts DC at 0.05 inch gap (ASTM DII69) Dielectric Constant (ASTM 0924-49) 100 C; 60 Hz Power Factor (ASTM D924-49) 100 C; 60 Hz Flash Point, Clev. open cup (ASTM D92-57) Fire Point TYPICAL Clear, colorless liquid 10 0.001 mg KOH/g 40 ppm 0.02 ppm 1.364 73.8 SUS 1.6219 44kv -20" C 0.07 ppm 0.17 ppm 0.09 ppm 10# - 327C 90# - 342c 400,000 X 10^ ohm-cm. min. 4.88 0.1# 350 to 365F None to Boiling AROCLOR 1X4Z {Tri^hloroWphenyl) Specification Properties - September 27, 1982 PROPERTY TYPICAL Vioc. at 37.8*C. (ASTM D88-56) Specific Gravity at 25/15.5C. (ASTM D1810) Color, APHA Condition Acidity, mg. KOH/g. (ASTMD974, D664) Pour Point, C. (ASTM D97-57) Inorganic Chlorides (ASTM D1821) Refractive Index at 25 C. (ASTM D1807) Distillation Range (ASTM D20-56) C. corrected for stem and barometric pressure - Water content (ASTM D1533-60) Resistivity, 100C. 500 volts DC at 0.1 inch gap. (ASTM D1169) Dh'-lcctric constant, 100*C. at 1,000 cycles (ASTM D924-49) Flash Point, Cleve. open cup (ASTM D92-57)* Fire Point* Sulfates (ASTM D117-31)* Fixed Chlorine Content (Carius)* Specific Heat at 25*C. * 82 - 92 seconds Saybolt Universal 1.381 - 1.392 50 max. Clear 0.01 max. -14 or lower 0.05 ppm. max. 1.6Z'.0 - 1.6260 10% 325 min. 90% 360 max. 35 ppm. max 500 X 109 ohm-cm. min. . 4.7 to 4.9 170* to 200*C. None to boiling point None 43 J; 0. 5% 0.29 . , Evaporation at 100*C. for 6 hrs.* Dielectric strength (ASTM D877-49) at 25*C. KV min.* Hydrolyzable Chlorine Compounds, (ASTM D1820-6l)ppm. chlorides, max. Thermal Stability (ASTM D1936) ppm. chlorides, max. Coefficient of Thermal Expansion* (ASTM D1903) 0.4% max. 35 0.5 0.4 0.00068 cc. i cc./C. Not determined unless by special request. Recipients of P. C. Benlgnus letter dated August 6, 1970 are as followat Mr. Abe Xalsteln AEROVOX CORPORATION 740 Belleville Avenue Rev Bedford. Massachusetts Mr. Kurt Lopes CORXELL~DUBILXER 1605 Rodney French Boulevard New Bedford, Massachusetts Mr. Ray Clark ELECTRONIC COMPONENTS, INC.' 902 Crescent Avenue Bridgeport 8, Connecticut Mr. Robert E. Abbe GENERAL ELECTRIC COMPANY Capacitor Department John Street Hudson Falla, New York Mr. Howard Brown HERCULES, INC.* P, 0. Box 5038 Terre Haute, Indiana Mr, Ralph Mcyera MC CRAW EDISON IND.` Line Materials Company South Milwaukee, Wisconsin Mr, H. B. Vaught P. R. MALLORY Waynesboro, Tennessee Mr. T. Katazama MITSUBISHI MONSANTO CHEMICAL COMPANY C. P. 0. BOX 879 Tokyo, JAPAN Mr. C, R. Coleman MONSANTO CHEMICALS, LTD.* Ruabon - Denbighshire North Wales, UNITED KINCD0M ' ' ' Mr. Boyce Whitman SANCAMO ELECTRIC COMPANY Pickens, South Carolina Mr. Howard Davis SPRAGUE ELECTRIC COMPANY North Adams, Massachusetts Mr. Donald L. McClain WESTINGHOUSE ELECTRIC CORPORATION P. 0. Box 341 Bloomington, Indiana Dr. L. Kandelcorn WESTINCHOUSE RESEARCH Beulah Road Churchill Borough Pittsburgh, Pennsylvania MCL000804 P. 0* Benignus - St. Louis February 22, 1971 S \ MCS 1016 H. S. BERGEN - HBERO please circulate to? T. L. Oossage - TGOSS W. R. Richard - WRICH R. H. Munch - Queeny J. R. Fallon - JFALL J. 0. Bryant - JBRYA Pursuant to our production of MCS 1016 we felt it desirable to send the attached letter dated February 18, 1971 as a reminder and follow-up of our previous communication of August 6, 1970 to all our U.S.A. domestic and Canadian capa citor Aroclor customers. Ve are also sending a copy to Peter Marsh in Brussels. P. 0. Benignus cs MCL000805 Monsanto P. w. QannffOM MAMt ft toCATtMt B2SF May 9, 1973 *U*M" ncrcftiMCt PC Warning Letters, Dielectric TO Memo to File if On May 8, 1973# 1 reviewed the dielectric warning letters and the corresponding address list with Paul Benlgnus. The purpose was to verify the address list for these letters. Tab No. 2, Feb. 18, 1970# Olson letteri This letter went to all of our transformer Askarel customers. Apparently the letter went to both transformer and oapaeltor customers. The list Included In the file appears complete, per Paul Benlgnus. Tab Me. 7# May 11* 1970# Olson Lettert Benlgnus agrees with the list for this letter. Tab No. 8. May 12. 1970. Olson Letter: Benlgnus agrees with this list for this letter. Tab 19. Sept. 28 - Oct, 12. 1970, Graham Lettert Benlgnus believes Randy's list looks falriy oomplete for Randy's area of responsibility. Benlgnus however, does not know If other salesmen sent out slmlllar letters. Benlgnus suggests I oheok this question with Don Olson. . Tab No. 22, Deo. 15* 1970# Qraham Letter; Benlgnus believes that this letter was the result of Don Pogue'8 attempt to gain Information on estimated amount of Askarel for Incineration. Behlgnus suggests I oheok with Pogue on that possible mailing list. . Tab 34, Deo. 20, 1971# Bergen #1 Lettert This letter was sent to the transformer and capacitor customers. A letter was written to companies were we had a personal name to contact. Tab No. 35, Deo. 20, 1971* Bergen #2 Lettert This letter was sent to transformer and capacitor customers were we did not have a name to write to. Many of these letters went to the Offloe of the President. The oomblned list of 34 and 35 appears to be complete for these customers according to Benlgnw f| I 1 i ( s: i * IO ftCV. 1/P* MCL000806 FOB Warning Letters, Dieleotrio May 9, 1973 Page 2 Tab Ho. 24, Feb, 18, 1971 Benlgnus Letter: This went to all capacitor people only. Benlgnus is con fident that this letter went to the people on his "1970 list of customers* which list he pulled out of Ms file cabinet on May 8, 1973* This liBt should be the same list as used for letter Tab No. 14, dated Aug. 6, 1970. Tab Mo. 39, Feb. 4, 1972* Bergen Letteri Benlgnus agrees the mailing list is oorreot. Tab No. 4p, Feb. 7, 1972, Qossage Letter: Benlgnus agrees with the mailing list. Tab No. 4l, Feb. 28, 1972. Qossage Lettert Benlgnus agrees with this list.' These are people who bought transformer fluid of any quantity, over a period of the few years proceeding 1972. Note; Benlgnus commented that many of these letters were months in their making. Be stated that it seemed to take forever to get a letter written and approved for mailing since eaoh letter and each word was reviewed vezy oarefully. /mo