CHAPTER 43
1960 Guide
warm air or forced hot water systems the fan or circulator usually is controlled by a thermostat in the furnace or boiler and runs whenever the air or water temperature is above a mraanum value, as discussed in Chapter 26. If straight two-position control is used for this application, the on and off periods are relatively long and there is a tend ency towards cold drafts on the floor during off periods. If timed two-position control is used, the burner may be cycled (started and stopped) often enough to provide re sults very comparable to proportional control. The heat input to the home is proportioned continuously to the heat loss from the home. The fan of a forced warm air system or the circulator of a forced hot water system may be run almost continuously, thus minimizing the possibility of cold drafts.
Proportional control is used on residential applications when provisions are made for it in the design of the system. Face and bypass dampers on warm air systems, throttling valves on steam systems and three-way miring valves on
hot water systems are typical examples of controlled devices which permit proportional control. With these arrangements the burner usually is controlled by a thermostat in the furnace or boiler. Proportional control will permit nearly continuous circulation of warm air or hot water, thus re ducing cold drafts.
Automatic night set-back through the use of a day-night type room thermostat is a refinement frequently added to residential control systems. Though opinions vary regarding the amount of fuel that can be saved by automatic night set-back, tests made both in the warm air beating research residence and the I = B = R research home at the Uni versity of Illinois indicate that, on thermostatically con trolled systems, a posable fuel saving of from 7 to 10 percent may be obtained by reducing the house tem perature 6 to 10 F from about 10:00 pm. to 5:30 am.
It is often dearable to divide the house into two or more aones for greater accuracy of control and comfort. Each rone may then be maintained individually at the desired temperature level. The division into zones should be based upon exposure or occupancy; the most common division is usually found to be (1) the living section such as living room, dining room, den; (2) the sleeping section; (3) the service section such as kitchen, pantry, servants' quarters; and (4) recreational areas.
Further discussion of zone control principles has been given in Part II of this chapter.
Year-round residential air-conditioning systems which provide for heating in whiter and cooling in summer should be given the same consideration in selecting the control system as required for commercial air-conditioning systems. See Chapter 19. The basic principles are the gam* and the final results must provide for the comfort of the occupants. A reduction in investment for automatic controls may re sult in wasteful operation of the system and discomfort for the occupants.
Special thermostats have been designed to take care of the year-round residential air-conditioning systems. The changeover from heating to cooling is usually aiwunplishod by a selector switch which is part of the thermostat. In some systems the changeover is completely automatic by the ac tion of the thermostat. Generally, both the heating and cooling functions are controlled by timed two-position action. Some form of humidity control may be added. If so, normally, re heat would be required.
When an add-on unit is installed to obtain a year-round air-conditioning system by change of a straight heating system, it may be controlled separately or integrated with the heating control system. However it is the control system should be simple enough for the user to understand how to operate it effectively.
REFERENCE
*E. J. Brown and J. R. Fellows: Pressure Inwvo and flow characteristics of multiple-leaf dampers (ASHAE Journal Section, Heating, Piping and Air Conditioning, August 1957,
Automatic Control Terminology (American Society of Me chanical Engineers, 1954).
MacMillan: An Introduction to the Theory of Control
York 1951) Sn9ineerino
University Prem, New
E. W. F. Feller: Instrument and Control Manual for Bnomeen (McGraw-Hill Book Co, New York,
.A- Haines: Automatic Control of Heating and Air Conditiorimp (McGraw-Hill Book Co, New York, 1953, 1st ed )
^ Save Fueljor Victory (University of Illinois; Engineering Experiment Station Circular Series No. 47, p. 31).
CHAPTER 44
INSTRUMENTS AND MEASUREMENTS
Temperature Measurement, Pressure Measurement, Air-Flow Measurement, Air Change Measurement, Measurement of Air Currents, Humidity Measurement, Measurement of Mean Radiant Tefliperoture, Heat Transfer Through Building Materials, Combustion Analysis, Smoke Density Measurements, Sound and Vibration Measurements, Oeterminotion of Air Contaminants
HEATING and air-conditioning engineers and techni
4 = the temperature of the bath.
cians require instruments for both laboratory and field
4 the average temperature of the emergent liquid column
use. Somewhat more precision is attainable and essential in
of n degrees.
the laboratory, where research and development are under taken, than in the field, where acceptance and adjustment
tests are conducted. The purpose of this chapter is to de scribe briefly some of the more important instruments, aod to outline thedT uses and characteristics.
A thermometer can be appreciably affected by radiation from surrounding surfaces. If the temperature to be meas ured is approximately the same as that of the surrounding surfaces, radiation effects may usually be ignored. If the tem perature being measured differs considerably from that of
TEMPERATURE MEASUREMENT1- *
the surroundings, steps should be taken to minimize the ef fect of radiation* This is usually accomplished either by
Thermometers
Any device capable of indicating temperature is a thermom eter, but in r/immnn usage the term thermometer without qualification has come to signify the ordinary hquid-in-glass temperature indicating device. Mercury-filled,thermometers have a useful range from --40 F, the freezing point of mer cury, to about 1000 F, at or near which the glass usually softens. Lower temperatures can be measured with alcoholfilled thermometers for which the range is about --94 F to +248 F. The better thermometers have their scales,-either Fahrenheit or Centigrade, etched with acid into the glass which forms their stems.
Thermometers are calibrated during manufacture for at least two temperatures, frequently the freezing and boiling points of water, and the space between the calibration points is then divided into the desired scale divisions. The probable error for etched stem thermometers is plus or minus one scale division. For precise work, recalibration is frequently necessary to determine the proper corrections to be applied
shielding or by aspiration. Shielding is accomplished by plac ing highly reflective surfaces between the thermometer bulb And the surrounding surfaces. However, this must be done in such a way that air movement around the bulb is not ap preciably restricted.4 Improper shielding may increase rather than decrease errors. Aspiration is accomplished by drawing a high-velocity stream of air or gas over the bulb of the ther mometer.
Industrial-type thermometers are available for permanent installation in pipes or duets. These instruments are fitted with metal guards to prevent breakage, and are useful for many purposes. However, the considerable heat capacity and conductance of the guards or shields may introduce er
rors. To prevent errors in temperature measurements, ample
time should be allowed for the thermometer to attain tem perature equilibrium with the surrounding fluid. In reading a thermometer, the eye should be at the same level as the top
of the liquid column to avoid parallax.
to the scale readings.
Thermocouples
Liquid-in-glass thermometers are calibrated by the manu facturer for either complete or .partial stem immersion. If a thermometer which has been calibrated for complete im mersion is used at partial immersion, that is, with a portion of the liquid column at a temperature different from that of the bath, an emergent stem correction should be made. This correction may be calculated by Equation 1:
When two wires made of dissimilar metals are joined by soldering, welding, or merely by twisting, a thermocouple or thermo-junction is formed. An electromotive force, which de pends upon the temperature of the junction, is found to exist between the wires. When the wires are joined at two points a thermocouple circuit isformed. If one junction is kept at a temperature different from the other, an electric current
Stem correction = Kn (4 -- 4)
(1) flows through the circuit due to the difference in emf devel
where
oped by the two junctions. This phenomenon is employed for temperature measurements in thermocouple systems, one
K = the differential expansion coefficient of the mercury or junction being ordinarily kept at a constant temperature, as
other liquid in the glass. K may be taken as 0.00016 for in an ice bath, while the other junction is placed at a point at
Centigrade mercurial thermometers and 0.00009 for which it is desired to observe the temperature. In practice it
Fahrenheit mercurial thermometers. For values of K is desirable to utilize emf to indicate temperature because, at
for other liquids and for specific glasses, see Reference small or zero current flow, the resistance of the circuit is un
1. important. A high resistance millivolt meter is useful in some
n = the number of degrees of the liquid column emergent cases but the potentiometer yields better results. In the po
from the bath.
tentiometer the electromotive force generated by the thermo-
/
645