Document jyNBogMYveL4QnvpL9YdLD2eQ

Chapter 51 1945 Guide 'Air Duct Design 564 565 where. H* = friction loss, inches of water at standard conditions. . V -- velocity of air, feet per minute. D = diameter of duct, feet. The chart shown in Fig. 2 was constructed from Equation 4 and there-" fore applies only for round galvanized iron duct of good construction with 40 joints per 100 ft, and for air at standard conditions. Nofactor of safety has been applied. In view of the many variations that may occur in duct construction and application, it is recommended that a factor of safety be used which, in the judgment of the engineer, will make due allowance for these variations. In the Laboratory tests the variation found in pressure loss between the best joints and the worst joints was approxi- . mately 10 per cent. This would suggest a minimum factor of safety of 10 per cent. Note: As no safety factor is included in chart due allowance must be made. For field application mu tiply pressure drop from, chart by not less than 1.1. Where- jupoises Ts deg abs cent C Sutherlands constant 120 tot air . Mo at t170.9 * 10i* t c0. Pounds mass per ft per sec -poises x 0.0672 0 40 80-120 160 200 240 AIR TEMPERATURE. DEG FAHR ' Fig. 3. Temperature--Viscosity Curve for Dry Air The friction loss varies with the surface characteristics of a duct and in case a rough conduit of tile, brick or concrete is used, a factor of about SB per cent should be added to the friction values obtained from Fig. 2. Since the friction chart' applies only for standard conditions, it is necessary to apply correction factors for other than standard conditions.' These corrections are: ~) (5) where 11A = friction loss, inches of water at actual conditions. 5 = ratio of density of air at actual conditions to density of air at standard con ditions. _' Ta = kinematic viscosity at actual conditions. Ts = kinematic viscosity at standard conditions. Kinematic Viscosity = --