Document jm8kD189jkpyKb4MQ8yz04xZQ

A.I.A. Form No. 30-C-l [February, 1971) :na installation fims The new G-40 gas boiler by American-Standard is suit able for installation in larger residences and small apart ment and commercial buildings. Designed for both hot water and steam installations, it can be furnished with a tankless type, internal, domestic water heater for either application. An attractive two-tone boiler jacket gives the G-40 a clean, streamlined appearance. Ruggedly constructed of durable cast iron, the new G-40 is available in 3 to 14 section sizes with A.G.A. design certified outputs from 120,000 to 780,000 btu/hr. All sections are tested for 50 psi water working pressure. On-site assembling time can be decreased by ordering up to 14 sections pre-assembled, with or without factoryinstalled tankless heater. An exclusive built-in air elim inator--the EUMINAIRE -- is furnished on all boilers, specifically for hot water installations, saving the addi tional expense of an external device. The G-40 is provided with two 3" top flow tappings and two 3" return flow tappings to allow flexibility in de signing system piping when the G-40 is installed in con fined areas. For further convenience, complete manifold and all controls are shipped factory assembled. Selfenergizing controls and electronic controls are available as options. 1- : -is a patented cost-saving feature of the G-40. This unique built-in air eliminator is integrally cast into the left hand end section. Furnished in all boilers, specifically for hot water installations, the EUMINAIRE baffle diverts rising air bub-' bles into a tapping for connection to the expansion tank. No external device is required to separate air and water-thus reducing both costs and installation time. 2- :r:rois-mounted on front and left side of boiler for easy adjustment and mainte nance. Optional electronic controls and self energizing controls available. 3- atsr heater-large, finned copper coil tankless type available for steam or water installations. Inserted where hottest water is in contact with heater coil. 4-'::omgs-two 3" supply (top) and two 3" return tappings (side) simplify piping hook-up. 5-,3:Ker-sturdy steel with smart beige and brown finish, modern square corners. Inner surfaces protected with heavy glass fiber in sulation-prevents wasteful heat loss, keeps jacket cool. 6-Juiit-in crart coco-completely enclosed in jacket; eliminates unsightly protrusion in rear of boiler. 7-'cs; Ton secticns--multiple pin-like pro jections for maximum heat extraction. Tested for 50 psi water working pressure. End sec tions designed with extended legs to elim inate need for separate base. 8-:urners-precision made and factory tested to assure quiet, efficient operation with all gases. Cast iron, drilled port burners supplied for natural gas. Cleanable ribbon burners standard for propane gas. 9-s*'Dry assembled ms.vfc:: `.re :.c --only requires attachment to boiler. Com pletely enclosed by jacket. EUMINAIRE# is a trademark 0/ AMERICAN STANDARD inc. G-40 ratings (natural and propane gases) boiler no. of no. of for installations from sea level to 2000 ft. A.G.A. ratings | net 1 = B = R ratings A 1 chimney input (Btu/hr) cutput (Btu/hr) water (Btu/hr) steam (sq. ft.) steam I diameter (Btu/hr) (inches) height (feet) G-403 G-404 G-405 G-406 G-407 G-408 G-4Q9 3 4 5 6 7 8 9 2 150,000 120,000 104,300 375 90,000 3 225,000 180,000 156,500 563 135,000 4 300,000 240,000 208,700 750 180,000 5 375,000 300,000 260,900 938 225,100 6 450,000 360,000 313,000 1125 270,100 7 525.000 420,000 365,200 1313 315,100 8 600,000 480,000 417,400 1500 360,100 G-4010 10 9 675,000 540,000 469,600 1688 405,100 G-4011 11 10 750,000 600,000 521,800 1875 450,000 G-4012 12 11 825,000 660,000 574,000 2063 495,200 G-4013 G-4014 13 14 12 900,000 720,000 626,200 2250 540,000 13 975,000 780,000 678,400 2438 585,100 For altitudes above 2000 ft., ratings should be reduced at the rate of 4% for each 1000 ft. above sea level. 8 8 8 10 10 10 10 12 12 12 12 15 Net I = B = R ratings shown are based on a piping and pick up allowance of 1.333 for steam and 1.15 for water. American-Standard should be consulted before selecting a boiler for installations having unusual piping and pick up refluirements. 15 15 15 15 15 15 15 15 15 15 15 15 G-40 tankless heater ratings 100F rise in temperature with 200*F bailer water temperature (gallons per minute) boiler number heater no. 218 water steam heater no. 222 water steam heater no. 226 water steam heater no. 232 water steam heater no. 445 water steam G-403 4 3 -- ___ ____ ___ ___ ___ G-404 4 3Va 4Vi 4 -- -- -- ---- -- G-405 4 3Vi 4Va 4 6 5Vi -- ---- -- G-406 G-407 G-408 4 3Vi 4 ' 3Vi 4 3Vi 4Vi 4 4Vi 4 4Vi 4 6 5 Vi -- 6Vi "6" " 7Vz 6Vi 6"_ 8 -- 7 7Vi -- -- 9 -- -- 8Vi G-409 G-4010 4 4 3Vi 4Vi 4 3Vi 4Vi 4 6Vi 6 8 -:-7vfT" 9 8Vi 6Vi ' e - : 8 - 7Vi: 9 " 8Vi ' G-4011 4 3Vi 4Vi 4 6Vi 6- 8 9 8V* G-4012 G-4013 G-4014 4 4 4 3Vi 4Vi 4 3Vi 4Vi 4 3Vi 4Va 4 6Vi 6. 8 -7V4 ' 9 6Va '6 8 7Vi 9 6Vz 6 8 Th 9 8Vz evi 8V4 NOTE: For Steam boiler-heater combinations shown shaded, extra aquastat in right end section is recommended. heater no. 460 water steam _ -- -- -- -- -- -- -- 12 13 14Vi 15Vi ____ ___ ____ ____ -- -- -- 11 12 13 13 G-40 gas boilers by American-Standard have ratings approved by the Institute of Boiler and Radiator Manufacturers. The boilers are constructed to the specifications of the American Society of Mechanical Engineers and are design certified by the Am can Gas Association. The G-40 bears the l=B = R, A.S.M.E. and A.GA symbols. All sizes if the G-40 are available in models for forced and gravity hot water, and steam systems. sample specification for G-40 Contractor shall furnish and install, as indicated on plans, ............ gas fired botler(s), having an input of............ Btuh and a gross output of............Btuh when fired with............. gas. Boiler(s) shall be constructed of cast iron in accord ance with A.S.M.E. requirements for low pressure heating boilers and bear the A.S.M.E. symbol. Boiler(s) shall be A.GA design certified and have l=B=R approved ratings. Boiler(s) shall be furnished with an air elimination device integrally cast into the left hand end supply tapping. Boiler(s) shall be composed of cast iron sections with ver tical flues and furnished with one atmospheric drill port or removable ribbon burner per flueway. Boiler(s) shall be supplied by manufacturer with one main automatic dia phragm gas valve, safety pilot with thermocouple and additional lighting pilots as required, one gas pressure regulator (except for propane gas), high limit control, and integral canopy and drafthood. Water or steam trim as required. Boiler(s) shall be supplied with internal type tankless heater capable of supplying.............. gallons per minute at a 100F rise in temperature. 3 minimum piping recommendations hot water steam gas fired boilers boiler number G-403 G-404 G-405 G-406 G-407 riser (in.j return (in.) equal izer (in.) 2 1 lVz 2Vi 1 lVz 2Vz 1 lVz 3 IV* IV2 3 ly* lVi boiler number gravity | forced supply return supply return (in.) (in.) (in.) (in.) G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014 2 2 2Vz (2)-2 (2)-2 (23-2 ' (2)-2Vz (2!-2Va (23-3 (2)-3 (23-3 (2)-3 2 2 2Vj (2)-2 (2)-2 (23-2 (2)-2Vz (2)-2Vj (2)-2Vi (2)-2Vj (2)-2Vz (2)-2% iv* iv2 2 2 2 2Vz 2Vz ZVi 3 3 3 3 ly* IV2 2 2 2 2Yi 2Vz 2Vi 3 3 3 3 NOTE: Left hand supply connection featuring the EL1MINAIRE is used on water boilers. Limit control should also be placed m the left hand section. Where Doth outlets and return are used on gravity systems, make respective supply and return connection at opposite ends of the boiler. to supply mam boiler number riser (in.) return (in.) header (in.) equal izer (in.) G-408 (23-2 lVi 4 lVi G-409 (2}-2 1% 4 2 G-4010 (2>-3 lVt 4 2 G-4011 (23-3 m 4 2 G-4012 (2)-3 1 Vt 4 2 G-4013 (2)-3 lVa 4 2 G-4014 (2)-3 lVi 4 2 ga? control and connection sizes; pertinent data boiler number water content (pounds) water steam approx. weight (pounds) size of manifold (inches) nat. Si propane gases G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014 220.8 281.0 341.2 401.4 461.6 521.8 582.0 642.2 722.4 782.6 842.8 903.0 164.4 209.9 255.4 300.9 346.4 391.9 437.4 482.9 528.4 573.9 619.4 664.9 858 1027 1195 1370 1544 1713 1880 2050 2219 2388 2557 2726 Pressure regulator not furnished for Propane gas. 1V IV. IV* IV* IV* IV* IV* IV* lVi lVi lVi lVi pressure regulators (inches) nat. Vi y* 1 1 1 1 IV* IV* IV* IV* IV* IV* automatic gas valve, gas connections and manual shutoff valve sizes (inches) nat propane Vi Vz y Vi 1 Vi 1 y 1 y* 1 y* IV* 1 IV* 1 IV* 1 IV* 1 IV* 1 IV* 1 AMERICAN STANDARD 4 dimensions for inlets and outlets bailer number A dimensions (inches) B CDE F G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014 7`X, 10K. 12X, 10X. 12K. 13X. 14X. 16K. 13X. 14'X. 1595. 16'X. 10 11 12V4 15 16% 13 14 1516 1614 5K 5'X. 6K. 5X. 5 5`X. 6X. 6K 5`X. 5'K. 6X. 6X 914 14 1814 23 2714 32 3614 41 4514 50 5414 59 3X. 3X. 3X. 3'X. 3`X. 3`X. 3`X. 3`X. 3'X. 3'X. 3`X. 3`X. 6 7 8 7 8 8 9 9 8 8 9 9 L 1514 2014 2514 30% 35% 39% 44% 48% 53% 57% 62% 66% gas fired boilers orifice drill sizes--main burner spuds (at sea level) natural gas sewage gases prepane gas per specific 800 900 1000 1100 1200 600 650 700 750 800 burner gravity BtU Btu Btu Btu Btu Btu Btu Btu Btu Btu (Btuh) of gas cu.fl. cu. ft. cu. ft cu. ft. CU.fL eu-ft eu. ft cu.ft eu. ft eu-ft 75,000 0.60 X. 16 19 21 24 _ _ -- -- -- 75,000 0.65 11 15 18 20 -- -- -- -- -- -- 75,000 0.70 10 14 17 19 21 A 2 3 4 7 75,000 0.80 -- -- -- -- -- C 1 2 3 4 75,000 0.90 -- ___ ___ ___ DB1 23 75,000 1.53 2500 Btu cu.rt _ -- -- -- ___ 41 NOTE: See level ratings era to be used for elevations between 0 and 2.000 ft For altitudes above 2,000 ft, sea level ratings should be reduced at the rate of 4% for each 1.000 ft above sea level. manifold pressure table gas natural propane sewage gas heating value* manifold pressure (in. HiO) 800-1200 2500 600-800 3.5 11.0 3.0 heating value of gas at sea level (60F and 30 In. Hg.) AMERICAN STANDARD 5 gas fired boilers assemblage of sections control tappings boiler number G-403 G-404 G-405 G-406 G-407 G-408 G-409 G-4010 G-4011 G-4012 G-4013 G-4014 assemblage of sections no. of sections 3 4 5 6 7 8 9 10 11 12 13 14 dimensions (inches) LK 13 17% 22 26% 31 35% 40 44% 49 53% 58 62% 9% 14 18% 23 27% 32 36% 41 45% 50 54% 59 3" (low location A control tappings (steam) size of tappings (in.) control used % pressure gauge 8 1% blow-off C % tankless heater control 01 safety valve E % gauge glass and low water cut-off installed in blow-off piping. location F G H J control tappings (hot water) size of tappings (in.) control used % temperature and altitude gauge % auxiliary limit control (when required) combination operating, high limit and low voltage relay immersion control (for installation with % tankless water heater) limit control (for installation without tankless water heater) 1 pressure relief valve orm No. 728-2 (Rev 2) (2/71) AMERICAN STANDARD PLUMBING / HEATING P.O BOX 2003. NEW BRUNSWICK. N. / 08903 -= .n u.S A