Document k0BBL4dKqwwDngD9Bz5zggnq

$AS / (Z- /AS' - J ASKAREL Inspection and Maintenance Guide DSV| 357667 STLCOPCB4086442 TABLE OF CONTENTS SECTION A TRANSFORMER ASKAREL Page I. Introduction....................................................................................................... 1 II. History of Trade Name Types............................................................................ 1 Table I -- The Composition of Transformer Askarels III. Table II -- Official Transformer Askarel Shipping Specifications.................. 2-3 A. General Electric Company's Transformer Pyranol A13B3B B. Westinghouse Transformer Inerteen PPO (7336-9) IV. Interchangeability and Stability............................................ ........................... 4 V. Directions For Handling and Personal Precautions........................................ 4 VI. Expected Service Life.................................... ................................. ................. 5 VII. Dielectric Strength -- Moisture Relationship............................. ............... A. Table III -- Dielectric Strength vs. Amount of Dissolved Water in Askarel and Mineral oil B. Table IV -- Approximate Solubility of Water in Askarel and Mineral Oil: 5 VIII. Table V -- Typical Values Found in Askarel Fluid Under Various Conditions of Use.................................................................................................... 6 IX. Check Points For Maintaining Askarel Insulation.......................... .............. A. General Considerations B. Modern Sealing Procedures C. The Older Sealing Arrangements 9 X. Periodic Fluid Inspection............................................................................ A. Visual Inspection B. Dielectric Strength 11 XI. Inspection Check List................................................................... 12 XII. Contamination in Transformers....................................................................... A. Table VI -- Effect of Common Insulation Materials on Power Factor and Dielectric Strength B. Table VII -- Effect of Common Insulation Materials on VolumeResistivity 12 XIII. Refining Askarel For Re-Use........... ............................................................... A. Filtering Through Dry Blotter Paper To Remove Moisture and Extraneous Particles. Table VIII -- Guide to Rate of Dissolved Water Removal By Filtration. B. Earth Treatment for Maximum Improvement of Power Factor and Volume-Resistivity 1. Procedure ' 2. Effect of Earth on Removal of Scavengers 3. Table IX -- Approximate Relationship Between Power Factor, Volume-Resistivity and Dielectric Strength of Transformer Askarel 14 XIV. Cleaning Arced Transformers.......................................................................... 15 XV. Sampling ASKAREL........................ ................................................................ 17 DSW 357668 STLCOPCB4086443 SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS Page I. Introduction......................................................................... ..................... . 18 II. Sources of Contamination........................................ ......................................... 18 III. Sealing Switches and Terminal Chambers....................................................... 19 IV. Askarel-filled Switches' Maintenance.................. ................. ......................... 19 SECTION C Monsanto Analytical Services on Transformer Askarel.................................. 21 Appendix A. Askarel Stability and Composition of ArcFormed Gas.................................. B. Solubility of Gas in Transformer Askarel........................................................ C. Approximate Vapor Pressure vs. Temperature ForTransformer Askarel-----D. Effect of Temperature on Dielectric Strength of Askarel................................ E. Viscosity of Askarel and Mineral Oil............................................... F. Density of Transformer Askarels........................................................ G. Thermal Conductivity....................................................................................... H. Heat Capacity.................................................................................................... I. Coefficient of Expansion...................................... --..................................... J. Fire-Resistance.................................................................................................. K. Seals, Properties and Procurement...................................... 23 23 24 24 24 25 25 25 25 25 26 DSW 357669 STLCOPCB4086444 ! Section A Transformer Askarel X. Xntroduct ion .. if The term aVsTkmarre*"l as defined by IEEE, ASTM. and the National 3Lfe'c'trical Code generally describes a broad class of non flammable synthetic chlorinated hydrocarbon insulating liquids widely used in transformers, reactors^ and accessory equipment operated at power frequencies. Askarels of various compositional types are in use* (for the general properties &hd types see ASTM D-2283). Under arcing conditions the g&ees produced, while consisting of predominantly non combus tible hydrogen chloride, can contain varying amounts of com bustible gases depending upon the askarel type. This manual describes the operating characteristics of trans ferer askarel liquid insulation and how it differs from fiifieral oil. Appropriate handling and disposal procedures both scrap askarel liquid and impregnated solid mate rials are given in accordance with the guidelines recommended By the American National Standards Institute. The information is based on facts gathered by Monsanto over a. 40 years as/producer of askarel, plus knowledge gained from the experience of transformer manufacturers and users. This guide outlines the very simple maintenance required for ctskarei fluid in "modern" transformers and offers sugges- tdh'S` for sealing and maintaining askarel in old units. we believe following this guide,/users will obtain maximum service DSW 357670 STLCOPCB4086445 -2- from askarel Insulation with a reasonable minimum of maintenance. If questions arise relating to the design- ' Ing and building of transformers, these should be referred to regular transformer suppliers. . ~. Monsanto gratefully acknowledges the assistance, guidance, and the contributions of certain data by the following: Edward L. Raab ----- General Electric Dr. T. K. Sloat -- Westinghouse Electric II. History of Trade Name Types .: "Askarel" is the generic name for the non-combustible ' liquid insulation and coolant first used by General Electric Company in 1932 for their Pyranol brand name fire-resistant transformers. Other brand names used by electrical manufacturers to desig nate transformer askarels used in their products include: Asbestol, Chlorextol, Inerteen, No-Flamol, Saf-T-Kuhl. Whatever the trademarked brand, the askarel contains chlorinated biphenyl ____ _ --- one of the best liquid insulations developed by science. This inert mate rial is chemically stable, fire-resistant, heat stable, non corrosive, and has high dielectric strength under the opera ting conditions encountered in transformers. DSW 357671 STLCOPCB4086446 -3- P In addition to manufacturing Aroclor (chlorinated biphenyl), . ^ Monsanto also mixes this dielectric fluid with chlorobenzenes * to produce the presently used Inerteen and Pyranol blends de scribed in Table I. Table I The Composition of Transformer Askarels Type D Method A STM D 2283__ Type E Type F Trade Names Inerteen 54201KA Inerteen 70-30 Inerteen 54201CM Inerteen 100-42 Pyranol A13B3B2 Ingredients ($ by wt.) Aroclor 1254, pentachlorobiphenyl 70 - Aroclor 1242, trichlorobiphenyl - 100 trichlorobenzene 30 - tri-tetrachlorobenzene - - phenoxypropene oxide scavenger 0.18 to 0.22 0.18 to 0.22 diepoxide scavenger 45 55 0.115 to 0.135 M ASTM Method D-2283* titled Chlorinated Aromatic Hydrocarbons // (Askarels) For Transformers, also lists the composition of all transformer askarels used at various times since 1932. Monsanto manufactures similar transformer askarel fluids in ft England where the trade name Pyroclor is used. , III. Interchangeability In general all transformer askarels are interchangeable. How ever, it is suggested that the transformer manufacturer be consulted prior to mixing In significant proportions or total substitution. DSW 357672 STLCOPCB4086447 L'Aii'iriY iTfcr^n>fii'fl'Trfif~V n li -4 * IV. Official Transformer Askarel Shipping Specifications t The official shipping specifications for the three modern transformer askarel fluids are shown in Table II. DSW 357673 i I STLCOPCB4086448 oo HO.. O H >1 4) CM Eh G-=r a> in G <d co G ON .8 s ce 4)oo p CVJ *rH XE bO o 4) hGfnt -4p) ga QftJ c X * <B X E *v o CB > p 60 ma C le a r P G G HS ErH w n ci) 4) Eh 4) G G G CO o m m ^ Eh M o< coo co Oft < co 3HOi <fDt ,, ot->> 4> . CM EH w G-=f G n o in 4> oo O~ ^~ 4)00 X S C P CVJ to o 4) Gey G ft 4) 4) ft HP ca P G G GHS 43 cB 4) Eh 4) G G G CO St Eh H 0< G X (B E X E CB X E G C8<- (B E <H O 4) in I-H o O in pH o COO CO in o p CM -=r O O ft o CVl I 4) G P G 4) & ft > o ft Eh 4) G ro O h co W ft <oo 03 CVJ rH G ec5 CO GG 4) Eh s G G Eh 4) >sC0 O ft < * X rGH (B E X E CB X . *< E G cB<- t> iB. ErHjsCj i0nn4d) o O in pH O COO CO VO o p CVJ VO U cvj CVJ G G VO ON rH <h G CO pH E X 4) *H <B ?HOO g X Po CVJ O Xo pH o mo CB ON P O CM VO Eo G P COCO -3- o 0 pH m cvj p CO 4) o o o vo CVJ t'-co G'yVfefc. pH .OOO O fto G OO O CVJ CVJ rH <B 4) O 3x inp n p oo >p + IO 4) COCVJ G 4) - a> c cvj g* 5^2 I 4) %^ ^p ^' ^^rrj.co xxO Sx.. Gp ^x4) CO vo o o o pH o pH CO 1 pH S rH ON < 4) E PX G cB P 3 H O H rH CO Eo < bO OOV CO G O t-CO 4) 3 O G GX 4) G vo _ CVJ -HO CVJ x o ca **.<!> G in pH o o CVJ * o 4) tH O ? P ? pH O CVJ O O X pH G\ VO TJ pH 4) 4) c g xs G CVJ PH X o ft X -P rH pH O ft 4) C-- (B VO P O O X CO E CO in o G000 P TGJ o pH P pH 4) H O O <B E ft G X ca ^ E O cB vo 3 O cB X E X O > (B E<- cB E p X *3 G O -H b O . . cBCO G X o o pH VO o in c p o vo co o n ino G 4) OOO 4) pH 3 o in-H 4> X O pH X rl rH in 1 HgH COON m e x P CVJ O CVJ O O ft 3 rH P xs m at o G C G x c iB O rl o p p GP E rH CO O CB t bo o o o in 5= 3 tH O o vo in c o t^cooo o\ CVJ PO CVJ CO CO CO bO E PO *fHt G in pH o 4) HpHOOOO G H E ^ 4f)t rOH in co pH StrH OCVJPPPP G 03 4) O o OX >&.icBH G ft X . 4) X P CO ph o ftooininma) E iH to (B X 0*0 4) CB -sf . p o o<- onvo b- x 3 X E cB P rH P O O rH Eo vo o G P G CVJ CVJ CO CO+ I pH P to cB E X 0 in XS G cB X G < g in o oP pH 4) in4) fcO-H pH in iB pH ft vo cvj in c p p Q) H 5 O O 4) pH 4) on < ow in m in moo ft x 4) O O rH rH rH CO 1 rHRHCOmvo onm< P ? pH CVJ O oofi b-- O oG oP oo o ft 3 4) 3 P EG O 0 aS 4) 1 ft E co G G <B X CVJ O bO O CO 0 4) OG 03 ViOm'"' c COlTirl WN ON o pH s CO VO pftH in I S --- 3 E-I VO 03 CO m 03 4) co i o Eh CO < 1 4) H in<- pH vo to soo OG ftP rH C-- ft < 03 aG Q QNO > > (B CO o mo 4ft)| O * O O hO <s G lo O S Oo o E OHA S rH O Eh So O OX ft CO O ON Eh G G CO Eh in O O O ft o < 4) i m CO P ft < to CVl pH pH G CO ft pH' < 4) > *rl m \CM- G v_rX P *> 03 rH oj o ph s mm o O e p q >ph 4>-=r 0 oj EH CVJ ft 4) G rH ft 60 bO CB p -a o >00 03 CO 60 CB P ft\ Cr'pP'rl O rH-=r X G < >iS G X cB W 4) ON ra ON > g w 4) b- 4)s--P EH CB o lO G-=f G<- -HO- o_ T) CO > rH CO G T3 rH .ft P Xi P I O I P ft ON pH TJ G rll) >< G CO b-0< W VO X O rHP Go cB^-r G CB T rH O 4) ft c ft < o bO t-- CVl rH 03 COO O ON 03 P rH...f.t....r.H....f..t.4) r--I G G ft O cB ft G O 4J P 60 P rH E o o > fNP G G P 4) H S rlPHrl O rH (B P bco io co CO rH >aPSPS >- ,, G P rH O O rH O pH 03 nP P O Eh O Eh 4) Eh (B O o} xi ft ft ft pH G rH O 'O GtH 4>C0 4)C0 4) 13 pH < rH < EOCO 30< hOW G cB G O C>BG, rH O rH GP G O <0 Q rH G P rH <D'-r 4)'--rH mw O O ft 03 CO 3 4) G 03 ft O O (B Or) rH O O O ^< ft ft > G H f4t) >, . O_ ft 3 ft CO ft ft -s- 4) P G 03 rH 4) GP O G XO o H 03 *3 O 4) G XG ft OO a ft 03 4) J30*3 >2 OO UJ pH iC s ft bO O E o P GG k rH o a> >> G -HP > P <B P G G rH hO rH O OT) GU O pH rH O G OO G OG O < H O 4) bO G 0) ` t> o CO STLCOPCB4086449 -6Pootnote 1 Askarels of various compositional types are used. Under arcing conditions the gases produced, while consisting predominantly of non-combustible hyarogen chloride, can include varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and cellulosic or other organic materials may, when arced, produce gaseous mixtures which are moder ately flammable. As a precaution, ouch gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas sfiace with dry nitrogen before any work is performed on tho apparatus. DSW 357675 STLCOPCB4086450 -7- fv. Ordering Instructions Monsanto's current policy is to sell askarel ' transformer fluids only to transformer manufacturers, and-'5-- Qthers interested in these fluids should contrct the manufacturers of askarel transformers and not Monsanl The transformer name plate indicates the transformer maker and usually gives sufficient data to identify the specific askarel fluid used. Vl Stability Askarel liquid insulation is highly pure, fire-resistant liquid made under close chemical control to meet the exacting specifications as shown in Table II. It does not vary In composition like the commercial range of mineral oils. Askarel insulation must never be mixed with mineral oil. Over two percent of mineral oil by volume in askarel be gins to lower Its fire resistance. Askarel does not deteriorate when exposed to air, heat, hot metal; it does not break down over long use to form conducting or corrosive chemicals; It does not oxidize or sludge. Askarel will remain perfectly stable year after year unless broken down by severe electrical discharge. # . DSW 357676 STLCOPCB4086451 T his guide is p u b lish e d by The In s titu te o f E le c tric a l & E le c tro n ic s E ngineers, In c ., 345 4 7 th S t r e e t , New Y o rk , New Y o rk 10017 -8 In modern transformers, the only real "enemy" of askarel Is contamination by water. Keeping askarel water-free will insure long-time service. . w Askarel is heavier than water. If water gets into askarel ` ^approximately insulation, only a tiny amount (L25 ppm) dissolves -- the rest floats on top. Askarel is very insoluble in water, only about 200 parts per billion of askarel dissolve in water, at normal temperatures. . VI i Precautions When Handling Drums, Tankcars-and,{Opening Trans formers The American Institute of Electrical and Electronic Engineers Guide No. 76, Dec., 1958 has been revised to give more de- tt tailed instructions and guidance For Acceptance and Main- tenance of Transformer Askarel In Equipment*./ The following are significant precautions: A. Keep Dry During Handling: 1 In handling, storing, sampling^inspecting askarel -- and in operating askarel transformers -- take every pre- . caution to guard the askarel insulation from exposure to high humidity and moisture contamination. Keep 5* 30 or 55 gallon drums of askarel dry; lay stored drums on their sides with the bung at the highest point from floor to keep water off the drum head (which can be sucked into the askarel by the drum "breathing"). This precaution is not necessary when drums are stored indoors. which is the preferred way-of Dtoringr-^- ^ i S'fc r p. ^ * DSW 357677 STLCOPCB4086452 ings should be collected and should- -9- To avoid leakage the drums used for askarel are of heavy construction. Sixteen gauge metal is used, with ' special rim seal and bung construction* , The drums should be drained as completely as possible and then flushed twice with kerosene type solvent to/re move all of the askarel. . be incinerated at high temperatures, e.g.^ 2000^to destroy the polychlorinated biphenyls (PCBs). gee Section A, VTI;' Tank cars used to transport askarels are in exclusive service and not used interchangeably for other products. All cars must be unloaded through the top (dome fitting) either by pumping or with controlled pressure using dry air or dry nitrogen. If nitrogen has been used for un loading it is necessary to advise the shipper so that when the car returns the nitrogen can be replaced with dry air before any one may enter the car. If the car is to be unloaded by pumping it will be neces sary to use a dryer on the air intake line to remove moisture. ' All tank cars are fitted with steam coils, which are . ict-J t n c r ri ii-ii"-i. available for unloading under extreme^conditions* f-^- lew -fecmperatu3?e-^_L__ Convenient handling and pumping temperatures and the re lated approximate viscosity ranges are given in Table III. DSW 357678 STLCOPCB4086453 -10- Table III Product Unloading, Handling and Pumping Tem perature C Approximate Viscosity SUS Pyranol A13B3B-2 15-40 \ 100-40 Inerteen 54201KA 20-55 Inerteen 54201CM 35-75 B. Use Ordinary Personal Precautions: 100-40 100-40 - Transformer askarel has been made, handled, and used for over 40 years. _ ... ........................... Softfr [. ,, . It can be handledlwith oly-minor precau tions. If accidentally spilled on hands, no serious skin irritation will occur. However, liquid askarel has a solvent action (similar to paint thinner) on the fats and oils of the skin and prolonged contact may lead to drying and chapping of the skin. In case of contact, wash off the skin with soap and water; remove and dry clean saturated clothing. Clean up spills with rags, sawdust or absorbent clay. Eye contact may result in painful irritation but no per manent damage to tissues. If askarel gets in the eyes, flush with large amounts of water. As with all eye first aid, refer to a physician. To relieve irritation, ct'n physicians have used Funt-ocai-ne as well as opthal- mic cortisone acetate solution, or castor oil. JL DSW 357679 STLCOPCB4086454 -11- Infrequent exposure to askarel vapors will not cause ill effects. However, prolonged exposure to high vapor concentrations should be avoided. If. hot askarel must be hand or confined area, provide the area witl ______ __ ust ventilation -- or -- wear an organic cartridge respirator approved by the U. S. Bureau of Mines. C. Precautions On Opening an Askarel Transformer: ........... Askarels of various compositional types are used. Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride^can yield varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and cellulosic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus. DSW 357680 STLCOPCB4086455 -12- VII| Avoid Environmental Pollution Transformer askarels contain polychlorinated biphenyls ,, (PCBs) which have been used in the United States and elsewhere over the past 40 years^for many industrial and consumer applications. During the past several years evidence has accumulated to indicate that PCBs are widely dispersed throughout the environment and that they can have adverse ecological and toxicological ef fects. The United States Government's Interdepartmental Task Force on PCBs, Com-72-104l9, in their March 20, 1972 report titled,"Polychlorinated Biphenyls and the Environ ment" recommended restricting PCBs to use in capacitors and transformers. This report is distributed by the National Technical In formation Service, U.S. Department of Commerce, Spring field, Virginia 22151. - A document titled,"Guidelines For Handling and Disposal , . of Capacitor and Transformer Grade Askarels, Containing and is available from Polychlorinated Biphenyls," has been prepared/byAthe `1 i American National Standards Institute, Committee C107* 155 East 44th Street, New York, N.Y. 10017. DSW 357681 STLCOPCB4086456 -13- The scope, objectives and the composition of this committee are: ANSI Committee C107 Scope: Procedures and guides for safe use^mainten ance and disposal of askarel and askarel-soaked materials used in electrical equipment. Objectives: 1. Source of technical information and advice for Federal, State, local authorities and all others concerned. 2. Encourage development of suitable disposal facilities and keep all concerned informed. 3. Serve as the advisory group for United States participation in international organizations: CEE, IEC, CIGRE. Composition: . Organizations act ive,, or represented by this ANSI committee include: National Electrical Manufac turers Association, Electronic Industries Assoc- - iation. Institute of Electrical and Electronic Engineers, American Society For Testing and Mate rials; Electric Light and Power Association; Cer- ; tified Ballast Manufacturers Association; Environ mental Protection Agency; Office of Environmental Affairs; DSW 357682 STLCOPCB4086457 -14- General Services Administration; National Bureau of Standards; Dept, of the Army; Rural Electrification Administration; Div. of Environ ____ mental Research, TVA; American Public Power Assoc., Water Pollution Control Federation; Food and Drug Administration; National Fire Protection Assoc.; ............... Underwriters Laboratories; and several sections of the U.S. Department of Interior The following are pertinent excerpts taken from the ANSI Guidelines for askarel transformers: 1. Labeling Askarel Transformers "All new askarel transformers should be labeled: Caution Hie Insulating Liquid In This Transformer Contains Polychlorinated Biphenyls (PCBs). Care Should Be Taken To Prevent Entry Into The Environment. In Case Of Malfunction Or Leaks, Consult The Instruc_ tion Manual Or The Manufacturer. The transformer manufacturer should make similar warning labels available for use on previously in stalled transformers." ' 22. Disposal of Liquid and Solid Wastes "Disposal of askarel fluid and askarel-soaked mate rials must be accomplished by means in which there is no significant release of askarel to the environ ment. At present, disposal Is accomplished by care fully controlled high temperature incineration of DSW 357683 STLCOPCB4086458 -15- liquids and soaked software; and by controlled dry .* land-fill burial of apparatus and other hardware from which askarel has been previously drained and washed." - "Present knowledge indicates that proper incineration should involve a suitable balance between dwell time and temperature in the incinerator plus oxygen availability and finally suitable scrubbers to re- .- move HC1 formed; eg. (l) two-second dwell time at approximate! 2000F and 356 excess oxygen in stack gas; (2) l-l second dwell time at 2700F*and 2$ excess oxygen in stack gas." The ANSI Guide lists the locations of facilities that conform with the above requirements. Monsanto has such an incinerator at the W. G. Krummrich Plant, 62201, Dept. A-246, Sauget, Illinois/ where> arrangements can be made for scrap askarel liquid disposal for a modest fee, ` / ..... currently 3 cents per pound. ' - For disposal of solid scrap a controlled dry land-fill ............ can used where permitted by Federal, State and local regulations. 33. Conditioning of New or Recycled Askarel Conditioning of new askarel or recycled askarel re-* . . quires Fuller's earth treatment. The spent Fuller's . DSW 357684 STLCOPCB4086459 -16- earth in cartridges or bags when replaced should be allowed to thoroughly drain over drip pans to remove as much liquid askarel as possible. The cartridge units of steel mesh construction should be placed in the "Steel Contaminated with Askarel" container for disposition. Cloth bags filled with Puller's earth should be placed in the "Scrap Burnable Askarel Waste" container for disposition. 4. Teardown of Transformers for Repair or Scrap a. Drain all askarel from the unit.either into a holding tank for reuse or into the drum labeled "Scrap Askarel"/for disposition, then allow suf ficient time for all the askarel to drain from the core and coils. ` b. Remove the core and coil assembly from the trans former and place it on the floor. Sufficient absorbent material should be placed on the floor to absorb any askarel fluid that still drips from the transformer. , c. Place all materials in the appropriate salvage containers during the dismantling for later dis position. d. All used materials. Including rags, sawdust, tape, etc., regardless of quantity, should be put into the appropriate containers for disposition. DSW 357685 STLCOPCB4086460 -17- Transformer Disposal The ultimate disposal of an askarei-filled transformer may be accomplished in either of two ways: a. Complete drainage and dismantling with the proper disposal of the askarel liquid and askarel-soaked components as described above. b. Disposition of askarel transformers by means of Junk or scrap dealers should be avoided unless a transformer is first drained, followed by soaking of the interior with a suitable solvent, such as kerosene. Accumulated liquids and washings are to be disposed of as described earlier. ^'jassC Expected Service Life "^Manufacturers indicate that ` properly designed and installed askarel transformers are expected to give trouble-free service for at least 30 years. Since their introduction in 1932, the manu facturers report finding the over-all failure rate to be less than 0.5$ for all units under test and service con ditions. The Edison Electric Institute's report (1956 1958) on their member utilities publishes the failure rate for askarel transformers as 0.13 per hundred banks per year. ' DSW 357686 STLCOPCB4086461 -18- Mr. Prank M. Clark, who Invented transformer askarels at the General Electric Company in the early 1930s, made the highly pertinent comment based on his many years of experience with G.E. Pyranol (askarel type) transformers that -- "The Important thing is to keep them dry -- otherwise leave them alone". ~ . These words of wisdom became especially applicable in more recent years when welding shut rather than gas keting became the main method of sealing askarel trans formers. These units are sold with the understanding that the liquid is in a normally hermetically closed system. v" ' ....................... General Characteristics of Transformer Askarel Fluid \ Appreciation of the following characteristics, as given in the IEEE Guide, leads to understanding the reasons for selecting dielectric breakdown voltage and moisture as the prime practical tests to judge the quality of transformer askarel fluid. AIso>due to these characteristics the power factor of transformer askarel will be normally much higher than the corresponding values for mineral oil. DSW 357687 STLCOPCB4086462 -19 In comparison:to mineral insulating oil, askarel is a relati- . ^ vely polar material; i.e., its molecules are dipoles, free to rotate around their axes and responsive to orientation by elec trical forces. Askarel also exhibits a much higher dielectric constant and capacitance than insulating oil, and these dif ferences must be kept in mind when interpreting electrical test data. Because it is relatively polar, and possesses high solvency power, askarel is much more electrically sensitive than mineral oil to traces of extraneous soluble polar materials, and conse quently the choice of constructional materials destined for use in askarel is very critical. This sensitivity is reflected in the power factor and resistivity (specific resistance) of the askarel. It is important to note that, with the exception of water, the dielectric breakdown voltage of askarel is not generally ad versely affected by many of the soluble polar materials to which its power factor and resistivity (specific resistance) are so sensitive. In fact, the dielectric breakdown voltage of askarel is somewhat greater than that of insulating oil. Therefore, the values assigned these dielectric fluids in newly supplied transformers are 30 KV min. and 26 KV min., respectively. DSW 357688 STLCOPCB4086463 -20- As with Insulating oil, askarel must be kept dry. It ^ can pick up moisture from exposure to humid atmosphere. Under similar conditions of exposure, askarel can pick up nearly twice as much moisture when measured on a parts per million weight basis. XJ Sampling, Transformer Askarel Fluid a _ The following precautions about sampling are quoted from the IEEE Guide. "Representative samples, whether of the complete contents or only parts thereof, are extremely important from the standpoint of evaluation of the quality of the product sampled. Obviously careless sampling procedure or con tamination in the sampling equipment will result in a sample that is not truly representative. This, generally leads to erroneous conclusions concerning quality and Incurs loss of time, effort, and expense Involved In se curing, transporting, and testing the sample. It Is strongly recommended that all of the procedures and pre cautions outlined in the latest revision of ASTM D 923 (Sampling Electrical Insulating Liquids) be followed.41 "Because of the high specific gravity (relative density) of askarel (greater than l), water and some other impu rities are most likely to be found at or near the surface. The top sample, therefore. Is considered to represent the worst condition." * DSW 357689 STLCOPCB4086464 -21- XI| Evaluation of Askarel Received in New Equipment __ -- Some users of askarel equipment find it desirable to make "as received tests'1 on all equipment. It is quite common to use the dielectric breakdown voltage test and visual appearance as the most significant tests. If suitable equipment and trained personnel are available additional information may be obtained from the power factor, color, and moisture content tests. In sampling askarel contained in apparatus extreme care must be exercised in order to obtain a representative sample. ASTM Method D 923 should be followed. New equipment with askarel exhibiting the following charac teristics is considered acceptable: ' Dielectric Breakdown Voltage Color Condition - Visual Water Content Power Factor at 25C ASTM Methods 30 kV min. D 877 300 max. (Straw color) D 2129 Clear . D 1702 35 ppm max. * D 1533 D 924, D150 The power factor of askarel taken from new transformers, reactors and accessory equip ment can reflect the presence of moisture, dissolved polar compounds, or other contami nants and may vary with the type of equip ment from which the sample was taken due to the different ratios of liquid-to-solid in sulation and to the high solvency power of the askarel. Given an acceptable water con tent and dielectric breakdown voltage of the askarel as indicated above, a high power factor seldom impairs the serviceability of the askarel within rather broad limits and is indicative of the degree of extraneous soluble polar materials present. oSnN 357690 STLCOPCB4086465 -22- Recognizing the possibility of a wide range of power factors being recorded for askarel . in new equipment, it is difficult to establish a single limit which would be acceptable to both suppliers and users for all applications. However, as a broad guide, power factors up to about 10$ at 25c and 60 cycles per second (hertz) do not in general indicate any abnormal con tamination providing that the other criteria (water content, dielectric breakdown voltage, etc.) are met. Much higher power factors may indicate excessive contamination or the misap plication of the solid materials used in manu facture in contact with the askarel and should be investigated. XIIi Dielectric Breakdown Voltage - Moisture Relationship The dielectric breakdown voltage of askarel is highly sensitive to excess moisture; not sensitive to ordinary . dissolved polar materials. While the dielectric breakdown voltage can also be lowered by severe arcing, . askarel turns noticeably black or has particles of sooty carbon floating in it if arcing has occurred. Then the transformer should be repaired and the askarel replaced. If the dielectric breakdown voltage is checked periodically and decreases significantly -- this indicates moisture pick-up, arcing, or both. When the dielectric break- voltage has dropped to 26 KV or less, an analysis for water is necessary. If water is found in excess of 40 ppm at room temperature, its source should be loca ted and corrections made. DSW 357691 STLCOPCB4086466 23- When the moisture content approaches 125 ppm (satura tion level at room temperature), the dielectric break down voltage of askarel drops below the value required for efficient insulating. The moisture content should '.i not be allowed to rise over 70 ppm, sampled at opera ting temperature. If the moisture content is found to be in a satisfac tory range and the dielectric breakdown voltage is low, the transformer manufacturer should be consulted. CLTable -Hf* shows the relationship of dielectric break down voltage vs. moisture and Table tv indicates the approximate Water solubility limits in askarel and mineral oil. . Table . Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil Breakdown Voltage (ASTM) Water Content (PPM) 0 20 4o 60 80 110 - Askarel 70 KV 55 47 40 38 10 Mineral Oil 50 KV 39 30 26 22 5 Table |fV ` APPROXIMATE SOLUBILITY OF WATER IN TRANSFORMER * ASKAREL AND MINERAL OIL Temperature c. F. Amount of Water (PPM) Dissolved Askarel Mineral Oil --30 --20 --10 0 10 20 30 40 --22 --4 14 32 50 68 86 104 8 16 28 41 65 94 128 170 8 10 13 20 33 58 . 85 130 & & STLCOPCB4086467 -24- Xlfcjt. Turbidity .may be the visual sign of undissolved water, or may * indicate dirt. Cloudiness may also result from cold precipitation of tin tetraphenyl "scavenger" that was used in the earlier Pyranols, This scavenger begins to come out of solution around 15P. above zero. To redissolve it requires heating to 150-200F and agita tion. High dielectric breakdown voltage will quickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askarel is still excellent. However, if the dielectric strength is below 26 KV, moisture should be determined, using the Karl Fischer method (ASTM D1533-60). . The dielectric breakdown voltage test for askarel serves primarily as an indicator for moisture. It is by far . the most important maintenance test for transformer askarel. x|v. Check Points for Maintaining Askarel Insulation A. General Considerations: ' Modern askarel transformers with welded construction or silicone or Viton gaskets hand hole-.cover. switch and terminal compartment coversJ with properly constructed bushings require little or no maintenance. With properly constructed transformers, annual or semi-annual visual inspection and dielectric break- DSW 357693 STLCOPCB4086468 -25- down voltage test of the askarel fluid should suffice for routine maintenance checking over many years of service. . However, many askarel units were installed in the early 1930s ~ before the development of some of the better modern gasketing materials and before improved designs were developed for sealing out moisture. Such early units should be, and can be, modernized. Leaky or deterio rated gaskets should be replaced. If the aska rel has become contaminated, it should be re conditioned. At the same time, a general clean up of the unit and possible refinishing may be desirable. If it is not convenient to take an old transfor mer out of service for general repairs, leaky gaskets can be sealed temporarily by painting over the leaky area with epoxy cement. A survey of users indicates a good number of early-built askarel transformers (over 20 years old) are kept in continuous service in critical installations by the following steps ^instead lof modernization). . DSW 357694 STLCOPCB4086469 . --26The operating units are equipped with compound pressure gauges for reading pressure above and below atmospheric. Positive pressure is maintained on the shell by introducing nitrogen at 2 to 3 pounds above atmospheric. Regular workmen in the area daily record the temperature and pressure. If a sudden pressure drop is noted more nitrogen is introduced and the gaskets are checked for leaks with soap solution. Leaks are sealed by applying epoxy cement. ,, ~' ; B. Modern Sealing Procedures: Transformer purchasers should specify the follow ing modern techniques for sealing: 1. Welding Construction: Covers, radiator con nections, switch and-terminal housings, in- strument connections, etc. should be welded. 2. Bushing Connections: A number of bushings have been developed to obtain a proper seal for the electrical connection through the tank wall. They are classified as follows: l) Welded Type - (Bushing flange welded to tank wall) - a. Cast resin bushing with a molded seal to the bushing stud and external stain less steel or copper flanges. b. Rolled Flange bushing with the metal to porcelain seal at the cap and flange ` . DSW 357695 STLCOPCB4086470 -268- made by being rolled into grooves in the procelain over silicone rubber rings. The seal between the cap and stud is made by welding. . c.-. Porcelain or glass bushings with metal to glass or metal to porcelain seals. 2) Bolted Type - (Bolted to tank wall) a. Cast resin bushings with either cast or metal flanges containing recessed gasket grooves. b. Porcelain or glass bushings with flanges containing recessed grooves or gasket stop. The gaskets may be either of rectangular or circular cross section, usually 1/4 inch thick. Bushings with recessed grooves are suitable to use with cork, cork-nitrile rubber combinations or nitrile rubber as well as gasket materials such as silicone or Viton. rJ` II i DSW 357696 -- ,J, y--- J l i l i U.. Ill .1 n.-.-J. j -r ' , ' i . u , II .iinn i 'i.i,, t . ... STLCOPCB4086471 -27- 3 Small Size Connections: When not possible to weld, small size connection seals should be made with Flexitallic stainless steel rings. The surfaces must be machined and parallel. The filler between the steel laminations of the Flexitallic ring should be either silicone or Viton. 4. Gaskets For Hand-Hole Covers: Modern design specifies;silicone gaskets. Such gaskets must be retained in a groove. The groove preferably is machined into the flange or cover. However, it can also be formed by welding, concentric steel strips to the flange or the cover. Generally the gaskets should be 5/l6 "to 1/2 in. thick for covers, depending on the depth of the or stop. cross groove'/ A rectangular/section is usually used. T The silicone material should be Dow-Coming No. 50 Silastic or equivalent. This is a low com pression set material. For best sealing 20-tcr^ 25$6 compression is recommended, with ample . or stop clearance in the groove/to allow for this com- prfession. No cement is required. With reasonable care the gasket is removable without damage and is re- useable. DsW 357697 , STLCOPCB4086472 -28- Si las tic 50 is slightly swelled by askarel which contributes to the tightness of the seal. It is not deteriorated by askarel fluid or vapors. It resists weathering and it is thermally stable and flexible at all operating temperatures. It is an excellent moisture barrier. .1 Notes: a. Dow-Corning, Midland, Michigan will supply a list of Silastic 50 gasket fabricators to all transformer manufacturers or users. They will also furnish technical data. See Appendix K: Seals, Properties and Pro- , curements. . C. The Older Sealing Arrangements: . The older type gaskets consist of either cork or cork-nitrile rubber combinations or straight nitrile rubber. ' 1. Cork-Nitrile Combinations: Covers for the main tank, hand-holes, switch and terminal chambers, relief diaphrams etc. are held in place by studs DSW 357698 STLCOPCB4086473 -29- welded to the flange or by bolts. The gaskets are cut with openings and placed over the bolts* Often Shellac (Westinghouse Style No. 1150419* or General Electric Company*s Glyptal 1276) is used to cement the cork to the flanges. The following is recommended for sealing with the cork -- nitrile rubber combination: . Use Armstrong NC-757 cork-nitrile material or * equivalent. The gasket can be cut from a single sheet or by scarfing strips of the material. A convenient method for Joining strips is to make purpi-n a Keystone Type Joint. For this^ Westinghouse* Sharon, Pa., offers their gasket cutter Style No. 328 B6l4 G01, (about $15). t>&0 i^'JL . The Joints^ should be cemented andr-tho gasket--also-- cemented to the flange, using one of the above cements. Excess cement should not be allowed to reach the interior of the transformer. , After installation and bolting, the outside edge of the gasket should be coated thoroughly with epoxy cement to increase weather resistance. This epoxy cement is a paste to which a curing catalyst is added immediately before use. Typical are: OSW 357699 i^r> W STLCOPCB4086474 -30- a. Epoxy Patch Kit #1-C Hysol Corporation, Olean, N.Y. . b. Scotchcast Resin #4 Minnesota Mining and Manufacturing Co. St. Paul, Minnesota c. Adhesive A-l and Activator Type B Armstrong Products Company Argonne Rd., Warsaw, Ind. d. Adhesive 986O-I, Synthetics Organic Company, ` Cleveland, Ohio, used with activator diethy lene triamine (Carbide and Carbon Chem. Co.) 2. Straight Nitrile Rubber: When straight nitrile rubber was originally used, invariably the gas ket was recessed in a groove. This was to pre vent gasket flow and to protect the material against excessive compression. Although this type seal was not cemented, the -nitrile rubber gasket is not reuseable. Since grooves or stops have already been provi- ' ded for the nitrile rubber seal. Silastic 50 can be easily substituted and is recommended. This conforms with modem practice. ' XVi Periodic Fluid Inspection and What Checkpoints Mean* On a regular schedule -- at six, nine, or twelve-month intervals -- make a simple visual inspection of your askarel insulation and run a dielectric breakdown vol tage check. DSW 357700 STLCOPCB4086475 -31- A. Visual Inspection: Askarel is a clear, faint-yellow liquid. After long term use this color may gradually intensify to light brown. The fluid should remain clear and free from turbidity or cloudiness. Any color change -- such as to a green, red or blue cast -- indicates extraction of impurities (color materials) from the solid insulation. If a distinct foreign color pick-up is noted, check the complete range of electrical'characteristics and notify the transformer maker. Blackening of the askarel may indicate an arcing condition. Other color changes / alone are not danger signals since the dielectric . breakdown voltage is not likely to be Impaired. B. Dielectric Breakdown Voltage If the dielectric breakdown voltage has decreased significantly from the last inspection, or if it has gradually decreased below 26 KV range (at 25C). -- RUN A CHECK FOR MOISTURE. Use ASTM D1533 (Karl Fischer Method). The dielectric breakdown voltage of askarel Is the major indicator to the operating efficiency of your liquid insulation. Besides the ^visual" Inspection tests, dielectric breakdown voltage Is the only test necessary to run on a routine basis. Well- sealed askarel transformers have service records of 25 to 30 years on the original askarel. dsw 357701 STLCOPCB4086476 -32- XVI. Inspection Check List w 15 1. If askarel is clear,- even though darkened to light brown, has no sediment or turbidity, has dielectric breakdown voltage over 26 KV tion " 0K,r. , g~i ve it the inspec- V 2. If askarel Is clearf^has foreign color of blue, green, red ... it is "extracting color" from internal mate rials. This is not, of Itself, an operating hazard when the dielectric breakdown voltage stays over 26 KV and moisture remains low. However, this rare oc- currance calls for checking into^condition of the interior construction and consulting the transformer maker. However, when sampling the fluid care should be taken to avoid getting color into the askarel from paint that may be inside or outside of the sample valve. 3. If the moisture content is found to be above 70 ppm at operating temperature, then sampling should be done at more frequent intervals to establish a possible trend, particularly on out^door installations. 4. If askarel is clear, but dielectric breakdown voltage drops to 22 or lower KV, and moisture rises over 80 ppm when sampled at operating temperature ... the askarel is ready for simple "refining". If the mois ture Is near the saturation level (about 125 ppm) at at room temperature^ a thorough inspection should be made for water droplets in the transformer tank. DSW 357702 STLCOPCB4086477 -33- and even for "globules" o|*/ water floating on the askarel surface. If found, the transformer manu facturer should be consulted for reconditioning both the transformer and the fluid. 5. If askarel is dark brown to black, if black par ticles of carbon are seen, and dielectric strength ' i\' ' is low. the askarel has been broken down by arcing. It cannot be refined and should be removed and incinerated under proper conditions. (See ANSI . Committee C 107 report on Use and Disposal of Askarel and Askarel-Soaked Materials. 155 East 44th Street, New York, New York 10017). If any of these four simple inspection tests appear out of the ordinary^or the relationship between appearance and test values is abnormal^H contact your transformer supplier for a complete analysis. Whenever a sample is to be shipped to Monsanto, please follow the directions shown under: "SAMPLING ASKAREL". ' XVII. Contamination in Transformers Moisture, particulate matter and arced decomposition products are known to be serious contaminating influences on transformer askarel. The power factor test normally used for the detection of confc amination in mineral oil* filled transformers is of little use for this purpose in askarel filled trans- DSW 357703 STLCOPCB4086478 -34- q formers, ... ue 0 . extreme effect of ex traneous soluble polar materials. This increase in power factor as illustrated in Table V has no adverse effect on dielectric breakdown voltage. Table VI EFFECT OF COMMON INSULATION MATERIALS ON POWER FACTOR AND DIELECTRIC STRENGTH (HEAT AGED 96 HOURS IN ASKAREL AT 100C.) Material Immersed None (control).................................................... Black varnished cloth....................................... Copper................................................................. Pressboard........................................................... Manila paper..................................................... Phenol formaldehyde resins............................ Shellac.................................................................. Iron....................................................................... _ ,Synthetic rubber............ ................................... .. . ___ ______ Askarel After Exposure Power Factor, Percent at 60 eye., IOOC. Dielectric Strength 25C. 1.0 85.0 1.5 2.0 1.5 1.6 6.0 5.0 70.0 35 KV 42 40 37 39 41 36 * 39 39 . Similarly, trace contaminants from commonly used con struction materials can lower the volume-resistivity of askarel, without affecting its dielectric breakdown . voltage.. Table ^-shows-this^ThiS \s m Table VII EFFECT OF COMMON INSULATION MATERIALS ON VOLUME . RESISTIVITY OF ASKAREL i Sample 1. New askarel before heat aging.............................. . 2. New askarel after heat aging 96 hours at 100C. 3. After heat aging with 1 sq. inch specimens of: . a. Phenolic resin tap changer material............... b. Paper....................................................................... c. Grade A press board (tan)................................ d. Grade A press board (gray).............................. e. Grade A press board, laminated strip............ f. Cotton wrapping.................................................. g. Glyptal 1276 cement, cured 48 hrs. at 110C. i Volume Resistivity x 10* ohm-cm (at 100C., 500 Volts DC., 0.1* gap) 2,000 1,900 1,200 750 500 500 400 300 100 -------------- ----------- ' ' nA OSNN^1042 3 STLCOPCB4086479 -35- While trace contamination easily lowers volume resisti vity from high levels, it is important to note that ' heavy contamination (as when arced) does not lower the resistivity below the order of 109 ohm-cm. at 100C. The different behavior of askarel vs. mineral oil in these respects can be summarized as follows: High power factor and low volume resistivity in transformer mineral oils are commonly re garded as "danger signals" that the oil has deteriorated and broken down chemically or excessive moisture is present. This is NOT TRUE of askarel liquid insulation,__<_ unless the dielectric breakdown voltage is low^_^ or the moisture content is high. Manufacturers of askarel type transformers point out that it is quite well known that askarel transformers with initial power factor of the askarel fluid in excess of 50# at room temperature and 60 Hz are giving satis- ' factory service life. However, there needs to be assurance that both dielectric breakdown voltage and moisture are at satisfactory levels and do not show adverse trends. DSW 357705 STLCOPCB4086480 -36- XVIII. ASTM Method For Investigating The Compatibility of Transformer Insulation and Construction Materials in Askarels ' ' This method^--which is presenly--in-process -of-publi^--K--- ^--cat-icur by A5TM uses the change of electrical and/or chemical characteristics of transformer askarel result'iis . ing from,^ controlled exposure to insulation and con struction materiaIs,a to evaluate their immediate major "contamination" effect on the askarel fluid. Delayed or long time "contamination"^effects may not be detected. The method also utilizes various physical tests on the insulation and construction materials after controlled exposure to the askarel to determine the compatibility of these materials with transformer askarel. Properly proportioned specimens of the insulation or structural materials are immersed in refined askarel for 168 hours at 100^1C in a forced draft oven. Changes in electrical and chemical properties of the transformer askarel are compared against a control sample of the askarel treated in the same manner, in absence of the test specimens. Dissipation factoi> (ASTM D924^ change is one of the criteria used. The askarel fluid is refined by adsorbtive treatment to a dissipation factor level of 0.05 max. at 100C and 60 Hz and 0.01 max. at 25C and 60 Hz. I* prccesi publ.ct.W flirw, ^lVs DSW 357706 STLCOPCB4086481 -37- XIX. Corresponding values of the askarel fluid after heating, 168 hours at 100C in absence of a test specimen are 0.075 and 0.02 respectively. The maximum dissipation factor levels suggested for the askarel after heating in presence of the test specimen are 0.20 at 100C and 60 Hz and 0.04 at 25C and 60 Hz. Refining Askarel For Re-Use A. Filtering Through Dry Blotter Paper to Remove Mois ture and Extraneous Particles: Most operators prefer portable refining apparatus, such as a plate press fitted with a dolly, favailable from Sparkler, Mundelein, 111. or General Electric Go., Pittsfield, Massf^^or the earthen *rcartridge filter type,tJ(available from Industrial Filter Corp., Lebanon, Ind. Filter paper liners for the plate press are available from Carl Schleicher and Schuell Company, Keane, New Hampshire and manu facturers of filter presses listed above. The filter paper must be dried immediately before use. For best results, spread the paper for maximum surface exposure in a hot air circulating oven and heat it for 4 to 6 hours at 110C. \ DSW 357707 STLCOPCB4086482 -38- Circulate the askarel hot (but not over 4oC) through the filter fitted with the dry paper liners. * After filtration the dielectric breakdown voltage of the askarel should be 35 KV minimum. 1. Precautions: Filtering should not be done when the relative humidity exceeds 75$. 2. Any flexible hoses and gaskets on the refining equipment should be lined with or made of mate rials that will not be softened by contact with askarel fluid. (Silicone or Viton or Teflonlined, or flexible metal materials are suitable.) Table VII GUIDE TO RATE OF DISSOLVED WATER REMOVAL BY FILTERING ASKAREL THROUGH A PAPER PRESS Passes Through Paper Press 0 1 2 3 4 5 6 Water in Askarel PPM 115 3522 18 12 10 . . 10 /> B. See Insert ,. C. If the solid insulation of the transformer requires drying, consult the transformer manufacturer or an apparatus service shop, as in such case oven drying is preferred. DSW 357708 STLCOPCB4086483 will I . Insert P. 38 B. Disposal of Solid Wastes: The ANSI Guide states that, "All solid wastes which have been saturated . with askarel should be disposed of by the following procedure: I 1. The saturated wastes should be placed into leak-proof containers ? and transported to a supervised dry landfill site meeting State * requirements. Alternatively, they can be disposed of by incinera tion in State-approved facilities. 2. Solid absorbents used for spills can l^e disposed of uncontained in ". the supervised dry landfill site; transport to*the site should be . in closed containers. Alternatively., incineration can be used in accordance with par. B (See Section 4 for facilities)." f DSW 357709 STLCOPCB4086484 -39- D. Earth Treatment for Maximum Improvement of Power Factor and Volume-Resistivity: We question whether pumping and filtering the fluid solely to achieve a change In power factor or volume resistivity alone is Justified in today's ecological climate regard - AJr ing PCBs. We recommend'fin these situations the original transformer manufacturer be contacted. 1. Procedure: ^The askarel liquid should be relatively ''dry prior to the following earth filtra tion. 3L _> Use finely divided Attapulgus clay or Fuller's earth ^dried and activated by heating for 12 hours at 300-350F Immediately prior to use|. as a coating on the filter paper surfacej^The amount of earth used should be 0.1 to 0.2 per cent by weight on the weight of the askarel to be treated, fAskarel weighs about 12.5 pounds per gallon|. To deposit the earth.evenly, stir one-third of the earth with a small portion of askarel in a clean container. Pump the mixture through the filter and follow with two more one-third por tions* Then circulate askarel taken from near the top of the transformer, pass It hot (not over 55-60C) through the earth-coated filter and feed back through the bottom transformer DSW 357710 STLCOPCB4086485 -40- outlet. Continue circulation until the fluid is clear and test shows that the electrical properties are fully restored. . 2. Effect of Earth on Removal of Scavengers Only slight and insignificant loss fpy selec tive absorptionjof tin tetraphenyl and epox ides occurs^when askarel is refined by treat ment with 0.1 to 0.2 per cent by weight of earth. To remove significant amounts of the scavengers requires repetitious treatment with much larger amounts of earth. 3. Table IX -- Approximate Relationship Showing the Insignificant Effect of Power Factor and ' Volume-Resistivity on Dielectric Breakdown Voltage of Transformer Askarelfc/ ' Power Factor (60 eye.) 100MC 25*0 Volume Resistivity x 109 ohm-cm (at 100C, 500 Volts DC, 0.1" gap) Breakdown Voltage 25C, 0.1" gap 2$ 55$ 15$ 20-25$, 40-50$ 0.05$ 0.1$ 0.7$ 2.0$ _- 1500 500 100 60-70 25 35 KV 35 35 35 35 XX. Cleaning Arced Transformers If a unit has arced so that the askarel is no longer fit for use, a thorough cleaning of the unit is necessary be fore refilling with new askarel insulation and returning it to service*. Follow this procedure: A. Drain out all dark, carbon-contaminated askarel. Arrange to have the scrap fluid incinerated under proper conditions. (See ANSI Committee C107 report.) DSW 357711 Mj.'HI /-* nr STLCOPCB4086486 -41- B. Carefully brush carbon deposits from internal - parts and insulation, using a soft bristle brush making sure that insulation is not damaged. C. Plush thoroughly using new askarel--fnot an oil, not a cleaning solvent|. D. Plush a second time with fresh askarel; drain; then fill to the proper level with new askarel. E. Energize transformer to warm the fluid for 24 to 48 hours; then circulate the askarel through a filter, returning it to the unit filtered and ready for use. This assumes that the cause of arcing has been established and corrections made. When severe arcing occurs, major repairs are usually necessary and the unit rebuilt. This procedure can be applied for flushing outfrepaired units. XXI. Sampling Askarel - Take a sample as close to the top of the liquid surface as possible. jMany large askarel transformers have a built-in sampling tube near the surface for convenient sampling^-. Then, to make sure that your SAMPLE truly represents your askarel insulation, take another sample from the bottom. If additional sampling tube connec tions are contrived on the valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; and siliconeViton or Teflon tubing for flexible types. _ DSW 357712 STLCOPCB4086487 -42- Use NEW containers for the askarel sample. A new and . .. ^ thoroughly pre-drled small-mouth quart glass bottle fitted with a Bakelite screw cap fitted with an- alumi num or tin bott-le cap liner is recommended for *quickj on^th$-site testing^ (if complete analysis is to be made, a 5-pint size sample is required). Be sure that the new bottle does not stand open to col lect dust or moisture. Rinse the sample bottle and cap lining two or three times with askarel from the transformer/^then fill it. If the sample will be tested prompt- 96 ly* a clear glass bottle can be used. If sample is to be stored indefinitely, use an amber glass bottle or wrap clear glass with aluminum foil. A. Select a dry day. Do not sample insulation on a warm, moist day when humidity exceeds 7.5& and B. Make sure that the askarel is at least as warm as the surrounding air. (Cold liquids can condense moisture from humid air.) ., C. When sampling askarel from transformers, it is best to take the sample when the unit is warm and opera- ting at average or maximum load^ Especially &s a check on moisture $a.s reflected by a dielectric breakdown voltage test|, sampling the warm askarel ihore truly represents its condition during operation. DSW 357713 -nrr1 <ip^ jhujmm f STLCOPCB4086488 -43- Experience shows that water will migrate from a transformer^ solid insulation to the askarel liquid and vice versa, depending on temperature. Therefore, when the transformer is hot, the mois ture is most likely to be found in the liquid. This accounts largely for- periodic variations in dielectric breakdown voltage. For example^ a relatively high dielectric breakdown voltage may be found during winter months and a relatively low dielectric breakdown voltage during the summer months on samples taken from the same unit. When testing has been completed, the remainder of the fluid sample should be destroyed by high tem perature incineration described in Section VII. DSW 357714 ---------------- .... i ir STLCOPCB4086489 -44- Section B ASJCAREL PILLED SWITCHES AND TERMINAL CHAMBERS I. INTRODUCTION '' . ` ' High voltage leads are usually connected to askarel or mineral oil-filled network transformers and power centers through terminal chambers and switches. In some cases terminal chambers are not used, and the high voltage leads are connected directly to the switch terminals. They may be filled with either askarel or mineral oil. Switches are usually rotary or drum type fitted with a revolving block and porcelain unit as the principal element arranged for three-phase service. ^A^^utaway view of a typical) terminal chamber-switch combinatioi \> Askarel transformers with attached switches have been in use for about 30 years. When they were first introduced, the availability of insulating and gasketing materials was rather limited and even the best materials at the time had no service history. As a result, inadequate gasketing materials such as cork, nitrile rubber, and nitrile rubberand-cork particles were used. While satisfactory for a DSW 357715 STLCOPCB4086490 -45- limited period of time, these materials cannot be depended . "^-en for the expected long life of the equipment. ' The terminal chamber is usually above or below the switch compartment and separated by a steel wall through which the bushings are inserted. When bushings are properly selected and correctly installed, there is no leakage from one com partment to the other. With poor bushing seals, and the terminal chamber above the switch, potting compounds or cable oil can seep into the askarel. When the terminal chamber is below the switch, askarel can drain into the terminal chamber. II. SOURCES OP CONTAMINATION There are three possible sources of contamination for askarel in switches and terminal chambers; they rank in this order of frequency: (l) water entering through poor gaskets; (2) decomposition products from arcing when switch is used to break magnetizing current; (3) entrance of pothead or cable compounds through leaky bushing seals. Unlike an askarel transformer where the amount of contami nant is likely to be very small (probably only trace amounts) in relation to the volume of askarel fluid -- in switches or terminal chambers with faulty seals, the amount of contami nation can be Relatively large. DSW 357716 STLCOPCB4086491 -46- Experience has shown that, based on the number of installed askarel-switch units, the percentage of failures is extre- ,, mely small. When investigated, it has been found that most failures originate in the switch chamber. Water is the chief source of contamination. However, heavy contamination of askarel with petrolatum and asphalt material, due to leakage, have caused a few failures. Petrolatum is used frequently for filling terminal chambers. When either cable oil or petrolatum seeps into askarel, no great harm results. The fire resistance will be somewhat decreased and power factor of the askarel will increase with an accompanying drop in resistivity. While highly undesir able, it is doubtful that failure of the unit results. Where asphaltic compounds are used in place of petrolatum, the danger is increased somewhat because asphaltic contamination may cause excessively high dielectric losses in the askarel. When the terminal chamber is below the switch chamber, the potting compound can be contaminated by askarel if the bush .1 ing seals are leaky. This is undesirable because the askarel will increase the power factor and conductivity of the potting compound or cable oil and develop heat from dielectric loss. If this mixture is drawn into the cable insulation, a cable failure is likely. This again emphasizes the importance of tight bushing Assemblies. 357717 STLCOPCB4086492 -47- III. SEALING SWITCHES AND TERMINAL CHAMBERS Proper bushing construction, use of Silastic seals and . welding wherever possible is highly desirable (as covered in Section A). Where an elastomeric seal is to be used in contact with both askarel and petroleum oil, DuPont's Viton is suggested. For new equipment the user should specify these modern sealing arrangements to keep out contaminants and minimize maintenance. ' IV. ASKAREL USED UNDER MILD ARCING CONDITIONS . The IEEE Guide for Transformer Askarel calls attention to the following: "Askarel is used, to some extent, in apparatus where it is subjected to light intermittent arcing, such as in self-contained induction regulators, where operating switches are con tinually producing slight arcs, in transformer deenergizing switches, etc. Under normal con ditions, deterioration of the askarel is very slight. However, improperly adjusted or defec tive switches in this type of apparatus can produce excessive and prolonged arcing and ac- cellerated deterioration of the askarel. It is recommended that when askarel is used under these conditions, checks of the liquid, espec ially for moisture and dielectric breakdown voltage made more frequently than when it is used only as a cooling and insulating fluid. Deteriora tion of this type is indicated by a blackening of the liquid. It can usually be reconditioned as previously described. Special attention should be given to maintaining the scavenger at the appropriate concentration." DSW 357718 STLCOPCB4086493 -48- V. MAINTENANCE FOR ASKAREL FILLED SWITCHES A. Switches used for grounding after power source has been' de-energized will not undergo arcing. B. Switches interrupting magnetizing current will be sub ject to arcing; the amount of decomposition will depend on power interrupted, time and frequency of operation. As a general rule, the liquid should be checked after 5 to 10 operations. . 1. On newly installed switches, check the askarel at 3, 6 and 12 month intervals; if found satisfactory, check once annually thereafter. With proper atten tion to the gasketing of covers and bushings, exper ience will probably indicate that less frequent in spection is warranted. . 2. Check askarel for: . a. Dielectric breakdown voltage (ASTM D8T7):_.It should , . voltage , ' be 26 KV minimum. If dielectric breakdown/is low, confirm presence of water by Karl Fischer method . ASTM D-1533. Filter to remove moisture. Die lectric strength should then be 30 KV minimum. b. Presence of carbon from arcing: Fluid should be relatively free of carbon. If badly arced and very black, replace fluid. If only minute amounts of carbon are present, filtration is recommended. . Check power factor of liquid (should not be over 5$ at 25C. and 60 cycles). Flush out switch chamber with several gallons of fresh askarel before refilling. dsw357719 STLCOPCB4086494 VT:j-- -- - - -49 3. If there is discoloration, high power factor, ,, detectable change in specific gravity or refrac tive index, or if fluid flashes below 250P, there is a possibility of seepage of potting com pound into the switch compartment. In this case, correct any leaky bushing seals with proper re placements and fill with new askarel. ... 4. If terminal chamber is below switch, check potting compound for presence of askarel (can usually be detected by odor or by an increase in specific gravity). If askarel Is present, correct any leaky bushing seals with proper replacements, and renew compounds. 5. Examine cover gaskets visually. Deterioration can be detected by swelling and cracking of the exposed edge. In cases of severe deterioration, liquid seepage Is usually present. 6. Check for leakage at packing gland of switching shaft. If leaking, repack with a Silastic ring type gasket. VI. ASKAREL UNDER EXCESSIVE TEMPERATURE OR FAULT CONDITIONS ! The IEEE Guide also points out that, j "Chlorobenzenes used in transformer askarels begin to boil i * : Dsw^20 ; t STLCOPCB4086495 -50at temperatures of about 205C, under atmospheric con ditions. If the material is heated to such high tem perature in a sealed system, pressure develops. Pres sure will also develop in the system if the askarel is arced sufficiently to generate copious hydrogen chloride gas "Therefore, it is recommended that wherever possible, sealed askarel filled equipment be provided with pressure relief devices. These devices must be large enough to provide immediate relief at a definite pressure, and to prevent further build up of pressure if decomposition continues. It must be remembered that the presence of devices of this sort does not necessarily preclude the rupturing of containing vessels, since pressure build up can be extremely rapid under violent arcing conditions." os*35'1*' STLCOPCB4086496 -51- SECTION C ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO - Transformer users not wishing to make their own fluid analyses can obtain the service from Monsanto. Simply contact Monsanto and specify what analyses are wanted. You will be sent the proper-sized Sample container fitted with a proper label. When you re ceive this, carefully ` take your sample (following the procedure for sampling in this guide). Send the container to Monsanto's laboratory. Charges listed include sample container, shipping, handling and laboratory costs. Types of Analyses Available Analysis 1) . ROUTINE MAINTENANCE CHECK . Total Charge: $25.00 To determine the general condition of the fluid and find whether further analysis is neces sary. (one-quart sample required) Properties Tested Color and Condition Dielectric Breakdown Voltage Moisture ' '. . You will be notified of the results of this test. If further testing is indicated, and you want a complete analysis, you will be sent a five-pint sample container. This sample will be used for the following series of tests: Analysis 2) COMPLETE ANALYSIS Total Charge: $55.00 ' (a) To determine the extent of fluid contamination, (b) earth refinement to determine what degree of restoration of electrical and insulating properties is possible, (c) check, test to see how the fluid responded to earth treatment. a) Complete Analysis: to determine the extent of contamination Properties Tested Color and Condition Specific Gravity Refractive Index Water Free Chlorides .. Acidity Dielectric Breakdown Voltage Power Factor, Dielectric Constant, and Resistivity STLCOPCB4086497 -52- b) Earth Refinement Response: Consists of treatment for 2.5 hours at 50-60C. with 0.1 to 0.2 percent by weight of properly conditioned Attapulgus clay and then filtration through dry filter paper. c) Analysis After Laboratory Earth Refinement: Properties Tested . Refractive Index Water . . Free Chlorides Acidity . Dielectric Breakdown Voltage Power Factor, Dielectric Constant, and Resistivity . . You will be notified of the results of this test series on your sample. Then aftei refining your entire transformer fluid fill you can check on the results by requesting the following analysis: ' Analysis 3) ANALYSIS AFTER EARTH REFINEMENT Total Charge:$35.00(This charge will not apply when analyses 1 and 2 have already been made.) To determine whether the entire lot of the askarel fill responded to the same extent as the laboratory sample, (five-pint sample required) Properties Tested Color and Condition Refractive Index Water Free Chlorides . Acidity ~ Dielectric Breakdown Voltage Power Factor, Dielectric Constant, and Resistivity To arrange for the tests described above write to the following address: Paul G. Benignus Monsanto Company 800 North Lindbergh Blvd. St. Louis , Missouri 63166 Samples to be tested should be clearly marked for identification and sent directly to: Monsanto Chemical Company W. G. Krummrich Laboratory. . Sauget, Illinois 62201 Attention: R. Kuster OS'* 351113 22 STLCOPCB4086498 -53- APPENDICES '' . ^ APPENDIX A -- Askarel Stability and Composition of Arc Formed Gas: Askarel insulation is one of the most inert, chemicaliy-stable heat resistant, non-corrosive liquids known. It will not break down, oxidize or sludge when exposed to air and high tempera tures, 150C. or even somewhat higher. Arcing, however, will break down the compound to liberate some hydrogen chloride and small amounts of carbon. APPROXIMATE COMPOSITION ARC FORMED GAS FROM TRANSFORMER ASKAREL BLENDS A STM TYPES D AND F . (INERTEEN 54201KA AND PYRANOL A13B3B-2, RESPECTIVELY) Gas Amount carbon monoxide.......... ............... ............................ 0.3 per cent carbon dioxide............................................................ 0.3 oxygen................................. 0.6 inert gases................................. 1.5 . hydrogen chloride.......... .............................97.3 (note the absence of phosgene) This arc-formed gas from ASTM Type D and Type F transformer askarels is non-flammable and non-combustible. For all practical purposes, the amount of gas liberated from askarel under a given set of arcing conditions is about 100 cubic centimeters per kilowatt-second. DSW 357724 STLCOPCB4086499 -54- APPENDIX B SOLUBILITY OP GAS IN TRANSFORMER ASKARELS . A STM TYPES D AND P Percent of Gas By Volume Corrected to: Carbon dioxide Air Nitrogen Hydrogen chloride1 ~ 25 C 780 mm -------- ioctu *n^ 5.7 6.0 37.8 4.9 4.8 50.9 0C. 760 mm 25^0 100 C -- 5.8 5.0 5.5 4.4 ' *' 1) In absence of scavenger APPENDIX C EFFECT OF TEMPERATURE ON DIELECTRIC BREAKDOWN VOLTAGE OF ASKAREL Temperature C -60 -40 -20 0 20 40 60 80 Dielectric Breakdown Voltage ASTM D877 67 KV 63 57 55 50 50 48 45 ' DSW 357725 STLCOPCB4086500 -55- appendix D Temp.C -20 0 20 40 60 80 100 COMPARISON OP THE APPROXIMATE VISCOSITY IN SAYBOLT UNIVERSAL SECONDS OF TRANSFORMER ASKARELS AND MINERAL OIL . Pyranol A13B3B-2 1,000 100 70 45 39 34 30 ' 10-C Mineral Oil 1,000 150 85 49 4o 34 30 Inerteen 54201 KA 2,tt00 195 85 5 40 36 33 APPENDIX E THE DENSITY OF INERTEEN 54201 KA 7336-9 AND TRANSFORMER PYRANOL A13B3B-2 Approx. Density gm/cc. . Temp. 0 20 40 60 80 C ` Inerteen 54201 KA 1.574 . 1.552 1.529 1.507 1.485 Pyranol A13B3B-2 . 1.577 1.555 1.532 1.510 1.488 APPENDIX p ' The thermal conductivity values of transformer Pyranol A13B3B-2 at 27C and 58C are 26.2 and 25.8 x 10~5 calories centimeters-1, degrees centigrade-1, second-1, respectively. Or, approximately 0.06 BTU per (hr.)(sq.ft.)(P.) per foot. This same approxima tion applies to Inerteen PPO.(7338-9). . APPENDIX G ' Heat Capacity . Over the temperature range of 25 to 125C the specific heat of transformer askarel is close to 0.30 calories per gram per degree. . APPENDIX"H . ; Coefficient of Expansion The average coefficient of expansion "of transformer askarel over the temperature range 20 to 100C is 0.0007 cc/cc/C. One gal lon would increase to 1;056 gallons on heating from 20 to 100 C. DSW 357726 STLCOPCB4086501 -56- APPENDIXUI ' Fire Resistance * Askarels of various compositional types are used. Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride can yield varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and cellulosic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitro gen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus. APPENDIX J . Seals, Properties and Procurement Dow Corning Corporation, Midland, Michigan with Districts at Atlanta, Boston, Chicago, Cleveland, Dallas, Los Angeles, New York City, Washington, D.C. and Toronto has available Bulletin 09-019, August 1962 entitled "Silastic Design Data". This lists the gasket fabricators throughout the country from whom the ' "Silastic 50" gasketing can be purchased in sheet, extrusions or molded shapes. Generally Silastic 50 sheet goods are stocked by local die cutters, hence, c.ould be generally purchased locally. Usually small quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other elastomers. . oSV\J 357727 STLCOPCB4086502 -57- Where the gasket is extruded for fitting into a machined groove or between gasket stops, Dow-Corning advises use of * :a scarved Joint. This Joint is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) mate rials, which air cure. . Dow Corning points out that the local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll mill in preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 50 for 24 hours at 48oF. SPECIFICATIONS* ` ASTM D676----ASTM D4l2 ASTM D4l2 ASTM D395 Color............................................................. White Specific Gravity at 77F................ 1.20 - 0.02 Hardness, Shore A. Scale............... 45 to 60 Tensile Strength, psi, min.....800 Elongation, percent, min................ 250 Compression Set after 22 hrs... at 300F, percent, max................. 30 *A11 physical properties measured on 0.075 inch thick samples molded 5 minutes at 24oF, and oven cured 24 hours at 480F. DSW 357728 STLCOPCB4086503 -58- appendix K Caution Label . ^ The following or equivalent caution statements should be fixed on all containers of transformer askarels and the transformers themselves: This product contains Polychlorinated Biphenyls (PCBs). Care should be taken to prevent entry into the environment through spills, leakage, use, vaporization, or disposal of liquid or containers. Avoid prolonged breathing of vapors or mists. Avoid contact with eyes or prolonged contact with skin. If skin con tact occurs, remove by washing.with soap and water. Following eye contact, flush with water. In case of spillage onto cloth ing, the clothing should be removed as soon as practical, skin washed, and clothing laundered. DSW 357729 STLCOPCB4086504 - CHEMICALS COMPANY . MONSANTO INDUSTRIAL/ 800 N. LINDBERGH BLVD. `,fEClALT't QZOcP ST. LOUIS, MISSOURI 63166 The information herein regarding obtaining optimum results from askarel fluids in your transformer has been accumulated by Monsanto for over 30 years from the experience of makers and users of askarel transformers and it is believed will be helpful. Nothing herein shall be construed as applying to other than askarel insulation. Data and maintenance suggestions herein do not apply to the other components of the transformer. All operating and maintenance suggestions recommended by the manufacturer of the transformer should also be carefully followed. Because these maintenance directions, apply only to the askarel insulation, Monsanto disclaims any liability for damage to property or injury to persons arising from transformer operation. DSW 357730 ' lltho In U.S. A. STLCOPCB4086505 SECTION A TRANSFORMER ASKAREL I. INTRODUCTION: This manual describes the operating characteristics of transformer askarel liquid insulation and how it differs from mineral oil. The information given is based on facts gathered by Monsanto over 30 years as producer of askarel, plus knowledge gained from the experience of transformer manufacturers and users. This guide is provided to outline the very simple mainte nance required for askarel fluid in "modern" transformers and to offer suggestions for the sealing and maintaining of askarel in old units. By following this guide, users will obtain maximum service from askarel insulation with a reasonable minimum of maintenance. If questions arise relating to the designing and building of transformers -- these should be referred to regular transformer suppliers. Monsanto gratefully acknowledges the assistance, guidance, and the contributions of certain data by the following: Frank M. Clark......................................................... .GeneralElectric Edward L. Raab............................................................. GeneralElectric James G. Ford...................................................... WestinghouseElectric George Shombert, Jr......................................... Allis Chalmers II. HISTORY OF TRADE NAME TYPES "Askarel" is the generic name for non-combustible (fire-resistant) liquid insulation. In this respect, the insulation is completely different from ordinary transformer mineral oils. Transformer askarel is marketed by Monsanto. Whatever the trade marked brand, the askarel contains Monsanto's Aroclor (chlorobiphenyl). . . one of the best liquid insulations developed by science. This inert compound is chemically stable, fire-resistant, heat stable, non-corrosive, and has high dielectric strength under the operating conditions encountered in transformers. DS\(V 357731 1 STLCOPCB4086506 Askarel liquid insulation is made by thinning Aroclor 1260 with trichlorobenzene or tri-, tetrachlorobeiizene mix. The first transformer askarel was made in 1932, in accordance with General Electric Company's patents, and was trademarked Pyranol ,, 1488. Westinghouse, too, offered this askarel insulation in 1936 under their trademark Inerteen. In the mid-1940's, as shown in the following table, tin tetraphenyl was added to General Electric's Pyranol to scavenge hydrogen chloride. Shortly thereafter, Westinghouse added phenoxy propene oxide to Inerteen for the same purpose. In 1963, General Electric replaced tin tetraphenyl with a diepoxide scavenger. This new formula, which replaces previous Pyranols, is called Transformer Pyranol A13B3B. Thus, today the two commercial types offormulations are General Electric's Transformer Pyranol A13B3B type and Westinghouse Inerteen PPO (7336-9) type. The composition changes made in transformer askarel formulations are shown in Table I. Table I THE COMPOSITION OF TRANSFORMER ASKARELS Inerteen Pyranol__________________________________ 1488 1467 1470 A13B3B Inerteen (7336-9) Year Introduced.......................... 1932 1944 1952 1963 1936 1945 Ingredients: Aroclor 1260 ................................. 60 60 45 45 60 60 Trichlorobenzene.......................... 40 40 40 40 40 40 Tetrachlorobenzene................. 15 15 Tin tetraphenyl........................ 0.125 0.125 Phenoxy propene oxide.......... 0.20 Diepoxide.................................. 0.125 PPO OTHER BRAND NAMES Various electrical equipment manufacturers use other trade-marked names for askarel liquid insulation, such as Chlorextol (Allis-Chalmers); Noflamol (Wagner Electric); Saf-T-Kuhl (Kuhlman Electric). These askarel insulating liquids are one or the other of the two standard formulations. Still other manufacturers, who designate their insulation only by its generic name, askarel, assign it a number or code. By this number, Monsanto knows whether to furnish Pyranol A13B3B or Inerteen PPO (7336-9) type formulation to the user.III. III. OFFICIAL TRANSFORMER ASKAREL SHIPPING SPECIFICATIONS The official shipping specifications for the two modern transformer askarel formulations are shown in Table II. DSW 357732 2 STLCOPCB4086507 '; iYTiTSt TiTritvVlMi DSW 357733 3 STLCOPCB4086508 IV. INTERCHANGEABILITY AND STABILITY A. Interchangeability: The two general types of askarel insulation shown in Table II can be either mixed or interchanged and there will be no difference in the operation of the transformer. However, askarel insulation must never be mixed with mineral oil. Over 2% mineral oil in askarel begins to lower its fire resistance. Further, materials of construction in the transformer that are compatible with askarel may not be compatible with oil and vice-versa. For example: a significant amount of askarel in a transformer built for mineral oil will attack gaskets, adhesives, core bindings, impregnating varnishes, etc. B. Stability: Askarel liquid insulation is highly pure, fire-proof liquid made under close chemical control. It does not vary in composition like the commercial range of mineral oils. Askarel does not deteriorate when exposed to air, heat, hot metal; it does not break down over long use to form conducting or corrosive chemicals; it does not oxidize or sludge. Askarel will remain perfectly stable year after year unless broken down by exposure to severe arcing. The only real "enemy" of askarel is contamination by water. Keeping askarel water-free will insure long-time service. Askarel is heavier than water. If water gets into askarel insulation, only a tiny amount (125 ppm) dissolves -- the rest floats on top.V. V. DIRECTIONS FOR HANDLING A. Keep Dry: In handling, storing, sampling, inspecting askarel -- and in operating askarel transformers -- take every precaution to guard the askarel insulation from exposure to high humidity and moisture contamination. Keep 5, 30, or 55 gallon drums of askarel dry; lay stored drums on their sides with the bung at the highest point from floor to keep water off the drum head (which can be sucked into the askarel by the drum "breathing"). This precaution is not necessary when drums are stored indoors, which is the preferred way of storing. B. Use Ordinary Personal Precautions: Transformer askarel has been made, handled, and used for over 30 years without causing toxic or other ill effects. It can be handled with only minor precautions. If accidentally spilled on hands, no serious skin irritation will occur. However, liquid askarel has a solvent action (similar to paint thinner) on the fats and oils of the skin and prolonged contact may lead to drying and chapping of the skin. 0S\N 357734 STLCOPCB4086509 In case of contact, wash off the skin with soap and water; remove and dry clean saturated clothing. Clean up spills with rags, sawdust or absorbent clay. Eye contact may result in painful irritation but no permanent damage to tissues. If askarel gets in the eyes, flush with large amounts of water. As with all eye first-aid, refer to a physician. To relieve irritation, physicians have used a 1% Pontocaine as well as opthalmic cortisone acetate solution, or castor oil. Infrequent exposure to askarel vapors will not cause ill effects. However, prolonged exposure to high vapor concentrations should be avoided. If hot askarel must be handled in a closed or confined area, provide the area with ordinary exhaust ventilation -- or -- wear an organic cartridge respirator approved by the U. S. Bureau of Mines. VL EXPECTED SERVICE LIFE Properly designed and installed askarel transformers will give trouble-free service for a minimum of 30 years. Since their introduction in 1932, the manufacturers report finding the over-all failure rate to be less than 0.5% for all units under test and service conditions. The Edison Electric Institute's report (1956-1958) on their member utilities publishes the failure rate for askarel transformers as 0.13 per hundred banks per year. Even the rare reports of failure are invariably found to be due to improper sealing that allows moisture to enter. VH. DIELECTRIC STRENGTH -- MOISTURE RELATIONSHIP . The dielectric strength of askarel is highly sensitive to excess moisture; not sensitive to ordinary dissolved contaminants. While the dielectric strength can also be lowered by severe arcing, askarel turns noticeably black or has particles of sooty carbon floating in it if arcing has occurred. Then the transformer should be repaired and the askarel replaced. New askarel has a minimum dielectric strength of 35 KV at 25; a maximum mois ture content of 30 ppm. If the dielectric strength is checked periodically and decreases significantly -- this indicates moisture pick-up, arcing, or both. When the dielectric strength has dropped to 26 KV or less, an analysis for water is necessary. If water is found in excess of 100 ppm at 25 C., its source should be located and corrections made. When the moisture content approaches 125 ppm (saturation level), the dielectric strength of askarel drops below the value required for efficient insulating. The moisture content should not be allowed to rise over 70 ppm; it should be held as near as possible to 30 ppm. Maintaining a low moisture level will assure high dielectric strength and top operating efficiency. Table III shows the relationship of dielectric strength vs. moisture and Table IV indicates the approximate water solubility limits in askarel and mineral oil. DSV\f 357735 5 STLCOPCB4086510 Table III RELATION OF "BREAKDOWN STRENGTH" TO AMOUNT OF DISSOLVED WATER IN ASKAREL AND MINERAL OIL Breakdown Voltage (ASTM) Water Content (PPM) Askarel Mineral Oil 0 70 KV 50 KV 20 55 39 40 47 30 60 40 26 80 38 22 110 10 5 Table IV APPROXIMATE SOLUBILITY OF WATER IN TRANSFORMER ASKAREL AND MINERAL OIL Temperature Amount of Water (PPM) Dissolved C. F. Askarel Mineral Oil --30 --20 --10 0 10 20 30 40 --22 --4 14 32 50 68 86 104 8 16 28 41 65 94 128 170 8 10 13 20 33 58 85 130 i | ! TURBIDITY ... may be the visual sign of undissolved water, or may indicate contamination from core materials, dirt, or deteriorating construction materials. Cloudiness may also result from cold precipitation of tin tetraphenyl "scavenger" that was used in the earlier Pyranols. This scavenger begins to come out of solution around 15F. above zero. To redissolve it requires heating to 150 - 200F. and agitation. High dielectric strength will quickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askarel is still excellent. However, if the dielectric strength is below 26 KV, moisture should be determined, using the Karl Fischer method (ASTM D1533-60). The dielectric strength test for askarel serves primarily as an indicator for moisture. It is by far the most important maintenance test for transformer askarel. VIII. TYPICAL VALUES FOUND IN ASKAREL FLUID UNDER VARIOUS USE CONDITIONS Table V gives the entire spectrum of properties that are typical for freshly-made transformer askarel as it goes through the various normal and abnormal conditions of use. The data in Table V are in terms of only the askarel fluid and do not refer to insulation resistance or power factor measurements on the over-all transformer insulation. Several utilities studying the power factor values of the over-all transformer insulation system indicate that the unit power factor of a new askarel transformer should range from 1% to not over 5%. This would generally-correspond with the askarel fluid properties as given under heading "B". DSW 357736 6 STLCOPCB4086511 Tabl 15-400 x 1 ohm -cm . W S fc o tn Zo HM Q Zo V Vi D Oi--i Pi C W Q Z 3 > D fe W ft! < * a> < Q Z oP b Vi W rt E u a o .e _ I S-g^.1 -3 t3 ~> uh tus-*a3 gH S .* " o "3 K S c ' E ca l OQ M W <3 c = 3 Etc ca 3 u oo EU o CO co >3 ca -- c Z3 & o 2 -- 'u w *>> u O> . T8> t: *dy u in cad >> . eo &co pa> S0. c3>> o1, !f-l T^ faf) P Ca A TZ C .5 3 w |o^o o *J 4> >oE E Ch 3 tf) E Qu o C S'2 - e c c"S .o3 s <*->0 cd sn o <n 1-1 > I OO Ot_ ;>> *C aa, a c /3 ca . S c ^ 33 33 4> .O -. . chd # 's ow M >_ 33 W -H Jo ,, <k* (DO V t. ^ ao rO I v- o es^ 2 * C /> J2Q'S So3 >o > Cd y i* 2o 1cd u a .g 2 S-d 5 Ua 2 & 3 /> .s xj > cd > o o gs c o c Z o -> 60 .^g *3 4> cd cd A a-- u3 o b C *eS6S0. <C5Vub < oo **- 3 3 . ac r5fSS g SS'O o--t'-X<0 o> tn E o u ,<H*<-u o/i Co cad> 'Zi-3h da C/3 4> cd .s? O "1 c sg -u I a a o x: w 2* E* aalL."40> 2 oo ,> X* tvi ocn :*3d > o > mi o Lh o u ^ 4*-) > oV rt cd c^ cd u I/I cd i*s-* ^ rv XJ > -*- A 60 uT 13 cd *P O M 2o tn *n i y~i cd Ua <-H *C *n P3 u cd '** cd a 2E > o a JC 60 J} 8 a Ucfc o m E I/I O K. ro o 31 P o5 * cd o x 00 ^ O cd O X vo E cd ^ O n V oE So e> O o E cd o a o | b E= x !e 3 0 E -S 2 S8 E2 6^ in <s 8^ *h cd N -i <N O Si 65 o O 4P* . o " o 6s? nO .rQt ^<o |S . t-< fa 2c c 22 22 !s ^ 22 New askare Light straw Clear, free from particl 30 ppm 35 K V m inim u 100 x 109 oh m in im u m usually 5002-5% 0.05-0.1% < u -n Cl, >h H . 'o On oo JC U c .2 Ou a J2 O u u o*<nN B 33 cd O us JMC 60 ca 2 Cd 60 O~ *C o ur .2V$ o{rj> I CM u p >>t2 3mC^ .1io/2>i >oP__ ehMrf ^o Eid ^r acd Uw XI!s2 ou >V >1 (J u o oo VO so cd Uh U u Iom CS o a DSW 357737 7 STLCOPCB4086512 Starting ideally with situation "B", it is normal to expect the powerfactor of the fluid in a satisfactorily operating askarel transformer to increase as shown under heading "C'\ The "over-all" power factor of the transformer in normal service is expected to rise, but preferably not much beyond 5%. In this normal situation, the moisture level of the askarel fluid and its dielectric strength will be satisfactory, as shown in heading "C". Occasionally the power factor of a non-arced, satisfactorily-operating askarel transformer is found to be relatively high, i.e., 15%. In this case, the power factor of the askarelfluid will also be high, perhaps as high as 50% at 20C. and 60 cycles. It is not good practice merely to note that high power factor of the askarel fluid is to be expected. The important step is to check dielectric strength and note whether there has been a downward trend. A downward trend in dielectric strength very likely indicates moisture entrance and should be confirmed by a Karl Fischer test for water. The importance of any abnormalities in dielectric strength and moisture content of the askarel fluid cannot be overemphasized! Where abnormal values for the dielectrie strength or moisture content occur, the power factor of the transformer can be expected to be abnormally high; the expected high power factor of the askarel fluid will induce this. The indication that a high power factor on the transformer and on the fluid is due to contamination can be verified by ea'rth refining the askarel fluid and noting whether after refining the test results correspond with heading Assuming no mechanical defect or arcing, if the power factor of a new askarel transformer is relatively high, the power factor of the fluid will also be high, giving the situation under heading This reflects contamination that should have been removed by the manufacturer of the transformer. In absence of mechanical defect, where there are no abnormal losses in dielectric strength, and no moisture pick-up in non-arced askarel --the use history shows that a relatively high power factor for the askarel fluid (as compared with mineral oil) is to be expected. Normally, high power factor is due to contamination and not deterioration of the askarel operation. As shown by F. M. Clark in his book, "Insulating Materials For Design and Engineering Practice," John Wiley & Sons, N. Y., 1962 -- activated alumina can be used in the circulating system to bring the power factor down and keep it as low as possible. osnN 8 STLCOPCB4086513 IX. CHECK POINTS FOR MAINTAINING ASKAREL INSULATION A. General Considerations: Modern askarel transformers with welded construction or silicone gaskets for hand hole-cover, switch and terminal compartment covers, with properly constructed bushings require little or no maintenance. With properly con structed transformers, annual or semi-annual visual inspection and dielectric strength test of the askarel fluid should suffice for routine maintenance checking over many years of service. However, many askarel units were installed in the early 1930's -- before the development of some of the better modern gasketing materials and before improved designs were developed for sealing out moisture. Such early units should be, and can be, modernized. Leaky or deteriorated gaskets should be replaced. If the askarel has become contaminated, it should be reconditioned. At the same time, a general clean-up of the unit and possible refinishing may be desirable. If it is not convenient to take an old transformer out of service for general repairs, leaky gaskets can be sealed temporarily by painting over the leaky area with epoxy cement. A survey of users indicates a good number of early-built askarel transformers (over 20 years old) are kept in continuous service in critical installations by the following steps (instead of modernization). The operating units are equipped with compound pressure gauges for reading pressure above and below atmospheric. Positive pressure is maintained on the shell by introducing nitrogen at 2 to 3 pounds above atomspheric. Regular workmen in the area daily record the temperature and pressure. If a sudend pressure drop is noted more nitrogen is introduced and the gaskets are checked for leaks with soap solution. Leaks are sealed by applying epoxy cement. B. Modern Sealing Procedures: Transformer purchasers should specify the following modern techniques for sealing: 1. Welding Construction: Covers, radiator connections, switch and terminal housings, instrument connections, etc. should be welded. 2. Bushing Connections: The most satisfactory bushings are the type with rolled-on flanges and two ring seals rolled into a depression in the porcelain -- sealed with silicone rubber rings held under compression. Metal-to-glass or metal-to-porcelain sealed bushings are also satisfactory. If for any reason the above type bushings cannot be used then use a por celain or glass bushing with a silicone or Viton gasket retained in a groove. The gasket can be either rectangular or circular cross section, usually *4 inch thick. 3. Small Size Connections: When not possible to weld, small size connection seals should be made with Flexitallic stainless steel rings. The surfaces must be machined and parallel. The filler between the steel laminations of the Flexitallic ring should be either silicone or Viton. DSW 357739 9 STLCOPCB4086514 4. Gaskets For Hand-Hole Covers: Modern design specifies silicone gaskets. Such gaskets must be retained in a groove. The groove preferably is machined into the flange or cover. However, it can also be formed by welding conccntric-steelstnips to the flange or the cover. Generally the gaskets should be ^/16 to Vi inch thick for covers, depending on the depth of the groove. A rectangular section is usually used. The silicone material should be Dow-Coming No. 50 Silastic or equivalent. This is a low compression set material. For best sealing 20 to 25% compres sion is recommended, with ample clearance in the groove to allow for this compression. No cement is required. With reasonable care the gasket is removable without damage and is reusable. Silastic 50 is slightly swelled by askarel which contributes to the tightness of the seal. It is not deteriorated by askarel fluid or vapors. It resists weather ing and it is thermally stable and flexible at all operating temperatures. It is an excellent moisture barrier. Notes: a. Dow-Corning, Midland, Michigan will supply a list of Silastic 50 gasket fabricators to all transformer manufacturers or users. They will also furnish technical data. b. Any user of Pyranol transformers, made by General Electric Company at Rome, Ga., will receive prompt and generous help for converting to the modern silicone or Viton gaskets by contacting the General Electric Company's Service Engineering Department at Rome,#Ga. See Appendix K: Seals, Properties and Procurements. C. The Older Sealing Arrangements: The older type gaskets consist of either cork or cork-nitrile rubber combinations or straight nitrile rubber. 1. Cork-Nitrile Combinations: Covers for the main tank, hand-holes, switch and terminal chambers, relief diaphrams etc. are held in place by studs welded to the flange or by bolts. The gaskets are cut with openings and placed over the bolts. Often Shellac (Westinghouse Style No. 1150419, or General Electric Company's Glyptal 1276) is used to cement the cork to the flanges. The following is recommended for sealing with the cork -- nitrile rubber combination: Use Armstrong NC-757 cork-nitrile material or equivalent. The gasket can be cut from a single sheet or by scarfing strips of the material. A convenient method for joining strips is to make a Keystone Type joint. For this, Westinghouse, Sharon, Pa., offers their gasket cutter Style No. 328 B614 G01, (about $15). The joints should be cemented and the gasket also cemented to the flange, using one of the above cements. Excess cement should not be allowed to reach the interior of the transformer. to DSW 357740 ! j i STLCOPCB4086515 After installation and bolting, the outside edge of the gasket should be coated thoroughly with epoxy cement to increase weather resistance. This epoxy cement is. a paste to which a curing catalyst is added immediately before use. Typical are: a. Epoxy Patch Kit ffl-C Hysol Corporation, Olean, N. Y. b. Scotchcast Resin ff4 Minnesota Mining and Manufacturing Co. St. Paul, Minnesota c. Adhesive A-l and Activator Type B Armstrong Products Company Argonne Rd., Warsaw, Ind. d. Adhesive 9860-1, Synthetics Organic Company, Cleveland, Ohio, used with activator diethylene triamine (Carbide and Carbon Chem. Co.) 2. Straight Nitrile Rubber: When straight nitrile rubber was originally used, invariably the gasket was recessed in a groove. This was to prevent gasket flow and to protect the material against excessive compression. Although this type seal was not cemented, the nitrile rubber gasket is not reuseable. Since grooves or stops have already been provided for the nitrile rubber seal, Silastic 50 can be easily substituted and is recommended. This conforms with modern practice. X. PERIODIC FLUID INSPECTION AND WHAT CHECKPOINTS MEAN On a regular schedule -- at six, nine, or twelve month intervals -- make a simple visual inspection of your askarel insulation and run a dielectric strength check. A. Visual Inspection: Askarel is a clear, faint-yellow liquid. After long-term use this color may gradually intensify to light brown. The fluid should remain clear and free from turbidity or cloudiness. Any color change -- such as to a green, red or blue cast -- indicates extraction of impurities from the solid insulation. If a distinct foreign color pick-up is noted, check the complete range of electrical characteristics and notify the transformer maker. The electrical characteristics may be found to be unim paired. Color change alone (except for black) is not a danger signal since the contamination is not likely to impair the dielectric strength. B. Dielectric Strength: If the dielectric strength has decreased significantly from the last inspection, or if it has gradually decreased below 26 KV range (at 25C.) -- RUN A CHECK FOR MOISTURE. Use ASTM D901, D877 (Karl Fischer Method). The dielectric strength of askarel is the major indicator to the operating efficiency of your liquid insulation and of the askarel transformer itself. Besides the "visual" inspection tests, dielectric strength is the only test necessary to run on a routine basis. Well-sealed askarel transformers have service records of 25 to 30 years on the original askarel. New askarel has a minimum dielectric strength of 35 KV at 35C., a maximum moisture content of 30 ppm. DSW 357741 11 STLCOPCB4086516 XI. INSPECTION CHECK LIST 1. If askarel is clear, even though darkened to light brown; has no sediment or turbidity; has dielectric strength over 26 KV. . . give it the inspection "OK". 2. If askarel is clear;'has foreign color of blue, green, red ... it is "extracting color" from internal materials. This is not, of itself, an operating hazard when the dielectric strength stays over 26 KV and moisture remains low. However, this rare occur rence calls for checking into condition of the interior construction and consulting the transformer maker. 3. If askarel is clear; but dielectric strength drops to 22 or lower KV, and moisture rises over 80 ppm ... the askarel is ready for simple "refining". If the moisture is near the saturation level (about 125 ppm), a thorough inspection should be made for water droplets in the transformer tank, and even for "globules" or water floating on the askarel surface. If found, the transformer manufacturer should be consulted for reconditioning both the transformer and the fluid. 4. If askarel is dark brown to black; if black particles of carbon are seen; and dielectric strength is low... the askarel has been broken down by arcing. It cannot be refined and should be discarded. If any of these four simple inspection tests appear out of the ordinary, or the relationship between appearance and test values is abnormal -- contact your transformer supplier for a complete analysis. Whenever a sample is to be shipped to Monsanto, please follow the directions shown under: "SAMPLING ASKAREL". ' XII. CONTAMINATION IN TRANSFORMERS Unlike mineral oil which can oxidize, sludge and deteriorate -- askarel breaks down in transformer use only when strongly arced. Thus, while askarel does not decompose in normal use -- it can be contaminated more readily than the relatively non-polar mineral oil. For example the following Table VI shows how a small amount of synthetic rubber or a bit of varnished cloth markedly increases the power factor of the askarel. Please note, however, that such minor contamination has no adverse effect on the dielectric strength. As explained, moisture entrance through faulty seals seems the only contaminant in normal use that lowers the dielectric strength of transformer askarel. i DSW 357742 12 STLCOPCB4086517 Table VI EFFECT OF COMMON INSULATION MATERIALS ON POWER FACTOR AND DIELECTRIC STRENGTH (HEAT AGED 96 HOURS IN ASKAREL AT 100C.) Material Immersed None (control)............................................. .... Black varnished cloth.................................. ... Copper........................................................... .... Pressboard.................. ...................................... Manila paper........................................... ........ Phenol formaldehyde resins..................... ... Shellac................................................................ Iron..................................................................... Synthetic rubber............................................... Askarel After Exposure Power Factor, Percent at 60 eye., 100C. Dielectric Strength 25C. 1.0 85.0 1.5 2.0 1.5 1.6 6.0 5.0 70.0 35 KV 42 40 37 39 41 36 39 39 Similarly, trace contaminants from commonly used construction materials can lower the volume - resistivity of askarel, without affecting its dielectric strength. Table VII shows this. Table VII EFFECT OF COMMON INSULATION MATERIALS ON VOLUME RESISTIVITY OF ASKAREL Sample 1. New askarel before heat aging........................................... 2. New askarel after heat aging 96 hours at 100C........... 3. After heat aging with 1 sq. inch specimens of: a. Phenolic resin tap changer material............................ b. Paper................................................................................. c. Grade A press board (tan)............................................. d. Grade A press board (gray).......................................... e. Grade A press board, laminated strip........................ f. Cotton wrapping............................................................ g. Glyptal 1276 cement, cured 48 hrs. at 110C............. Volume Resistivity x 109 ohm-cm (at 100C., 500 Volts DC., 0.1' gap) 2,000 1,900 1,200 750 500 500 400 300 100 While trace contamination easily lowers volume resistivity from high levels, it is important as previously noted in Table V Case F, that heavy contamination (as when arced) does not lower the resistivity below the order of 109 ohm-cm. at 100C. The different behavior of askarel vs. mineral oil in these respects can be summarized as follows: High power factor and low volume resistivity in transformer mineral oils are commonly regarded as "danger signals" that the oil has deteriorated and broken down chemically. This is NOT TRUE of askarel liquid insulation, unless the dielectric strength is low. OSIN 35TT 13 STLCOPCB4086518 B. Earth Treatment for Maximum Improvement of Power Factor and VolumeResistivity: 1. Procedure: (The askarel liquid should be relatively dry prior to the following earth filtration.) Use finely divided Attapulgus clay or Fuller's earth (dried and activated by heating for 12 hours at 300-350F. immediately prior to use) as a coating on the filter paper surface. The amount of earth used should be 0.1 to 0.2 per cent by weight on the weight of the askarel to be treated. (Askarel weighs about 13 pounds per gallon). To deposit the earth evenly, stir one-third of the earth with a small portion of askarel in a clean container. Pump the mixture through the filter and follow with two more one-third portions. Then circulate askarel taken from near the top of the transformer, pass it hot (not over 55-60C.) through the earth coated filter and feed back through the bottom transformer outlet. Continue circulation until the fluid is clear and test shows that the electrical properties are fully restored. 2. Effect of Earth on Removal of Scavenger^. t Only slight and insignificant loss (by selective absorption) of tintetraphenyl and epoxides occurs when askarel is refined by treatment with 0.1 to 0.2 per cent by weight of earth. To remove significant amounts of the scavengers requires repetitious treatment with much larger amounts of earth. 3. Table IX -- Approximate Relationship Between Power Factor, Volume Resistivity and Dielectric Strength of Transformer Askarel: Power Factor (60 eye.) 100C. 25C. 2% 5% 15% 20-25% 40-50% 0.05% 0.1% 0.7% 2.0% -- Volume Resistivity x 109 ohm-cm. (at 100C., 500 Volts DC., 0.1' gap) 1500 500 100 60-70 25 Dielectric Strength 25C., 0.1' gap 35 KV 35 35 35 35 If it is desired (although these factors are not generally considered important for askarel transformers), to keep the power factor as low as possible and the resistivity as high as possible, hang a container of anhydrous alumina or activated clay in the circulating system of the transformer. XIV. CLEANING ARCED TRANSFORMERS If a unit has arced so that the askarel is no longer fit for use, a thorough cleaning of the unit is necessary before refilling with new askarel insulation and returning it to service*. Follow this procedure: DSW 357744 IS STLCOPCB4086519 A. Drain out all dark, carbon-contaminated askarel. (Discard by dumping or burying where it will not contaminate a water supply.) B. Carefully brush carbon deposits from internal parts and insulation, using a soft bristle brusn ma'king sure that insulation is not damaged. C. Flush thoroughly using new askarel (not an oil, not a cleaning solvent). D. Flush a second time with fresh askarel; drain; then fill to the proper level with new askarel. E. Energize transformer to warm the fluid for 24 to 48 hours; then circulate the askarel through a filter, returning it to the unit filtered and ready for use. * This assumes that the cause of arcing has been established and corrections made. When severe arcing occurs, major repairs are usually necessary and the unit rebuilt. This procedure can be applied for flushing out repaired units. QStN 357745 16 STLCOPCB4086520 XV. SAMPLING ASKAREL Take a sample as close to the top of the liquid surface as possible. (Many large askarel transformers have a built-in sampling tube near the surface for convenient sampling). Then, to make sure that your SAMPLE truly represents your askarel insulation, take another sample from the bottom. If additional sampling tube connections are contrived on the valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; and silicone or Teflon tubing for flexible types. Use NEW containers for the askarel sample. A new and thoroughly pre-dried smallmouth quart glass bottle fitted with a Bakelite screw cap fitted with an aluminum or tin bottle cap liner is recommended for "quick on-the-site testing." (If complete analysis is to be made, a 5-pint size sample is required). Be sure that the new bottle does not stand open to collect dust or moisture. Rinse the sample bottle and cap lining two or three times with askarel from the transformer; then fill it. If the sample will be tested promptly, a clear glass bottle can be used. If sample is to be stored indefinitely, use an amber glass bottle or wrap clear glass with aluminum foil. A. Select a dry day. Do not sample insulation on a warm, moist day when humidity exceeds 75%, and ... B. Make sure that the askarel is at least as warm as the surrounding air. (Cold liquids can condense moisture from humid air.) C. When sampling askarel from transformers, it is best to take the sample when the unit is warm and operating at average or maximum load. Especially as a check on moisture (as reflected by a dielectric strength test), sampling the warm askarel more truly represents its condition during operation. Experience shows that water will migrate from a transformer's solid insulation to the askarel liquid and vice versa, depending on temperature. Therefore, when the transformer is hot, the moisture is most likely to be found in the liquid. This accounts largely for periodic variations in dielectric strength. For example: a relatively high dielectric strength may be found during winter months and a relatively low dielectric strength during the summer months on samples taken from the same unit. i I j t i i | I j l i OSIN l 17 STLCOPCB4086521 SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS I. INTRODUCTION: High voltage leads are usually connected to askarel or mineral oil-filled network transformers and power centers through terminal chambers and switches. In some cases terminal chambers are not used, and the high voltage leads are connected directly to the switch terminals. They may be filled with either askarel or mineral oil. Switches are usually rotary or drum type fitted with a revolving block and porcelain unit as the principal element arranged for three-phase service. (A cutaway view of a typical terminal chamber-switch combination is shown for reference.) il + &&.! Askarel transformers with attached switches have been in use for about 30 years. When they were first introduced, the availability of insulating and gasketing materials was rather limited and even the best materials at the time had no service history. As a result, inadequate gasketing materials such as cork, nitrile rubber, and nitrile rubber-and-cork particles were used. While satisfactory for a limited period of time, these materials cannot be depended on for the expected long life of the equipment. The terminal chamber is usually above or below the switch compartment and separated by a steel wall through which the bushings are inserted. When bushings are properly selected and correctly installed, there is no leakage from one compart ment to the other. With poor bushing seals, and the terminal chamber above the switch, potting compounds or cable oil can seep into the askarel. When the terminal chamber is below the switch, askarel can drain into the terminal chamber. II. SOURCES OF CONTAMINATION There are three possible sources of contamination for askarel in switches and terminal chambers; they rank in this order of frequency: (1) water entering through poor gaskets; (2) decomposition products from arcing when switch is used to break magnetizing current; (3) entrance of pothead or cable compounds through leaky bushing seals. i Unlike an askarel transformer where the amount of contaminant is likely to be very small (probably only trace amounts) in relation to the volume of askarel fluid -- in switches or terminal chambers with faulty seals, the amount of contamination can be relatively large. DS\N 357747 18 STLCOPCB4086522 Experience has shown that, based on the number of installed askarel-switch units, the percentage of failures is extremely small. When investigated, it has been found that most failures originate in the switch chamber. Water is the chief source of contamination. However; heavy contamination of askarel with petrolatum and asphalt material, due to leakage, have caused a few failures. - Petrolatum is used frequently for filling terminal chambers. When either cable oil or petrolatum seeps into askarel, no great harm results. The fire resistance will be somewhat decreased and power factor of the askarel will increase with an accom panying drop in resistivity. While highly undesirable, it is doubtful that failure of the unit results. Where asphaltic compounds are used in place of petrolatum, the danger is increased somewhat because asphaltic contamination may cause exces sively high dielectric losses in the askarel. When the terminal chamber is below the switch chamber, the potting compound can be contaminated by askarel if the bushing seals are leaky. This is undesirable because the askarel will increase the power factor and conductivity of the potting compound or cable oil and develop heat from dielectric loss. If this mixture is drawn into the cable insulation, a cable failure is likely. This again emphasizes the impor tance of tight bushing assemblies. . I j | ' j i - : ; j III. SEALING SWITCHES AND TERMINAL CHAMBERS Proper bushing construction, use of Silastic seals and welding wherever possible is highly desirable (as covered in Section A). Where an elastomeric seal is to be used in contact with both askarel and petroleum oil, DuPont's Viton is suggested. For new equipment the user should specify these modern sealing arrangements to keep out contaminants and minimize maintenance. i IV. MAINTENANCE FOR ASKAREL FILLED SWITCHES A. Switches used for grounding after power source has been de-energized will not undergo arcing. B. Switches interrupting magnetizing current will be subject to arcing; the amount of decomposition will depend on power interrupted, time and frequency of oper ation. As a general rule, the liquid should be checked after 5 to 10 operations. DSW 357748 19 STLCOPCB4086523 1. On newly installed switches, check the askarel at 3,6 and 12 month intervals; if found satisfactory, check once annually thereafter. With proper attention to the gasketing of covers and bushings, experience will probably indicate that less frequent inspection is warranted. 2. Check askarel for: a. Dielectric strength (ASTM D877): It should be 26 KV minimum. If dielectric strength is low, confirm presence of water by Karl Fischer method ASTM D-1533. Filter to remove moisture. Dielectric strength should then be 30 KV minimum. b. Presence ofcarbon from arcing: Fluid should be relatively free ofcarbon. If badly arced and very black, replace fluid. If only minute amounts of carbon are present, filtration is recommended. Check power factor of liquid (should not be over 5% at 25C. and 60 cycles). Flush out switch chamber with several gallons of fresh askarel before refilling. 3. If there is discoloration, high power factor, detectable change in specific gravity or refractive index, or if fluid flashes below 250F., there is a possibility of seepage of potting compound into the switch compartment. In this case, correct any leaky bushing seals with proper replacements and fill with new askarel. 4. If terminal chamber is below switch, check potting compound for presence of askarel (can usually be detected by odor or by an increase in specific gravity). If askarel is present, correct any leaky bushing seals with proper replacements, and renew compounds. 5. Examine cover gaskets visually. Deterioration can be detected by swelling and cracking of the exposed edge. In cases of severe deterioration, liquid seepage is usually present. 6. Check for leakage at packing gland of switching shaft. If leaking, repack with a Silastic ring type gasket. 20 STLCOPCB4086524 / _ \ : ' SECTION C ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO Transformer users not wishing to make their own fluid analyses can obtain the service from Monsanto. Simply contact Monsanto and specify what analyses are wanted. You will be sent the proper-sized sample container filled with fresh askarel. When you receive this, empty it and carefully take your sample (following the procedure for sampling in this guide). Send the container to Monsanto's laboratory. Charges listed include sample container, shipping, handling and laboratory costs. Types of Analyses Available Analysis 1) ROUTINE MAINTENANCE CHECK Total Charge: $20.00 To determine the general condition of the fluid and find whether further analysis is neces sary. (one-quart sample required) . Properties Tested Color and Condition Dielectric Strength Moisture You will be notified of the results of this test. If further testing is indicated, and you want a complete analysis, you will be sent a five-pint sample container. This sample will be used for the following series of tests: Analysis 2) COMPLETE ANALYSIS Total Charge: $50.00 (a) To determine the extent of fluid contamination, (b) earth refinement to determine what degree of restoration of electrical and insulating properties is possible, (c) check test to see how the fluid responded to earth treatment. a) Complete Analysis: to determine the extent of contamination Properties Tested Color and Condition Specific Gravity Refractive Index Water Free Chlorides Acidity Dielectric Strength Power Factor, Dielectric Constant, and Resistivity oS\N 357750 21 STLCOPCB4086525 b) Earth Refinement Response: Consists of treatment for 2.5 hours at 50-60C. with 0.1 to 0.2 percent by weight of properly conditioned Attapulgus clay and then filtration through dry filter paper. c) Analysis After Laboratory Earth Refinement: Properties Tested Refractive Index Water Free Chlorides Acidity Dielectric Strength Power Factor, Dielectric Constant, and Resistivity You will be notified of the results of this test series on your sample. Then aftei refining your entire transformer fluid fill you can check on the results by requesting the following analysis: Analysis 3) ANALYSIS AFTER EARTH REFINEMENT Total Charge: $30.00 (This charge will not apply when m analyses 1 and 2 have already been made.) To determine whether the entire lot of the askarel fill responded to the same extent as the laboratory sample, (five-pint sample required) Properties Tested Color and Condition Refractive Index Water Free Chlorides Acidity Dielectric Strength Power Factor, Dielectric Constant, and Resistivity To arrange for the tests described above write to the following address: Paul G. Benignus Monsanto Chemical Company 800 North Lindbergh Blvd. St. Louis 66, Missouri . Samples to be tested should be clearly marked for identification and sent directly to: Monsanto Chemical Company W. G. Krummrich Laboratory Monsanto, Illinois Attention: R. Kuster . II DSW 357751 22 STLCOPCB4086526 APPENDIX APPENDIX A -- Askarel Stability and Composition of Arc Formed Gas: Askarel insulation is one of the most inert, chemically-stable heat resistant, non corrosive liquids known. It will not break down, oxidize or sludge when exposed to air and high temperatures, 150C. or even somewhat higher. Arcing, however, will break down the compound to liberate some hydrogen chloride and small amounts of carbon. APPROXIMATE COMPOSITION ARC FORMED GAS FROM TRANSFORMER ASKAREL Gas carbon monoxide........................... carbon dioxide................................ oxygen.............................................. inert gases........................................ hydrogen chloride.................... (note the absence of phosgene) Amount 0.3 per cent 0.3 0.6 1.5 97.3 This arc-formed gas is non-flammable and non-combustible. These requirements must be met in accordance with the Underwriters' Laboratory for permission to use the term askarel. Mineral oil evolves combustible hydrogen and hydrocarbon gases. For all practical purposes, the amount of gas liberated from mineral oil or askarel under a given set of conditions is about 100 cubic,centimeters per kilowatt-second. APPENDIX B Carbon dioxide................ Air...................................... Nitrogen............................ Hydrogen chloride1 .... 1) In absence of scavenger SOLUBILITY OF GAS IN TRANSFORMER ASKAREL Percent of Gas By Volume ______Corrected to: - 25C. 760 mm 0C. 760 mm 25C. 100C. 25C. 100C. 71% 47% -- -- 5.7 4.9 5.8 5.0 6.0 4.8 5.5 4.4 37.8 50.9 -- -- DSW 357752 23 STLCOPCB4086527 APPENDIX C APPROXIMATE VAPOR PRESSURE vs. TEMPERATURE FOR TRANSFORMER ASKAREL Temperature C 40 60 80 100 120 140 Inertecn PPO, 7336-9 1 mm Hg. 5 9 30 60 90 Transformer Pyranol A13B3B 0.9 mm Hg. 3.5 8.3 18 32 53 APPENDIX D EFFECT OF TEMPERATURE ON DIELECTRIC STRENGTH OF ASKAREL Temperature C. --60 --40 --20 0. c 20 40 60 80 Dielectric Strength 67 KV 63 57 55 50 50 48 45 . APPENDIX E COMPARISON QF THE APPROXIMATE VISCOSITY IN SAYBOLT UNIVERSAL SECONDS OF TRANSFORMER ASKARELS AND MINERAL OIL Temp. C. --20 0 20 40 60 80 100 Transformer Pyranol AI3B3B 1,000 100 70 45 39 34 30 10-C Mineral Oil 1,000 . ...... 150 85 49 ...... 40 34 30 . Inerteen PPO, 7336 2,800 195 85 50 40 36 33 j dsn*1 24 os'*1 jIi STLCOPCB4086528 APPENDIX F THE DENSITY OF INERTEEN PPO 733fc*>fiND TRANSFORMER PYRANOL A13B3B Approx. Density gm /cc. Transformer Temperature C. Inerteen PPO, 7336-9 Pyranol AI3B3B 0 1.574 1.577 20 1.552 1.555 40 1.529 1.532 60 1.507 1.510 80 1.485 1.488 APPENDIX G The thermal conductivity values of transformer Pyranol A13B3B at 27C. and 58C. are 26.2 and 25.8 x 10'5 calories centimeters'1, degrees centrigradesecond*1, respectively. Or, approximately 0.06 BTU per (hr.) (sq. ft.) (F.) per foot. This same approximation applies to Inerteen PPO (7336-9). APPENDIX H Heat Capacity Over the temperature range of 25 to 125C. the specific heat of transformer askarel is close to 0.30 calories per gram per degree. APPENDIX I ` Coefficient of Expansion The average coefficient of expansion of transformer askarel over the temperature range 20 to 100C. is 0.0007 cc/cc/C. One gallon would increase to 1.056 gallons on heating from 20 to 100C. APPENDIX J Fire-Resistance To use the generic name "askarel," the fluids must be approved by the Underwriters' Laboratories as possessing adequate fire-resistance and freedom from forming explosive gases when arced. These liquids do not have a burn point (ASTM D92-33) (Cleveland open cup method) up to about 205C., at which temperatures they begin to boil. The significance of this is that they do not burn or support combustion under conditions encountered in transformer operation. Thus the danger of secondary explosion (or fire) is eliminated. DSW 357754 25 STLCOPCB4086529 _\ appendix k Seals, Properties and Procurement Dow Corning Corporation, Midland, Michigan with District's at Atlanta, Boston, Chicago, Cleveland, Dallas, Los Angeles, New York City, Washington, D. C. and Toronto has available Bulletin 09-019, August 1962 entitled "Silastic Design Data". This lists the gasket fabricators throughout the country from whom the "Silastic 50" gasketing can be purchased in sheet, extrusions or molded shapes. Generally Silastic 50 sheet goods are stocked by local die cutters, hence, could be generally purchased locally. Usually, small quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other elastomersWhere the gasket is extruded for fitting into a machined groove or between gasket stops, Dow-Corning advises use of a scarved joint. This joint is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) materials, which air cure. Dow Corning points out that the local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll mill in preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 50 for 24 hours at 480F. SPECIFICATIONS* Color............................................... White Specific Gravity at 77F...............1.20 =*= 0.02 ASTM D676 -- Hardness, Shore A. Scale...........45 to 60 ASTM D412 -- Tensile Strength, psi. min...................... ... .800 ASTM D412 -- Elongation, percent, min............................ .250 ASTM D395 -- Compression Set after 22 hours at 300F., percent, max................................ 30 * All physical properties measured on 0.075 inch thick samples molded 5 minutes at 240F., and oven cured 24 hours at 480F. General Electric Company, Redmond Circle, Rome, Ga., uses silicone or DuPont's Viton wherever it is not possible or desirable to weld. For some small seals, where good matching surfaces are provided, Flexitallic stainless steel rings are used. By contacting the Engineering Services Department of General Electric Company, Redmond Circle, Rome, Ga., users of Pyranol transformers made prior to develop ment of these modern seals will obtain prompt assistance for conversion. Users of askarel transformers made by other manufacturers should contact the original transformer manufacturer, or Monsanto for assistance in converting to these modern seals. * DSW 357755 26 STLCOPCB4086530