A.I.A. Form No. 30-C-l [February, 1971)
:na installation fims
The new G-40 gas boiler by American-Standard is suit able for installation in larger residences and small apart ment and commercial buildings. Designed for both hot water and steam installations, it can be furnished with a tankless type, internal, domestic water heater for either application. An attractive two-tone boiler jacket gives the G-40 a clean, streamlined appearance.
Ruggedly constructed of durable cast iron, the new G-40 is available in 3 to 14 section sizes with A.G.A. design certified outputs from 120,000 to 780,000 btu/hr. All sections are tested for 50 psi water working pressure. On-site assembling time can be decreased by ordering
up to 14 sections pre-assembled, with or without factoryinstalled tankless heater. An exclusive built-in air elim inator--the EUMINAIRE -- is furnished on all boilers, specifically for hot water installations, saving the addi tional expense of an external device.
The G-40 is provided with two 3" top flow tappings and two 3" return flow tappings to allow flexibility in de signing system piping when the G-40 is installed in con fined areas. For further convenience, complete manifold and all controls are shipped factory assembled. Selfenergizing controls and electronic controls are available as options.
1- : -is a patented cost-saving feature of the G-40. This unique built-in air eliminator is integrally cast into the left hand end section. Furnished in all boilers, specifically for hot water installations, the EUMINAIRE baffle diverts rising air bub-' bles into a tapping for connection to the expansion tank. No external device is required to separate air and water-thus reducing both costs and installation time.
2- :r:rois-mounted on front and left side of boiler for easy adjustment and mainte nance. Optional electronic controls and self energizing controls available.
3- atsr heater-large, finned copper coil tankless type available for steam or water installations. Inserted where hottest water is in contact with heater coil.
4-'::omgs-two 3" supply (top) and two 3" return tappings (side) simplify piping hook-up.
5-,3:Ker-sturdy steel with smart beige and brown finish, modern square corners. Inner surfaces protected with heavy glass fiber in sulation-prevents wasteful heat loss, keeps jacket cool.
6-Juiit-in crart coco-completely enclosed in jacket; eliminates unsightly protrusion in rear of boiler.
7-'cs; Ton secticns--multiple pin-like pro jections for maximum heat extraction. Tested for 50 psi water working pressure. End sec tions designed with extended legs to elim inate need for separate base.
8-:urners-precision made and factory tested to assure quiet, efficient operation with all gases. Cast iron, drilled port burners supplied for natural gas. Cleanable ribbon burners standard for propane gas.
9-s*'Dry assembled ms.vfc:: `.re :.c --only requires attachment to boiler. Com pletely enclosed by jacket.
EUMINAIRE# is a trademark 0/ AMERICAN STANDARD inc.
G-40 ratings (natural and propane gases)
boiler
no. of
no. of
for installations from sea level to 2000 ft.
A.G.A. ratings
|
net 1 = B = R ratings A 1 chimney
input (Btu/hr)
cutput (Btu/hr)
water (Btu/hr)
steam (sq. ft.)
steam I diameter
(Btu/hr)
(inches)
height (feet)
G-403 G-404 G-405 G-406 G-407 G-408 G-4Q9
3 4 5 6 7 8 9
2
150,000
120,000
104,300
375
90,000
3
225,000
180,000
156,500
563 135,000
4
300,000
240,000
208,700
750 180,000
5
375,000
300,000
260,900
938 225,100
6
450,000
360,000
313,000
1125
270,100
7
525.000
420,000
365,200
1313
315,100
8
600,000
480,000
417,400
1500
360,100
G-4010
10
9
675,000
540,000
469,600
1688
405,100
G-4011
11
10
750,000
600,000
521,800
1875
450,000
G-4012
12
11
825,000
660,000
574,000
2063
495,200
G-4013 G-4014
13 14
12
900,000
720,000
626,200
2250
540,000
13
975,000
780,000
678,400
2438
585,100
For altitudes above 2000 ft., ratings should be reduced at the rate of 4% for each 1000 ft. above sea level.
8 8 8 10 10 10 10 12 12 12 12
15
Net I = B = R ratings shown are based on a piping and pick up allowance of 1.333 for steam and 1.15 for water. American-Standard
should be consulted before selecting a boiler for installations having unusual piping and pick up refluirements.
15 15 15 15 15 15 15 15 15 15 15 15
G-40 tankless heater ratings
100F rise in temperature with 200*F bailer water temperature (gallons per minute)
boiler number
heater no. 218 water steam
heater no. 222 water steam
heater no. 226 water steam
heater no. 232
water
steam
heater no. 445
water
steam
G-403
4
3
-- ___
____ ___ ___
___
G-404
4
3Va 4Vi 4
-- -- -- ----
--
G-405
4
3Vi 4Va 4
6
5Vi --
----
--
G-406 G-407 G-408
4 3Vi 4 ' 3Vi 4 3Vi
4Vi 4
4Vi 4 4Vi 4
6 5 Vi --
6Vi
"6" "
7Vz
6Vi 6"_
8
-- 7 7Vi
--
-- 9
-- --
8Vi
G-409 G-4010
4 4
3Vi 4Vi 4 3Vi 4Vi 4
6Vi
6
8
-:-7vfT"
9
8Vi
6Vi ' e - : 8
- 7Vi: 9 " 8Vi '
G-4011
4
3Vi 4Vi 4
6Vi
6-
8
9 8V*
G-4012 G-4013 G-4014
4 4 4
3Vi 4Vi 4 3Vi 4Vi 4 3Vi 4Va 4
6Vi
6. 8
-7V4 '
9
6Va '6
8 7Vi 9
6Vz 6 8 Th 9
8Vz evi 8V4
NOTE: For Steam boiler-heater combinations shown shaded, extra aquastat in right end section is recommended.
heater no. 460
water
steam
_
--
-- --
--
--
--
-- 12 13 14Vi 15Vi
____ ___
____ ____ -- --
--
11 12 13 13
G-40 gas boilers by American-Standard have ratings approved by the Institute of Boiler and Radiator Manufacturers. The boilers are constructed to the specifications of the American Society of Mechanical Engineers and are design certified by the Am can Gas Association. The G-40 bears the l=B = R, A.S.M.E. and A.GA symbols. All sizes if the G-40 are available in models for forced and gravity hot water, and steam systems.
sample specification for G-40
Contractor shall furnish and install, as indicated on plans, ............ gas fired botler(s), having an input of............ Btuh and a gross output of............Btuh when fired with............. gas. Boiler(s) shall be constructed of cast iron in accord ance with A.S.M.E. requirements for low pressure heating
boilers and bear the A.S.M.E. symbol. Boiler(s) shall be A.GA design certified and have l=B=R approved ratings. Boiler(s) shall be furnished with an air elimination device integrally cast into the left hand end supply tapping. Boiler(s) shall be composed of cast iron sections with ver tical flues and furnished with one atmospheric drill port
or removable ribbon burner per flueway. Boiler(s) shall be supplied by manufacturer with one main automatic dia phragm gas valve, safety pilot with thermocouple and additional lighting pilots as required, one gas pressure regulator (except for propane gas), high limit control, and
integral canopy and drafthood. Water or steam trim as
required. Boiler(s) shall be supplied with internal type tankless
heater capable of supplying.............. gallons per minute at a 100F rise in temperature.
3
minimum piping recommendations hot water steam
gas fired boilers
boiler number
G-403 G-404 G-405 G-406 G-407
riser (in.j
return (in.)
equal izer (in.)
2 1 lVz
2Vi 1
lVz
2Vz 1
lVz
3 IV* IV2
3 ly* lVi
boiler number
gravity | forced
supply return supply return (in.) (in.) (in.) (in.)
G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014
2 2
2Vz (2)-2 (2)-2 (23-2 ' (2)-2Vz (2!-2Va (23-3 (2)-3 (23-3 (2)-3
2 2
2Vj (2)-2 (2)-2
(23-2 (2)-2Vz (2)-2Vj
(2)-2Vi (2)-2Vj
(2)-2Vz (2)-2%
iv* iv2 2 2 2 2Vz 2Vz ZVi 3 3 3 3
ly* IV2 2 2 2 2Yi 2Vz 2Vi 3 3 3 3
NOTE: Left hand supply connection featuring the EL1MINAIRE is used on water boilers. Limit control should also be placed m the left hand section. Where Doth outlets and return are used on gravity systems, make respective supply and return connection at opposite ends of the boiler.
to supply mam
boiler number
riser (in.)
return (in.)
header (in.)
equal izer (in.)
G-408 (23-2 lVi 4 lVi G-409 (2}-2 1% 4 2 G-4010 (2>-3 lVt 4 2 G-4011 (23-3 m 4 2 G-4012 (2)-3 1 Vt 4 2 G-4013 (2)-3 lVa 4 2 G-4014 (2)-3 lVi 4 2
ga? control and connection sizes; pertinent data
boiler number
water content (pounds)
water steam
approx. weight
(pounds)
size of manifold (inches)
nat. Si propane gases
G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014
220.8 281.0 341.2 401.4 461.6 521.8 582.0 642.2 722.4 782.6 842.8 903.0
164.4 209.9 255.4 300.9 346.4 391.9 437.4 482.9 528.4 573.9 619.4 664.9
858 1027 1195 1370 1544 1713 1880 2050 2219 2388 2557 2726
Pressure regulator not furnished for Propane gas.
1V IV. IV* IV* IV* IV* IV* IV* lVi lVi lVi lVi
pressure regulators (inches)
nat.
Vi y* 1 1 1 1 IV* IV* IV* IV* IV* IV*
automatic gas valve, gas connections and manual shutoff valve sizes (inches)
nat propane
Vi Vz y Vi 1 Vi 1 y 1 y* 1 y* IV* 1 IV* 1 IV* 1 IV* 1 IV* 1 IV* 1
AMERICAN STANDARD
4
dimensions for inlets and outlets
bailer number
A
dimensions (inches) B CDE F
G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014
7`X, 10K. 12X, 10X. 12K. 13X. 14X. 16K. 13X. 14'X.
1595. 16'X.
10 11 12V4 15 16% 13 14
1516 1614
5K 5'X. 6K. 5X. 5 5`X. 6X. 6K 5`X. 5'K. 6X. 6X
914 14 1814 23 2714 32 3614 41
4514 50
5414 59
3X. 3X. 3X. 3'X. 3`X. 3`X. 3`X. 3`X. 3'X. 3'X. 3`X. 3`X.
6 7 8 7 8 8 9 9 8 8 9 9
L
1514 2014 2514 30% 35% 39% 44% 48% 53% 57% 62% 66%
gas fired boilers
orifice drill sizes--main burner spuds (at sea level)
natural gas
sewage gases
prepane gas
per specific 800 900 1000 1100 1200 600 650 700 750 800 burner gravity BtU Btu Btu Btu Btu Btu Btu Btu Btu Btu (Btuh) of gas cu.fl. cu. ft. cu. ft cu. ft. CU.fL eu-ft eu. ft cu.ft eu. ft eu-ft
75,000 0.60 X. 16 19 21 24 _ _ -- -- --
75,000 0.65 11 15 18 20 -- -- -- -- -- --
75,000 0.70 10 14 17 19 21 A 2 3 4 7
75,000 0.80 -- -- -- -- -- C 1 2 3 4
75,000 0.90 -- ___ ___ ___
DB1 23
75,000 1.53
2500 Btu cu.rt
_
--
--
-- ___
41
NOTE: See level ratings era to be used for elevations between 0 and 2.000 ft For altitudes above 2,000 ft, sea level ratings should be reduced at the rate of 4% for each 1.000 ft above sea level.
manifold pressure
table
gas
natural propane sewage gas
heating value*
manifold pressure (in. HiO)
800-1200 2500
600-800
3.5 11.0
3.0
heating value of gas at sea level
(60F and 30 In. Hg.)
AMERICAN STANDARD
5
gas fired boilers
assemblage of sections control tappings
boiler number
G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014
assemblage of sections
no. of sections
3 4 5 6 7 8 9 10 11 12 13 14
dimensions (inches)
LK
13 17% 22
26% 31 35% 40 44% 49 53% 58 62%
9% 14 18% 23 27% 32 36% 41 45% 50 54% 59
3" (low
location A
control tappings (steam)
size of tappings (in.)
control used
% pressure gauge
8 1%
blow-off
C % tankless heater control
01
safety valve
E
%
gauge glass and low water cut-off
installed in blow-off piping.
location F G
H
J
control tappings (hot water)
size of tappings (in.)
control used
%
temperature and altitude gauge
%
auxiliary limit control (when required)
combination operating, high limit and low voltage relay immersion
control (for installation with % tankless water heater)
limit control (for installation without tankless water heater)
1 pressure relief valve
orm No. 728-2 (Rev 2) (2/71)
AMERICAN STANDARD
PLUMBING / HEATING
P.O BOX 2003. NEW BRUNSWICK. N. / 08903