636 CHAPTER 42 - 1965 Guide And Data-Book * Per toe of refrigerating effect occurring in evaporator. Fig. 2 .... Heat Removed in Refrigerant 12 Condenser* Ushed after some period of use, but on steel tubes fouling seems to be progressive and performance after each successive period of use and recleaning is often progressively lower.' Bimetallic tubes, in which the outer tube is steel and the inner liner is copper, admiralty metal, or other nonferrous alloy, have good cleanability. for ammr>nj* condenser applica tions. Since ammonia condenser ratings should be based upon the fouled and corroded condition of steel tubes, it is possible to obtain the same performance and a more consistent heat transfer rate with less surface by using bimetallic tubes. The cost of bimetallic tubes may be about three times that of * ordinary steel tubing, but can often be justified by the use of less surface, longer life, and better performance. The progressive decrease in capacity of shell-and-tube or shell-and-coil condensers is due to the fouling on the water-side of the tubes. In order that condensers will have sufficient excess tube surface to maintain satisfactory performance in normal operation, with a reasonable period of service be tween cleanings, it is recommended that standard minimum fouling factors be used. For general raring purposes the values of fouling factors 1/A, are recommended4 as 0.0005 for nonferrous tubes and 0.001 for steel tubes. For conditions of ex treme fouling and poor maintenance, higher fouling factors should be used. The factor is the reciprocal of the heat trans fer rate through the layer of the deposit on the surface of the tubing. The effect of fouling resistances in reducing elami Note.- footing ndttaneo 1/h It equfvafe/sf to Sa/by. h Fig. 1, If the added footing /variance it bated on external sorfoce, ur* the fooling re- ririanev carve* directly. If the odded fowling reactance h bated on rntemaf s/rfbee, cue an equivalent externerf /variance hand by multiplying (be internal footing reriricace by (be ratio of external to internal surface (SeJ. Fig. 4 .... Effect of Fouling Resistance on Heat Transfer Coefficients tube coefficients is shown in Fig. 4. Since' it' is customary to refer all resistances to external surface. Fig. 4 may be used directly for external fouling, but for internal fouling the foul ing factor 1/A, must be multiplied by the ratio of the external to internal tube surfaces Sa- Example t: Determine the design coefficient U for a ahdl-eiidtobe condenser (water in the tubes and refrigerant in the shell) with finned tubes having a ratio of external to internal, surface, Sx, of 3.54. if the coefficient for clean tubes a 200 Btu d (hr) (sq ft) (F deg) and the water-side fouling resistance 1/ft, ts 0.001. Table 2 .... Fouling Factors for Condenser Water typos of Water . For Noa-ferroot Tubes Water Velocity, fps For Ferrout Tuber Wafer Vefoa'fy, fps 3 or leu Over 3 3 or leu Over 3 Sea Water 0.0005 Brackish Water 0.002 Cooling Tower and. Artificial Spray Pond: Treated Make-Up 0.001 Untreated 0.003 City or Well Water (Such aa Great Lakes) 0.001 Great Lakes 0.001 0.0005 0.001 0.001 0.003. 0.001 0.001. 0.001 0.0010.004 0.002 6.002* 0.602' 0.006 0.006' 0.002 0.002 0.002 0.002 River Water: Minimum 0.002 Mississippi 0.003 Delaware, Schuykill 0.003 East River and New York Bay 6.003 Chicago Sanitary Canal - 0.008 0.001 0.002 0.002 0.002' 0.006 0.004 0.006 0.006 0.006 0.016 0.002 0.004 0.004 0.004 0.012 Muddy or Silty Hard (Over 15 groins/sal) Engine Jacket Distilled Treated Boiler Feedwater Boiler Blowdown 0.003 0.003 0.001 0.0005 0.001 0.002 0.002 0.003 0.001 0.0005 0.0005 0.002 0.006 o:oo3 0.002 0.001 o;oo2 0.004 0.004 0.003 0.002 0.001 0.001 0.004 * Par tea of rafrigarefiag affeef occurring in evaporator.' Fig. 3 .... Heat Removed in Refrigerant 22 Condenser* Notd:-Values are "f....... .. a* 1/4,. Valuev for nonferrous tubea are from data in the Tubular Exchanger Manufacturer* Aooetatioa Standards, IMS. /or assn tubuv * t*4ie4 the water (6 be employed it ns/i-eariveue te the allrV Seav teed. Far the purposes of this reooauaeaaed standard, A2U has interpreted these data aa applying to nen/arvvs tubes. For stainless steel tubes, use values for Botrierrous tubes. Condensers 687 Condenser and Receiver Solution: The equivalent- fouling resistance is determined by multiplying the fouling resistance 1/A, by the ratio of external to internal surface Ss, or 0.001 X 3.54 = 0.00354. Enter Fig. 4 at the 'coefficient value of 200 and proceed vertically to the equivalent fouling resistance of 0.00354. Proceeding horizontally the coefficient U is found to be 117 Btu per (hr) (sq ft) (F deg). Tubes of halocarbon refrigerant condensers are normally nonferrous, externally finned tubes. Although internal scale forms at a slower rate than with steel tubes, .the fouling factor for a given scale thickness is greater for finned tubes because it must be multiplied by a higher surface ratio. Table 2 fists the fouling factors for various types of water. __ Horizontal Cosed Shell-and-Tube Ammonia Con densers Tins type of condenser is used in many industrial appUra-"* tions since it can be located in the compressor room in a com pact installation under convenient supervision of-the operatr-. mg engineer. See Fig. 5. Steel tubes, 1 in. OD, having 0.095 in. average wall are common. The number of tubes varies from approximately 50 in a 14-in. shell to 1100 in a 60-in. shelL Fig. 6 may be used to calculate the performance of hori zontal nmmnnift condensers based on: (1) commerciailyclean tubes in a condenser free of noncondensable gases, (2) a temperature rise factor of 30 gal deg per (min) (ton) for the condenser water, and (3) heat rejection of 15,000 Btuh per ton from the ammonia vapor.4 The leaving terminal difference; (Parts A & B of Fig. 6) is the difference between the condensing temperature (tempera ture corresponding to the pressure of the ammonia) and the leaving temperature of the condenser water. The length of travel is the tube length multiplied by the number of passes through riie condenser. The loading of a condenser is the square feet of external tube surface per ton of refrigeration. The quantify of circulated water is commonly given' in gpm per ton of refrigeration. The condensing temperature (the sum of the entering water temperature, the temperature rise in the condenser,' and-the leaving terminal difference) is determined by the selection of a water quantify, length of travel, and loading that will give a relatively low condensing temperature, with a'reasonable pressure drop. Since the terminal differences given in Fig. 6 are based on a condeoser free of noncondensable gases,-it is recommended that an allowance of 1J> P deg be added to- the leaving terminal difference, to allow for noncondensatde gases. In refrigeration systems operating below atmospheric pres sure, or where unusually high percentages of noncondensable gases are present, this allowance should be increased. Parts A and B of Fig. 6 show typical values of leaving terminal difference as a function of length of travel, water quantify, and loading. Part A is based on a loading of 8 sq ft per ton, while Part B provides corrections for other loadings; LENGTH OF TRAVEL FEET CORRECTED PRESSURE DROP -L9/SQ JN.