Document jgarGKOmoyeJQxd7Zn59kvgOQ
762
CHAPTER 41
>1948. Guide
angles are usually riveted to the duct about 2 in. from the slips. It is good practice to cross-break or kink all flat surfaces to prevent vibration or buckling due to the air flow arid accompanying variations', in'internal
pressure.- Round ducts are sometimes swedged l.oin. from the ends so that the larger end will-butt against the swedge and are held in place with sheet metal screws. Where swedges are not used it is general practice to paste the joint with asbestos paper to insure a tight joint.,
Grooved seam
Standing seam
S
slip
1 T-J,-
Drive slip
OouMe seem
Pittsburgh seam
Bar
Reinforced Pocket .
End slip
Angle
Fig. 8. Sheet Metal Duct and Arrangement Details
The construction of elbows and changes of shape cannot be definitely outlined because of the varied conditions encountered in the field, but in general long radius elbows apd gradual changes in shape tend to maintain uniform velocities, accompanied by decreased turbulence, lower resistance and a minimum of noise.
. -Heavy canvas connections (asbestos cloth if there is a fire hazard) are recommended on both the inlet and outlet to all fans. The fan discharge connections shown in Fig. 8 are marked good, fair, and poor in the order
Air Duct Design
763
Table 6. Recommended Sheet Metal Gages fob Rectangular Duct Construction3
s.U. Std. Maximum Side,
Gags
Inches.
26 Up to 12
Type of Transverse Joint Connectionsb
S, Drive, Pocket or Bar Slips, on 7 ft 10 in. centers
None
Bracing
13 to 24
S, Drive, Pocket or Bar Slips, on
7 ft 10 in. centers
None
25 to 30
S, Drive, J in. Pocket or 1 in Bar 1 x 1 x Y in. angles
Slips, on 7 it 10 in. centers0
4 ft from joint
31 to 40 Drive, 1 in. Pocket or 1 in. Bar 1 x 1 x Y in- angles
Slips, on 7 ft 10 in. centers0
4 ft from joint
22
41 to 60 1)4 in. Angle Connections, or 1)4 1)4 * 1)4 * H in. angles
in. Pocket or 1)4 in. Bar Slips 4 ft from joint
with 1)4 in. x Y in. bar rein
forcing on 7 ft 10 in. centers0
20
61 to 90
1 )4 in. Angle Connections, or 1 )4 IYxIYxY in.
in. Pocket or 1)4 in. Bar Slips diagonal angles, or
3 ft 9 in. maximum centers with 1Y x 1Y x Y in. angles
iyg x Y in. bar reinforcing
2 ft from joint
18 9J and up 2 in. Angle Connections or 1H in- 1J4* lYxYin.
Pocket or
in. Bar Slips 3 ft diagonal angles, or
9 in. maximum centers with 1% x 1)4 x 1)4 x )4 in. angles
in. bar reinforcing^
2 ft from joint -
For normal pressures and velocities (see Table 4) utilized in typical ventilating and air conditioning systems. Where special rigidity or stiffness is required, ducts should be constructed of metal two gages 'heavier. All uninsulated ducts 18 in. and larger should be cross-broken. Cross-breaking may be omitted on uninsulated ductstf two gages of heavier metal are used.
bOther joint connections of equivalent mechanical strength and air tightness may be used. Duct sections of 3 ft 9 in. may be used with bracing angles omitted, instead of 7 ft 10 In. lengths with * joints indicated. dDucts 91 in. and larger require special field study for hanging and supporting methods.
of the amount of turbulence produced. An inspection of the heater cop-: nections shown in Fig. 8 will readily show that uniform velocity through the heaterxannot be expected in the diagraih noted poor. When obstruc tions cannot be avoided, the duct area should never be decreased more than 10 per cent and then a streamlined collar should be used. Larger obstructions require an increase .in the duct size in order to maintain as nearly uniform velocity as possible. Branch take-offs should always be arranged to cut or slice into the air stream, in order to reduce as far as possible the losses in velocity head.
The recommended gages for sheet metal duct construction are given.in Table 6. Weights of sheet metal per square foot of surface for different gages are given in Table 7. The weights of various gages and the areas, for any length of run of rectangular sheet metal ducts may also be determined from Fig. 9. The bottom scale' represents the surii of the two sides-of the duct and the oblique lines give the length of run in .feet. Proceeding horizontally to the right from the intersection of vertical and oblique, lines on the chart, the area of the duct may be determined in the first vertical scale. The scales to the right give the weights of. the duct ruri for different gages of metal. In calculating the weights of duct, it is considered good practice to allow 20 per cent additional for weights of joints and bracings. Various weights and thicknesses of standard copper sheets will be found in Table 8.