BUUHIN NO. IC/FF-38R 2 (Revised August, 19761
Inspection & Maintenance Guide
Monsanto
TOWOLDMONOQ35735
' .1.1
a
j ;
TOMfe
SECTION A TRANSFORMER ASKARELS........................................... 1 I. Introduction...........................................................1
II. History of Trade Name Types.............................. 1
Table I - The Composition of
Trmsformtr Askarel* ...........................................2 III. Interchangeability ................................................2
IV. Tabic II -- Official Transformer Askaral
Shipping Specifications........................................ 3
V. Ordering Instructions ...........................................2 VI. Stability.................................................................. 2
VII. Precautions When Handling Drums, Tank Cars
and When Opening Transformers.........................2
A. Keep Dry During Handling ........................... 2
Table III - Handling and
Pumping Temperatures...................................4
B. Use Ordinary Personal Precautions ..............4
C. Precautions on Opening an
Askarel Transformer........................................ S
VIII.
Avoid Environmental Pollution........................... 5 1. Labeling Askarel Transformers......................6 2. Disposal of Liquid and Solid Wastes ........... 6
3. Conditioning of Naw or Recycled Askarel .8
4. Ttardown of Transformers for Repair or Scrap ........................................ 7
6. Transformer Disposal..................................... 7
IX. Expected Service Life...........................................7 X. General Characteristics of Transformer
Askarel Fluid.......................................................... 7
XI. Sampling Transformer Askarel Fluid ................ 8
XII. Evaluation of Askarel Received In New Equipment..........................................
XIII. DMcotrie Grcakdown Voltage Moisture Ratetlonship...........................................9
Table IV - Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in
Askarel end Mineral Oil.................. Table V - Approximate 8olubility of Water
9
In Transformer Askarel and Mineral Oil .... 10
XIV. Turbidity............................................................. 10 XV. Cheek Points for Maintaining
Askarel Insulation ....................
10
A. General Considerations................................. 10
B. Modern Sealing Prooaduras ......................... 11
C. Tha Older Seeling Arrangements................. 12
XVI. Periodic Phild Inspection end Whet CbeApokrts Mean ................................... 12
A. Visual Inspection........................................... 13
B. Dielectric Breakdown Voltage ....................13
XVII. Inspection Checklist........................................... 13 XVIII. Contamination In Tramformen..........................14
Table VI - Effect of Common insulation
Materials on Power Factor and Dielectric Strength..............................................14
Table Vtl - Effect of Common Insulation
Materials on Volume Resistivity
of Askarel............................................................. 14
XIX. ASTM Method for Investigating the Compatibility of Transformer Insulation
and Construction Materials in Adtarete............15
XX. Refining Adcerel for Re-Uaa.............................. 15 A. Filtering Through Dry Blotter Paper
to Remove Moisture end
Extraneous Particles...................................... 15
8
XXI. XXII.
Table VIII - Water Removal by Filtering Askarel Through e Paper Press .......................16
B. Disposal of Solid Wattes ..............................16 C. Solid Insulation Requiring Drying.............. 16 D. Earth Treatment for Maximum
Improvement of Power Factor end Volume Resistivity ......................................16
Table IX - Effect of Power Factor and Volume Resistivity .........................17
Cleaning Arced Transformers ........................... 17 Sampling Askarel ................................................17
SECTION B ASKAREL PILLED SWITCHES AND TERMINAL CHAMBERS ..................................... 19 I. Introduction........................................................19 II. Sources of Contamination................................ 19
III. Staling Switches and Tarmktal Chambars...20 IV. Aikaral Usad Under Mild Arcing Conditions . 20 V. Maintenance for Askaral FIBed Switches ... .20 VI. Askarel Under Excessive Temperature
or Fault Conditions .......................................... 21
SECTION C TOXICITY AND SAFE HANDLING..............................21
I. Inhalation.............................................................21 II. Skin Contact........................................................21
SECTION 0 ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO ................................22 Types of Analyses Available: ...........................................22
1) Routine Maintenance Check..................................... 22 2) Complete Analysis.....................................................22 3) Analysis After Earth Refinement ...........................22
SECTION E APPENDICES.....................................................................23
Appendix A - Askarel Stability and Composition of Arc Formed Gas...................................23
Appendix B - Solubility of Gaa in Treniformer Askerels .....................................................23
Appendix C - Effect of Temperature on Dielectric Breakdown Voltage of Askarel ...................23
Appendix O - Comparison of the Approximate Viscosity in Saybott Universal Seconds of Transformer Askerels and Mineral Oil...........................24
Appendix E - The Density of Inartaen 84201 KA 7336*9 and Transformer Pyranol A13B36-3..........................................................24
Appendix F - Thermal Conductivity Values of Transformer Pyranol A13B3B3................................24
Appendix G - Heat Capacity.......................................... 24 Appendix H - Coefficient of Expansion........................ 24 Appendix I - Fire Resistance.......................................... 24 Appendix J - Seels, Properties
and Procuramant ............................................................ 25 Apptndix K - Caution Label.......................................... 25
NOTICE: "Nothing oontalned herein Is to be construed
as a recommendation to use any product in conflict with any patent. MONSANTO MAKES NO WARRANTIES AS TO THE FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OF ANY PROOUCT REFERREO
TO, no guarantee of satisfactory results from reliance up on contained information or recommendations, and dis claims ail liability for any resulting loss or damage.''
HOMS 078660
I
f i t
i
>
1
>
TOWOLDMONOQ35736
^fficoiin A Transformer
Askarel
l. Introduction
The term "askarel" as defined by IEEE, AS1M and the National Electrical Code generally describes a broad class of fire resistant* synthetic chlorinated hydrocarbon insulating liquids widely used in transformers, reactors and accessory equipment operated at power frequencies. Askarels of various compositional types are in use. (For the
general properties and types see AS1M D-2283.) Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride, can contain varying amounts of combustible gases depending upon the askarel type.
This manual describes the operating characteristics of transformer askarel liquid Insulation as manufactured by Monsanto and how it differs from mineral oil. Appropriate handling and disposal procedures for both scrap askarel liquid and impregnated solid materials are given v,;- In accordance with the guidelines recommended by the American National Standards Institute.
The information is based on facts gathered by Monsanto over 40 years as a producer of askarel, plus knowledge gained from the experience of, transformer manufacturers and users. This guide outlines the maintenance required for askarel fluid in "modem" transformers and
Offers suggestions for scaling and maintaining askarel in old units Bv following this guide, wc believe users will obtain maximum service from askarel insulation with a reasonable minimum of maintenance if questions arise relating to the designing and building of tsensfom*:ts.
these should be referred to regular transformer suppliers.
Monsanto gratefully acknowledges the assistance, guidance and the contr ibutions of certain data by the following:
Edward L Raeb - General Electric Dr. T. K. Stoat - Westlnghouse Electric
, II. History of Trgde Name Typos .
"Askarel" is the generic name for the fire-resistant liquid insulation
and coolant first used by General Electric Company In 193? fur their Pyranol1.brand name fire-resistant transformers, Westinghousc Electric Corporation uses their brand name, tnertecn.2
Whatever the trademarked brand, the askarel contains chlorinated biphenyl - one of tire best liquid insulations developed by science, this inert material Is chemically stable, fire-resistant, heat stable, non-corrosive, and has high dielectric strength under the operating conditions encountered in transformers.
In addition to manufacturing Arocloc* chlorinated biphenyl ,
Monsanto also mixes this dielectric fluid with chlorobenzenes to
l produce the presently used Inertecrt and Pyranol blends describee! in
Tabic I.
,
r "NOTE: Materials designated 'lira resistant' generally are more difficult to Ignite, or once ignited, burn at e slower rate than corresponding conventional mateiials. This terns dods not mean that tire resilient materials wilt not bum. However, when properly used, Monsanto's fir* resistant ASKAREL FlUlOS ara useful In helping cuitomers meet their fire Safety requirements."
^trademark of General Electric Company *1radenietk of Westinghousc Electric Corporation
Registered trademark of Monsanto Company
HONS 078661
TOWOLDMONOQ35737
.`
/ , Table I, The Composition of Typical Transformer Askarelt
,
. Method AS1MD2283 .
,
Jypc D
.Type E
' Jypc G .
Trade Names '
' Inerteen 7030 ,
Inertecn 100-42
Pyrenol A130303
Ingredients 1% by wt.)
' . . .y
.
AroCloi12M, , chlorinated biphenyl
<64% chlorine by weight)
Aioclor 1242, . ' ' chloilnatcd blphonyl <42% chlorine by weight)
-'
70 . / ,
.
'' . . t~
' ,
1 ' ... .
< 60
'
'100 .'V .
'
Trichlorobcnrene
30
, 4<J
Htehoxyprdpene oxide * . / .
-.
scavenger..
6.18tpQ.?? Q.16to02?
'y ,- . .
Diopoxidc scavenger ' :
; 0.116 to 0-136
ASIM Method 0-2283, titled "Chlor/netcd Aromatic Hydrocarbons iAsktrek) for Transformers", *lsp lists Ihf composition; of all
, uansfomrcr.'askarelsusc'd at various time* sln6e )937. ' >/ ;
Mcmst'hlo mfliudacturei slmilai transformer esksrel fluids in England
wheje tjic track: namc PyVoclot ,1sus$d. . . . ;.
\.
: '/, /
' . . ' '. ; -
;
HI. loteichangeability . r
'
In grncial gll transformer asfc,arls are interchangeably. However, it Is
suggested that the transformer oUnuftrctyrer be consulted prior to
mixing In significant proportionsor' total substitution. s ,y; -
IV. TrantfonKr Askar el Specifications
: ! ' .
. Specifications for thf .three. modern transformer askaral fluids are shown Jn.TeWs II.' ' '>J'y . y y V.-, / y' y.
V. Ordering Instruction* y-
^
MonsShto** edrront policy fs tos?lj askaral transformer nuidi only to ,
liantformcr mfcnufeclurielrs.''Others'interested. Inthese fluids should
contact the iWnOfartWers <jf askaiel transformers arid not Monsanto.,
Inc trarrsfurmcr nemf pf^te indicates tlie transfyrmer maker and
(Usually gives'sufficient datrt to Identify the specific askaral fluids used.
VI. Contamination . .'yy ` 7y ,y
V.
..
Askarcl Inflation must, ncvfcr be' rhlxecf ,with' rpliieral oil. Ovortwo
percent Of mineral of) by volume In iskarel begins to lowor |t$ frre
resistance.
,y '
` . V 1 . .r'\ ] J'.
In modern transformers, the principal "enemy" of askaral 'is
Contamination by watch Keeping ,askaral water frac wtH insure
longtime Service. .
..V
'.
Askaral Is heavier than, watch <f Water gets Into ^skaiel Insulation, only .
a tiny amount (approximately 126 ppn) dissolves - the Vest floats On
top. Askaral.is Very Insoluble In water, only about 200 parts per billidh
of a^karel dissolve Ip WBtcr^it noihial tertrperjstijres-1
, ' '
VH. PrOGtritliphi^lliCh Handling Orun)t, *lhk Cpr'e, fvd When
Opening transformers ;, * , .
. ` \;
The following are significant precautions: '
:.
,v
A. Keep Dry Dyfing Handling:
, ,(
..
' In hendling, storing, sampling and Instvjcting askarel - arid.In
Tat* It
I
- $ow~nej>ion Pnwatia1
r . . ' ;
. - ./
GeneralElactrieCo. ' - Tramfomar . . Pyrenot A1383B-3 ; ASTV 02283 Type G
. ' . WoftfenjAoMe . Transformer
Inerteen 7(V30* ASTM 02283 T-ypoO
.
Westing*muse transformer
'nerteen 10642* ASTV 02283 Tyne E
cohx,a**a
,
-.. .
,
- 150 max. -
;Coryfi-ton '' " - - ' - '. ;
-; ^
- _-
"Watecconte^-iobm'lASTV tT'SGS-SO) .. > / .
. Ae**v. m?KOWa'ASTV 9974-55>
'C
...
,> de*--1
.
- 30 max.' :
. 9.0*4 max. ' \ .
^i`ect'-cStrenQh, ^S'C^O;1 >.-<o
.: ` .-
35 KV^min;
\ 'ASTW 0877^9)'
. - / : *
Dielectric Constant^100*C,69 wz
. ' ' : v - .^to-4.6 - \
.. (ASTV 992A49>
v ",
Volume Resistvtv, lOOKr,_
500-vo'ts DC 0.' inch gaar >0,oh^crT''. .*
'TO ;'
' - {ASTV 0-^69}
-;
*
_ inoroanicchkxides, opm (ASTV-Di82i. and 'V'
O.'O ma*.
^'
- G.E.Verhod E4C4I9)
P`ract.v9 iK^ 2S,C<ASrV O,807> ,
i.S^O.to *;6'20
v< Visco^t^stf^j8^\ASTVV^88-5&}^ **./ .- y.'.'ArM'r ^to.48^ ^ , 1 . ,
. Saybo1'. ijniywrg^i Seconds *
'r
iP0ur PointC^AST,V.O-97-$7 ^
v .
' -38 Of 'ower
Soec^ic^avty 25/15-VC.tASTV 0*8*0)
. ^'
l.A95to^tO
, oornt {ASTV Q92> ra
Delation range/A$TM~020-56i corrected
* : * _: ' None *o bot'tno ' - - tst droo 200*Crruit.
. *or. stem and barometric orsr . ;
:r
40%max.5eOw27CrC
V-; < . .
90^ 379 to 394
'
- ',
'50 max^ Clear .. .
30 max. ' 0.01* nx. 35 KV, min. .
4^ to 45
; .
.
50 max. C'ear
' 35 max. 0.0' max. 35 KV, min.
4.7 to 4.9
'00
' 100 . ..
' O.iOmax.
0.05 max.
'.6153 to 1.5173 -.- ., *56 toY^_
- - 1.6240 to 1.6260 , . . . 82 to 92 v . .
-30or lower -
t.518 to 1.528 - ftonetoboilinQ
rst drop 20C|BC m<n.
35% below 270^ 90% 379 to 394
`
~
-17 or lower
: i.38i.to 1.392 , ' . f/one To boi'ino -
10%325-Cmtn*.
* 90%.360 max.
cv*ed c^orjne' -- .
- - ' ; .
56.4 -0.5% '
' - . -- 555% min.
43 0.5%'
CorroSion Test
'; '
. Color. APA ' .
.. -
' - .AcrdtY,mQ KO^'g - ' - ' - -
, ,ooraB,>tc.c`*iondes oom '.
>: Condition '. J
'
Scavenger content -
Typical IVopertses2 .
Coe<`*C`er`'. o* "r V"r,a' Exoansion rASTV 0'9C3'.cm2/cm?/C
A^c *ormed oases
hMestin^iouM wt their prhwt* numtw lAfrmn 5*20' KA `ot i.nnw 7030 and their private 'i/nOr Inarteen V*20^CV 'or 'neneen 'QO-*2
'; '
"'
' l A^ter heating
alumjrmm *ot 6 hrs. at20CXto 220*0, tV atyminum must not be corroded
o e!he< v*sua* or
inspection and t+iea^tare1 s'wu'd meet the-fo,towing sDeci*c3Tons:
200 max. .. . . ,
200 max.
2<X) max.
^ - -0.9*4 max. * -
0.0'4 max.
'
0.0* max.. '
- ` . ,0.15 max. .
".
- 2.0 max.
- . 0.'5max. .
0.mto0.*3B%
O.'s'toMW
0.'8^o0J2%
Oieooxde
ohenoxvorooene oxide
Dhenoxyorooene oxide
. ' 0.0007
0.0007
0.00068
Asfcareh o' various comoosmonal tyon arc ined. Under aremg condihorts the aases oroducad. while consisting
oredonynanfv o' non-combustib'e 'hdrogen c^'oride. can include varying amounts o' combvst*ble gases daoending uoon ^e asha'e* type. Insulation systems incorporating these asfcere's and ce"uios< x other organic marena's moy. when arced, oroduce gaseous mixtures which are moderately hamma&lc. As a orecaunon, such gases should be removed *rom the askare< by bubbling dry nitrogen >hrou^> the aAarel and 'lushing the ^s soace w>tn dry rnttugeti
Or'ora *r*y wx* n c*r*o*TM*ti on me aooeratus
Thtm otamiii*! am * ia* w*es ncHietiont on*v t th* axtent that they coincide with Monawto t oubiidnd sMct*icat>om.
*THi
and it net jya a'Und fw * wnetas. Write u* <or complata seta* weerflcatiofw or Askar* n*dt.
MOMS 078663
TOWOLDMONOQ35739
operating askarel transformers ^"take every precaution to guard
thp askarel Insulation from expdsure, to high Wmidlty and.
molsUifo contamination. Keep 5 or $6 gallon drums df askarel
dry; lay storod drums on their sides with the bung at the highest
point from floor to keep water off the drum head (which can be
>u6ked Into the askarol by the drum "breathing'*). This precaution
Is not necessary when drums are stored Indoors,'which U the
prefened place fo> storage.
/.
,,
To avoid leakage the, drums used' for1 askarel are of heavy construction. Sixteen gauge metal is used, with special rim seal and bung construction. The drums should be drained as'completely as possible and then flushed twice with kerosene type solvent to remove all of tire askerel. Accumulated liquids and washings' should be oollected and should be Incinerated at high
temperatures, e.g., about 2000"?, to destroy the polychlorinated biphenyls (PCBs). Sec Section A, VIII, , ... 1
Tank cars used to'traniporl askarol* are In exclusive service and
. not used interchangeably for other products. All cars must be
. unloaded through tire top (dome fitting} either by pumping or
with controlled pressure using dry air or dry nitrogen. If nitrogen
hat'been used for unloading It Is necessary to advise the shipper so
, that when the gar returns the nitrogen can be replaced with (fry air
before any one may enter the.car. If the car J* to be unloaded by
pumpiiH) It will be necessary to use a dryer1 on tire air intake line to
remove moisture. . .
'\
.All tank.cars are fitted with steam coils', which are available for uhtotKbng under extreme low temperature conditions.
Convenient handling and pumping temperatures die given In
Table fl|.
;
B. U?6 Ordinary Personal Precautions: o v.: ,
. . *,
Tra,hsfor`n\el'isj|<ai ei ha* tK'cn made, handled, and used for over 40
years. It c4h be handled safely with Ncomnrcqded precautions. If -accidentally spilled on hands./tO.scrloos skin iriftotioii.wijl occur'.'
.However, liquid askerel has a solvent action (similar to paint
'
' ./ r. \y '
,r'' v.
- >. v`;
Tabic III .. - *
`
/
Handling and Pumping Temperatures ' . ' .
,
-V' :/. ' 1 ., -
' v /
k
; A Product .
Dnlokding, ' .
Handling ijitd '
' Puntping
...
\Teo\pc;rature*C " . >...
. .
'
,'* y*
' Pyranof A13e30-3`.
< Inerteci) 7P-30 Incrteor'i t0CM2
' S& -.6b ' . .
;
W-6& ,36 *76
';. ;
' thinner) on the fal> aqd oils of the $k|o and prolonged contact
"' may lead to diylng and chapping of tl^ sk.lrt. .
*;
, to eeso of contact, wash the skin with jbap rind water; remove and
,'destroy saturated clpthing; Clean up Spllfs wlth rags, sawdust and
absorbent clay. Scfliegato tl*e$<f (Vshts for proper disposal. (Sec
' page 6, "Disposal of Liquid and .Solid Wattes11*.) tye contact may'
' , result in painful Irritation bqt rf^pOihmniml' damage to tissues. If
askarel gHs In the ayes, flush with, large amounts of water., As with'
. all eye first aid, ro'fct to a physician. To relieve Irritation, physl-
clans have used an opthelqilc anesthetic solution s well ai opthal-
/mlccorti$<Hjv a^latv Solution. ' A .
('
Infrequent..ixpoHire to Iskarol .vapors will not cause III effects. Howcvpr, prolonged fexposutc to f)ioh vapor coPcentraiioriS should
be ivoldcd. H hot ajskartrl m0st.be handled in a closed or confined area, provide the area'with mechanical exhaust ventilation - or
4
i
MOSS 078664
TOWOLDMONOQ35740
wear an organic cartridge respirator approved by the U.S. Bureau of Mines.
C. Precautions On Opening an Askare! Transfor mer:
Askarels of various compositional types are used. Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride, can yield varying amounts of combustible gases depending upon the askare! type.
Insulation systems incorporating these askarels and cellulose or other organic materials may. when arced, produce gaseous mixtures which ere moderately flammable. As a precaution, such gases should bo removed from the eskarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus.
The American Institute of Electrical and Electronic Engineers Guide IEEE Std. 76*1974 gives more detailed instructions and guidance "For Acceptance and Maintenance of Transformer Askare/ in equip
ment". This guide is published by the Institute of Electrical & Elec tronics Engineers, Inc., 345 East 47th Streot, New York, Now York 10017. We recommend that users of askarel transformers refer to this IEEE document.
VIII. Avoid Environmental Pollution Transformer askarels contain polychlorinated biphenyls (PCBs) which have been used in the United States and elsewhere over the past 40 years for many Industrial and consumer applications. Ouring the past sevaral years avidenca has accumulated to indicate that PCBs are widely dispersed throughout the environment and that they can have adverse ecological and toxicological affects.
The United States Government's Interdepartmental Task Fore* on PC8s, Com-72-10419, |n jhetr March 20, 1972 report titled, "Polychlorinated $lpheny/s ,knd the Environment", recommended restricting PCBs to uf'e in capacitors end transformers.
This report it distributed by the National Technical Information Service, U.S. Department of Commerce, Springfield, Virginia 22151.
A document titled, "Guidelines for Handling end Disposal of Capacitor
end Transformer Grade Askarels. Containing Polychlorinated
8iphenyh", has been prepared and fi available from the American
National Standards .Institute, Committee C107, 1430 Broadway, New
York, New York 10018. Document number is ANSI C107.1-1974.
(This guideline Is being revised during 1$?6. The new edition should
be ayillable 1076/77). ;
.
The scope, objectives and the composition of this committee are;
;'
ANSI Committee fcl07
; Scope: '
'
1 !; t
1
Procedures arfd guides for'safe use, maintenance and disposal of
. askarel and askerel-ioaked materials used In electrical equipment.
Objectives:
1,
1. Source of technical information and advice for Federal,
State, local authorities and all others concerned.
2. Encourage development of suitable dispose! facilities and
keep all concerned informed.
3. Serve as the advisory group for United States participation in International organizations: CEE, IEC, CIGRE.
Composition: Organizations active in or represented by this ANSI committee include: National Electrical Manufacturers Association. Electronic
' Industries Association, Institute of Electrical and Electronic Engineers, American Society for Testing and Materials; Electric
Light and Power Association; Certified Ballast Manufacturers Association; Environmental Protection Agency; Office of Environmental Affairs; Genera! Services Administration. National
HONS 078665
:o)
TOWOLDMONOQ35741
Bureau of Standards; Department of t the Army; f^ural
.
E lecti Ificatlon Administration; Division' of Environmental . / , '
Research, TVA; American Public Power Association, Water : '
Pollution Control federation; Pood and Orug Administration; _
National Fire Protection Association; Underwriters'Latxrratorles;
ar*d several sections of the U.S. Department of Interior. '
'. .
The following aic pertinent excerpts taken front die ANSI Guidelines
for eskaiel transformers:
:
''
1. L APT LING ASKARE L 7 HANSf QRMERS (Pg. 16)
. 4.2 2 1 New Transformers. All new transformers thet
contain PCBs S/tall have t label of adequate durability,
permanently and prominently attached to the tank by tire,
manufacturer, given adequate warning and instructions. A
suggested lal>cl includes tire following: ..
-
CApHON: The inflating liquid in this transformer 1
contains polychlorinated biphenyls (PCBs). Cpre should be
taken to prevent envy Into tire environment. In case of
malfunction pr'teaks, consult the instruction manual or
the manufacturer.
.. '* ,
.
4.2 27 ln$crvlce Transformer*. The trensformbrmenu-
lecturer should make available suitaNc labels with a similar
wafnlhg as shown in 4.7.2- l for use on testing transfofmeii.
2 DISPOSAL OF LIOUIO AND SOLID WASTES (Pg. 16)
.
, ,4J.6,5.1 General, Dist>ofal of askarefs andaskarjl foaked
'*'
e `hialcrlais should bf accomplished by means In which there Is ,
. no significant release of askarel to the environment.. At ' -
. prisentf jdlq^osaf It accomplished by carefully controlled
-
/ Incineration of, liquids and soaked software, and by eon- :
trolled landfill burial of apparaluyand other hardware from ' v
: wfiiehaskarelhQS been previously drained and washed, - ' 'Present knowledge Indlcaty that proper incineration '.
/
s Jwti Involve e tiiHaNc ba/ahce bet^etn dwell time and :
4 temperature in die ihcindraifotiPlus bkygcit availability and,
;
, finallysuitable .scrubbers fo remoyC tfie HCI d>at will be
_ formed; fpr, example, 2tcc6nd dvi(ell (in# bl' 700(FF and
z : 3% excess' okyden Ip stack gas, pf f.Sset ond dwell itpie at ' */>.; O'
.* ; ' 2>00f and 2%pkygor> in stack gas.
,:
: l:.
, thgse facilities Should meet the applicable requirements , : ' 1
" of state lh\addch. they are located add sitoultf control . V >'
affluents Wftlrifl the limits s0( forth it) this standard * <' `
>
. , Controlledlandfilipt dccp-wpUdts/>osalcan beOted where. f:
permitted by fadtvaf, state, bndlofaf regulations.
. . ifhe ANSI Gul^c lists tire, ideations of facilities Viatednfornt. `>
\ ysfltli the above .retpflrdnteiitV Mpnianto'has $ucii r\ Inclrv '
. ; arator it the W, G. KrOtrinlnch P)ant.Dopa<tnient 63)f/
. , ; Eaugrt, Illinois 6??01,.whef<, ar(en'n*-mems can' 6c mad$
' < scrap askarel liquid disposal'fpr | Modest fee. For disposil :
' it solid scrap controlled y land-fill can be us(ro wtiere' -
,. permitted by Federal, Sta'tcffid local regulations.
- v. !', .
3. CONDITIONING OF NFW Oft .RCCYCLEl) askarel r
' *' (Pg. 16) ;:/i
^ ' .
:/
4.21.3.1. '.Askarel Conditioning Fquipmcnt. Thtj tondi- '!i
. tinning unit s/rould be located either in the storage tapk areg
gr in tltc main transfornter .fyaruifactoring area fpf filling
with askarel. .
' ..
- . . 4.2 1,3.2 Fuller's Tarifi^Ct'pdftionjng of new askarel or 'jUrr*-
\ recycled askarel requires, fuller's earth treatment. The s/>cnt V . fuller's ebrth/n cartridges d(, pegs, when replaced, should be . u
, allowed to drain thoroughly bycr drip pans to rernove as < :
much liquid askarel as posable. The cartridge units of steel
mesh .copisituctlon should be placed In the "SlEFt. CON
-
TAMINAlkO WUH ASKAPf L" container for disposition. '
; Ooth pegs filled with fuller's eprth should bd placed in'the.
"SCRAP BURNABL ASKARSL WASH'! container for ' . - ,disposition, ,
.
' 1
Z1 -
>4 .
;
'
.
TOWOLDMONOQ35742
I.f
4. UARDOWN OF TRANSFORMERS FOR REPAIR OR SCRAP <Pa. 16) 4.2 1.4.1 Drain all askare! from the unit either into a holding tank Or reuse or Intv the dn/m fettled "SCRAP ASKARIL" for diwosition, and then allow sufficient time for all of the askare! to chain from the core amt co/v 4.2.14.2 Remove the core and coil awmbly from the
transformer. Sufficient absorbent material should be pf# ed on the floor to absorb any askare! fluid that StUl drips from the transformer. 4.2.1.4.3 Place all nuttc-rials In the approfiriah salvage Containers during the dismantling for later disposition. 4.2.1.4.4 AH u$$cf materials. Including rags, sawdust, tape, ate. regardless of quantity, shall be put lnu> the appropriate containers for di$/>o$ition.
6. TRANSFORMER DISPOSAL (Pg. 17) 4.2.3.6 7he ultimate disi>os*l of an ask are! filled tramformer may be accornp/ishcdin either of two ways
\ (t) Conrp/eti .drainage and dismantling with the proper drs/msal of tfre askare/ and askare/soaked coniponcnts as desc ribed in 4.1.6. (21 Dfspositicft of atkarel transformer* by means of junk or Scrap dealers. This should be avoided tinlcy< a transformer Is first drained, followed by soaking the inmrlor with a
. suitable solvent. Accumulated liquids and washings arc tv be disposed of as described in 4.1.6
IX. Expected pr vice Life
Manufacturers Indicate that properly designed and Installed askaiel transformers arc exjrcctcd to give' trouble free service for at least 30 years. Since.their introduction In 193?, the manufacture!* report . finding the' overall.failure rate to be less than 0 5% for all units under test grtd tet vice .Conditions. The Edison Eleetric Institute's ret>ort M9b6 1958) on their'member utilities publishes the failure rale fur askare] transformers as 0.13 per hundred batiks p*n year.
Mr. Frank M, Ottrk, Who Invented transformer ^Karels at the General `Electric. Company in the early 1930. made the highly pcitincnt comment based on hij many yeeis of experience with G.f Pyianol ,'ioskare[ type) tiadsfoimeis that -
"'Me important thing Is to keep them dry - otherwise leave them a/or/d"* '
year* when welding shut rather than gasketing became the mam method of sealing t^karel .transformers. These units ae sold with the' undmtandmg that the liquid it in a normally hermetically closed , system. ' ' . ' '
X. General ChfiiaUerlslicfr of Transformer Askare! Fluid
Appreciation of the following clira(teiistics, as given In the If El Gutyc, leech. to understanding the fcajc-oi for selecting dielectric
breakdown Voltage end moisture as the prime practical test'- to judg>tlu? Quality ;of .transformer a$ke<cl fluid. Also, dm- to those characteristics the power factor of,transformer askare! will be normally rrnch higher than tiiO corresponding values for mineral oil.
In comparison to mineral insulating oil, e<kiirtl is a relatively polar
material; be., Its molecules are dipoles, tree to rotate around their axes
and responsive to orioniaiion by elotnlcal foicc*. Askarel also exhibits
a much higher diclcculc Constant and capi'dlence than Insulating oil,
and these differences must be kept in mind wji<pi inter pi cling etecl< icel
test data.
'
Because it Is relatively polar, and possesses higli solvency power, asVarel is much more electrically sensitive than mineral oil to traces of extraneous solyble,polai materials, and consequently the choice of
MCNS 07466?
1
TOWOLDMONOQ35743
constructional mater Jah destined for use in askarel Is very Critical. This
sensitivity l* reflected In tlc power lector end resistivity (specific
resistance) of the askarel.
.
ft is Important to note that, with the exception of water, the dielectric
breakdown voltage of askarel is not generally adversely affected by
many of the soluble polar materials to which its power factor and
resistivity (specific resistance) arc so sensitive. In fact, the dielcctilc
breakdown voltage of askarel is somewhat greater than that of
Insulating oil. Therefore, the values assigned these dielectric fluids In
newly supplied transformers are 30 KV min. and 26 KV min.,
respectively.
-
,
As with Insulating oil, askercl must be kept dry. It can pick up moisture from exposure to humid atmosphero. Under similar conditions of exposure, askaret can pick up nearly twice as much moisture when measured on a parts per million weight basis.
Xi. Sampling Transfomicr Askare! fluid
The following precautions about sampling are quoted from the IEEC
Guide.
'
"Representative samples, whether of the compete contents or only
parts thereof, are extremely important from' the standpoint of
evaluation of the duality of the product sampled. Obviously careless
sampling procedure or contamination in the sampling equipment will
result In < Sample that is not truly representative. This generally leads to
erroneous conclusions concerning quality and incurs loss of time,
effort, end expense involved in securing, transporting, and testing the
sample. It Is strongly recommended that all Of the procedures en<J
precautions outlined in the.latest revision of ASTM D923 (Sampling
tlcruicaUmuletlng Liquids) b? followed.
'
"Because of the high sixclfic gravity (relative density) Of askarel
(greater than 1), water end some other Impurities are most likely to be
foOnd at 6r near the surface. The top sample, therefore, Is considered to
. feprcseniibc worst, condition."
.
.
. XI). EvaluMion of A*torl Received In New Equipment
Sornc utrfrt of askarel equipment find It desirable to make "as received
tests" on ail equipment! It Is quite common to use thedielectric
breakdown voltage test end visual Vppcauince as the most significant
tests. If suitable equipment end trained personnel are available
additional information may be obtained horn the power factor, color,
and moisture content tests.
^ . ..,
In sampling askarel contained in'apparatus extreme care must be
xercisrd In order to obtain a representative sample. ASTM Method
0 923 should be followed.
\.
.
New equipment With askarel exhibiting the following characteristics is
considered acceptable!
, .' ,
1
Dielectric Breakdown
Voltage ; Color ,
.
Condition Visual .
Wafer Content
,
Power Factoi at 2b" C
30 KV min. 300 max! (Stiaw color)
Clear 3b ppm max.*4
ASTM Methods
D87/ 0 2)29 D 1702 D 1633 0 924,0 160
*The power factor of askarel taken from new transformers, . reactors and accessory eqirfpnicnt cart reflect the presence of
moisture, dissolved polar compounds, or other contaminants and may vsiy with the type of equipment front which the sample was taken due to the different ratios of liquld-to solid insulation and to the high solvency poWci of the askarel. Given an acceptable water content and dielectric breakdown voltage of the askarel as Indicated above, a high phwer factor seldom impairs the serviceability of the askarel within rather broad limits and is
indicative of the dcgicc of extraneous soluble polar materials . present.
Recognizing the possibility of a wide range of power factor being recorded for askarel In new equipment, it is difficult to establish a single limit which would be acceptable to both suppliers and users for ali applications. However, as a broad guide, power factors up to about 10% at ?GCand 60 cycles pci second (hertz) do not in general indicate any abnormal contamination providing that the Other criteria (water content, dielectric breakdown voltage, etc.) re met. Much higher power factors may Indicate axcessivc contamination or the misapplication of the solid materials used in manufacture in contact with the askaret and should be investigated.
XIII. Dieloctiic Breakdown Voltage - Moisture Relationship The dielectric breakdown voltage of askaiel is highly sensitive to excess moisture; not sensitive to ordinary dissolved polar materials. While the dielectric breakdown voltage can also be lowered by severe arcing, askarel turns noticeably black or has particles of sooty carbon floating in it If arcing has occurred. Then the transformer should be repaired and the askarel replaced.
If the. dielectric breakdown voltage is checked periodically and decreases significantly - this Indicates moisture pick-up. arcing, or both. When the dielectric breakdown voltage has dropped to 26 KV or less, an analysis for water is necessary. If water is found In excess of 40 ppm it room temperature. Its source should be located and corrections made.
When tire moisture content approaches 126 ppm (salutation level at room temperature), the dielectric breakdown voltage of askarel drops below the value required for efficient Insulating. The moisture- content should not be allowed to rise over 70 ppm. saniplcd at operating .temperature. If the moisture content is found to be in a satisfactory range and the dielectric breakdown voltage Is low, the transformer manufacturer should be consulted.
Table IV shows the relationship of dielectric breakdown voltage vs. moisture apd Table V indicates the approximate water solubility limits In askarel and mineral oil.
Tal-le IV
Relation of Piclecbic Breakdown Voltage to Amount of Disvlvcd Watrr In Askarel and Minora! Oil
JNatei Content (f*PM)
Breakdown Voltage (ASIM D67/I
Askarel
Mineral Oil
0 20 . ' 40 60 ' 80
no
. -
,
70 KV 6b 47
40 38 10
60 KV 39 30 2C 2?
6
Rons 07866$
TOWOLDMONOQ35745
r
i,
30 i 20
10 0 to 20
30 40
Table V
Approximate Solubility of Water in T rarisforiMCr
Askar el end Mineral Oil
1
Amount of Water (PPM) Dissolved
y.
Askerel
- Mineral Oil
2? -4
- 14 3? 60
68 8C 104
,
8 16 28
4.1 66 94
128 170'
,
8 10 13 20 33
68. 8D 130
XIV. Turbidity
'J
... may bo the visual sign of undissolvcd water, or may Indicate dirt.
Cloudiness may also result front cold precipitation of tin tetraphenyi
"scavenger" tlial was ysed in the eailicr Pyranol transformers. This
scavenger begins to come out 6f solution around tb'f above zero. To
raclissotvc It requires heating to 150-2007 end agltatiorl.
. ';
High dielectric breakdown voltage will quickly indicate that any
r!:. turbidity present Is not moisture; diet the insulating efficiency 6f the askerci is still excellent. However, if the dielectric strength Is below 2$
. KV, moisture should be determined, using the Karl Fischer method
(AS1M D1633 60).
.
7/rf diplcclt/c briokdQwn yv/tagf fast for askaref scivtis primarily as ah :
Indlcatot for moisture. It h by Ur the niOitjntportatH maintenance Wit
for frensfor/hcr eskaref. Jr-
..
, t; .
1 XV. Cheek ^olnta for Molnlhinlnji Askarel lnsLtl8\lpu '.*
. A. General Considerations: .
` .v
.'
Modem Isker'e) transformers with welded construction or silicone -
or Vitori* gaskets (hand hole-cover, switch aiod terminal
compai(merit covers) and with .properly constructed bushings ,
require little maintenance. With proicily' constructed trah$; 1
formers, ennuat or semi-annual Visual inspfcclion and dielcfclirc, ,
breakdown voltage tost of the iskercl fluid should suffice for . ` -
routine maintenance checking ovei mpnY yems of service. -
However, mepy eskarcl units ywf* insl*l(cd jn the aptly 193ps - `
before the development of s6me of the better modern gasketihg
-
. materials and before .Improved deigns were develoKd for sealing '
out ntolsiure. Sucli early units shoidd bt;, and can b<`, niodVhbed.
...
Leaky or deterioraled gaskets should be replaced. If the askaiCI '
has become cotHtirnlhatcd, It should be hicoixlitloned. At the seme
time, a gencial cleafi up of the unit and possible rcfinishltrg may be
desirable.
'1
H It Is nol convenient to take on bid trqhsformei out of service for
general repairs, le?ky grukets can be scaled ieiuj>o*aiily by painting
over the leaky irejr with epoxy cement. `` `
'
A survey of users Indicates a good numb*1' of eaily-bull.t askargl
transformers (over 20 years old) are kepi In continuous service In
Critical Installations, by She ' following steps (instead of
modernr/aUon).
.
'.
. .
Tire Operating units are equipped with compound pressure gauges ,fot readhsg pressure #Uvc and bcipw atmospheric. Positive
m*k ot fcl. Dufoiil DcNtriiOUfs & Company, Inc.
I.
piessurt Is maintained on tin shell by introducing nitrogen at 2 to 3 pounds above atmosphere. Regular workmen in the area daily record the temperature and pi assure. If a suddr n pressure drop is noted more nltrogr n Is introduced and the gaskets arc checked for
leaks with scrap solution, leaks are scaled by applying tpoxy cement.
' Mods-'n Sealing Procedures:
Transformer purchasers should specify the following modem
techniques fqr scaling: ' .
1. Wcldlrsg Construction; Covers, radiaku ennneedorrs, switch
` and teiftiInal housing-, Instrument connections, etc. should
be welded. '
.
'
2. _ Boshing Connections: A number of bushing*, have been
. developed to obtain a propn seal fo the electrical - connection through tire tank wall. They arc classified as
follows;
t) Welded Type - (Bushing (Ungc welded to tank wait)
a. Cast resin bushing wii|> a molded teal to tire
' ; bushing stud and exiemat stainless steel or copier
, .. flanges.
b. Rolled flange bushing with the metal to porcelain
seal at th^; cdp arni flangi'made by bring rolled into
' ; . grooves in the porttlnin over silicone ruhl-cr rings.
The seal between the cap and sted is made by
."
welding. .
,
. c. Porcelain or glass bushing-, with met#! to glass or
'J
metal u> porcelain see Is
2) Boiled Type (Bolted to tank wall) . . a. Cast resin bushings with either c*sl or metal flang<-s
. containing rCws<\! go'-l-et grooves
; b Porcelain or glass buShirigs with flanges containing
. recessed grooves or gaskrt stop.
The gaskets may be either of ractvoula' o< circular cro>s section, usually >4 inch thick. Bushings with reCv-pd grooves arC suitable
, to UM- With Ct"k, coik hi trile fifhhi cumin nations or nitrile rubier as well a< gasket materials such as silicone or Viinn
3. Small Sue Connections. When not txwvblt to weld, snull
, s|?*' Conheebon seals stiould b nn 'f> with Flexita'tic*
. . stainless Stil l ring., Ihc siMiK*-' must t* mat hined and
, parallel. Ihc fillet bclWCUi'the sti-r-l )ai<iinatini>s of the '.Flcxitallic ring should be either silicone-or Vitun.
4. Caskeis for Hand--Mole Covers: Mmim design s^-cifrcd
. silicone g.id-cts. Su<h g-v.keb nU'-t t* retained Inagroovc.
The groove prtfeiably Is hiarhinr.i into the Hang' or covet.
- However, it can also be formal by Wetting concentric steel
, Strips to the flange or the rover. Gem r utly the gasket:, should
bo 5/1C t(> ]/? in. thick for cove's, dip. ..ding on the depth ' of the groove or stop A uOlo.iyulai du'S serbon is usually
;';-UStd.
..
Ihc silicone hiiUtial h(.ii'-J be Owv Co*nitig No. 50
*$il,v4ic* * or e<|U'vaicl>i. This is a low comprc >-;om sot
. mstci ial. For best Sivliirg 20
compression is
recommended, with ample cliota'io in tl groove or stop to
allow for this compression.
No Cement K required. With re;-Hmil.lt Ca'e the g,-i>.Sct is . >' removable without damiiu' and is icuq-ahli
. Silastic 50 is slightly swelled by a'-kan I which contributes to the tightness pf tin.- twol H is not d> t. liorait.l by askarel fluid or vapors It resists weathering ami it is thermally stable and
Tffldcmfl'ir of f leaitnllic Gasket Comp-my "1ract#rttrk of Dow Contlriy
HONS 078671
nn
TOWOLDMONOQ35747
flexible at all operating temperatures. It is an Excellent moisture barrier.
NOT t: Oow Corning, Midland, Michigan will supply a list of
Silastic 60 gasket fabricators to alt transformer
manufacturers or users. They will also furnish technical
data. Sec Appendix J: Seals, Properties and
Procurements.
^
The Older Sealing Arrangements:
/
.
The older type gaskets consist of either oork or cork-nib He rubber
combinations or straight nitrile rubber.
1. Cork-Nitrite Combinations:' Covers for the main tank,
hand-holes, switch and terminal chambers, relief diaphrams,
etc., are held in place by studs welded to the flange or by
bolts. The gaskets are cut with openings and pieced over tire
bolts. Often Shellac (Westinghouse Style No. If60419, or
General Electric Company's Glyplal* 1276) Is used to
cenicnl the ootk to the flanges.
.
1 ho following Is recommended for sealing with the cork
nitrile rubber combinations;
'
a
Use Armstrong NC-757 cork-nittlie malt-rial or equivalent.
The gasket can be cut front a single sheet or by scArfing strips
of tire material. A convenient method foi joining strips is to
make a Keystone Type Joint. For this purpose, Westinghousc,
Sharon, Pennsylvania, offers their gasket cutter Style No. 326
6614 GOf, (abotnSIb).
`
/
The joints - and also the gasket - should be cemented to the flange, using one of the above cements. Excess oemenl should not be allowed to reach the Interior of tire transformer.-
After Installation md bolting, the outside edge of the gflskel
Should be coAh-d thoroughly with ejsoxy cement to Increaio
wCathcr resistance.
1
:
This epoxy cement is a paste to which a curing catalyst is
added immediately before use. Typical are: ;
a. . Epoxy Patch Kit al-C '
. ,'
- Hysol Corporation, Olean,NoW York
. b. Scotchtast* * Resin #4
;
"... '
.Minnesota Minlrsg & Manufacturing Company
.
St. Payt, Minnesota
' .' .
c. Adhesive A-1 and Actiyilor Type B
Armstrong Products Company
\
i:-.. . Argi>imc Road, Warsaw. Indiana
d. Adhesive .0CGO 1. Synthetics Organic Company,
Cleveland, Ohio, used with activator dicthylenC liiamlpc
. (Carbide and Carbon ChcnilcarConir*rny)
'
Straight Nitrile Rubber: When straight nitrile rubber was or iginally used, invariably the gasket'wav recessed in a groove. This was to prevent gasket flow and to piotecl the material against excessive compression, Although this type seal was
not cemented, the nitiile robber gasket Is ngf reuseable,
Since giooves or stops have heady been provided for tire
nitrile tubUi seal, Silastic 60 ctm be easily substituted and is
recommended. T his conforms with modern practice.
,
XVI. Pci iodic Fluid inspection and What Checkpoints Mc<m
On a regular schedule - at six, nine, or twelve month inteivah - moke
simple visual InSjX-clion of your askaicl Insulation and run a dielectric
breakdown voltay'check.
' -`
*1 f*rtn>o-K ol Otur^ol decide Compr-ny ' * *1 fKlcmbik 0< MiiHitprlH Minhly & Mi>nu(nuinu Comjuiriy
A
TOWOLDMONOQ35748
A. Visual I f>Sjf*<*ctipn:
. Askarel is a pleat, f*ini-yc!low liquid. After longterm use this color may gradually Intensify to light brown. The fluid should remain cleat And free fiom turbidity or cloudinc;s.
!!
V Is1Any color change - such as to a green, red i blue c<*<t - Indicates enaction of imtMjrities (colot materials) bom the solid insulation. If a distinct foreign colot pick up is noted, cheek the complete
it
range of electrical characteristic* and notify the transformer maker. Blackening of tire askarel may Indicate an arcing condition. Other Color changes alone are not danger signals since the dielectric breakdown voltage Is not likely to be impaired.
i
B. Dicloctrrc Breakdown Voltage
If the dielectric breakdown voltage ha1 decreased significantly from tire laM ln$j*cction, or if it has gradually decreased below 26 KV rang* (at ?(>tl - RUN A CHICK FOR MOISTURE. Use AS1MD1633 (Karl Fischer Method).
The dielectric breakdown voltag* of askaicl is the major indicator to tire operating efficiency of your liquid insulation, 8csidcs the
visual inspection tests, dielectric breakdown voltagr Is the only
test necessary to rurt on a routine basis. Well-sealed askarel
transformers have wwjc* records of 2b to 30 yea's on the original
askarel.'
.
XVH, Insf'cciion Checklist 1, If askarel 1$ clear - even tlrough darkened to light blown, has no
sediment or turbidity, ha* dielectric breakdown voltag- over 26 KV - give it If re Inspection "OK".
2. If askarel Is clear, but.ha( foreign c'lcr of bU't, g'fein, red ... It is
"extracting color" from internal materials. 1 his Is noi, of itself, an
0|*crating ha?a>d when tht dielectric brv.ikrluwn voting*- Mays over
26 KV and moisture remain* low. However, ihi* rare ocfotrenct
calls for chocking into the condition of flit inleilor construction
and.consulting the transformer higher. However, when sampling
the fluid ewe should be taf.cn to avoid g* tuny color into the
askarel from i>airt that may be insid- or uteid- of the aample
valvc.
.
:
lair
!# \)
hi;
\i
3 If the moisture Content is found to be al'ov't 70 pp*n at Operating
temperature, 1b<;n sampling should hr done at mo*. frequent
inlet vats to establish, a pry-ML-h trend. piUli'dIHy on Outdoor
-installations.
'
i
If askarel is dear, but dielectric hr cal. down volte;/ drop* to 77 or lower KV, and moisture rises qvci 80 ppm when sampled at operating temper Blurt; ... the a<.k?u;I Is tv-dy for sim^c ''tcfirvmy", If the moisture is nc;a the saturation level (about 126
ppm at rod'n temp' raknc) a thorough inspection should be made foi water droplet* in the iiau:.fi/mcr tank, and even for "globules" of water floating on tin askaul sur(<".*. If found, the tiansloMni i manufar imer should he consulted fo< ruundilionlng bolh the tianslofirici and the fluid
6. If askarel Is dark brown to blank, If blast policies of carbon arc Pen, arid dielectric sttcnylh Is low . . . the a-.lye! ha'- l* cn broken
down by arcing. It cannot be refined and should hi. removed arKl
Incinerated undei prui*- r condidous. (Sc ANSI CI0/.t-f074,
Sr-cifon 4.1,C).
.
H, any of these five simple Impr chon teste pm ;< out of the ordinary or the relationship between ap|-,. uiiu amt i,-4i values Is
abnormal, contact your' transformer supplier foi a cor tptoi.
analysis,
.'
.Whenever a Sample is to U shipped to Monsanto, ph pm follow the directions shown uhdci; "SAMI'LING A$KAFtt I
HONS 078673
TOWOLDMONOQ35749
XVIII. Contamination In Transformer*
.
Moisture, pt'ilcutate mattai end arced decomposition product* arc
known to be mi lout contaminating Influences on transformer iskarel.
The power factor test normally used for tlie detection of contamination In mine>l oil filled tirisforneri is of little use for this, purpose In
iskarel filled tiansfomicis, due to the extreme effect of extraneous . soluble polor materials. This Increase in power factor as Illustrated in
Table VI hat no adverse effect on dielectric bieeicdown voltage.
Table VI Effect of Common Insulation Materials on Power . Factor and Dielectric Strength
(Hoot Aged 9C Hours in Askaral at TOCrC.)
` .'
Askarel After Exposure
ir,
,
Power Factor,
Dielectric
,
Perocnt at 60
Strength
- Material Immersed ' >
' ^cyc., 100*0
_ 26"C.
' None (control)
Vj 1
Black varnished cloth
' ..
i'i ,, ,< . Copper
-`
i'': ' Piessboerd 4 Manila paper
, `
) ; ; '
Phenol formaldehyde resins
fiheltac1 : .
v'
`
> . . boh ! ': ij } , Synthetic rubber
'
1.0 86.0
1.6 2.0
1.6 1,6 6.Q . 6.0
70.0 .
3b kv 42
. 40 37
. 39 41 36 39 39 `
i1 ; !<,:
Similarly, tract,' contanilnehts from commonly used construction
material* can lower the volpme resistivity of'atkarol, without affecting
Its dielectric breakdown voltage. This is shown In Table VII.
`
'
., ; "
", . .'> ; w labioVli . ' ' - ..,
Effect Of Common Insulation Material; . ,
'
on Volume Rts(*t(vfty of AtkaVel .
.
Sample
-
: . . ' .
Volume peslstivity x 10 ohmem (at
lOD'C., BOO Volts ; DC.,.0.1" gap) '
.1. New askatcl before heal'ag|ing ' ' v
,
?, New atkarel e/ter heal aging 90 hourt at 100"C ,
3. After heat aging with 1. id- inch specimen's of:
a. Phenolic retin tap changer . b. Pepfcr . .
' V
-. '
: c.Grede A pressboard (tanf r )\ ,
d.Gradr A pteslboard (gray)
/' . `
a. Grade A pieisloard, ianiirtaied itrip . ,
f. Cotton wrapping
':
g.&Jyptal 1?76 cement, cured48hrsl*M1Q*C
2,0()o r . 1.900
1.700 ' . 1 7b0 \
600 \ '600 400 ; 300 100 - V
to'
While trace contamination easily lower* volume resistivity from high level*, It it important to rtote that heavy contamination (as when treed) does not lower the resistivity below the order of 10 ohm cm. at 100*0.
The different 'bchavioi of iikarej vs. mineral oil In those respects pari be
>ummer1*ed a* follows: .%'
'' ,, ; .
,,
' > High power factor "and low volume resisjivily In transformer
, rhlncial plls are commonly regarded #s "danger signals" that the oil has deteriorated 4nd broken down chemically or.excessive
moisture ft preient.
- , >
/` ,
1 his Is NO.l T HUE of gskarel liquid insulation unless the dielectric breakdown voitago Is low'or the moisture content is high.
M
TOWOLDMONOQ35750
Manufacturers of askarel type transformers point out tl.at it It quite well known that askarel transformers with Initial power factor of the
askarel fluid in excels of 50% at room temperature and 60 Hz are giving satisfactory service life. However, there needs to be assurance that both dielectric breakdown voltage and moisture are at satisfactory levels and do not show advc r sc ti et ids N
XIX. ASl M D326b Method For Investrgnting The Compat
ibility Of Transformer Insulation and Construction Materials in Askarols
This method uses the change of alochica! and/or chemical .characteristics of transformer askarel resulting front its controlled exposure to insulation and construction materials. In order to evaluate their Immediate major "contamination" affect on the askarel fluid. Delayed or long time contamination effects may not be detected.
The rpethod also utilizes various physical tests on the insulation and Construction materials after controlled exposure to the askarel to determine the compatibility of these materials with transformer askarel.
Properly proportioned specimens of the Insulation or structural materials are Immersed in refined askarel for 168 hours at 100 1*C in a forced draft Oven. Changes in electrical end chemical properties of the transformer askarel are compared against a control sample of the askarel treated In the same manner, In absence of the test specimens,
Dissipation fadtof (A$1 M D 924) change Is one of the criteria used i he askarel fluid Is, defined by absorptive freotihcnt to a dissipation factor level of 0.05 max, at 100*0 and 60 Hz and 0.01 max. at 25*C and 60 'Hz. Corresponding values of the askarel fluid after heating 168 hours at tOOt In absence of a tes) specimen are 0.07b and 0.0? resjrcclively. The maximum! dissipation`factor levels sugycstrd for the askarel after
heating In presence of the'test specimen are 0.20 at lOOX and 60 Hz and 0.04 at 25t and 60 Hz.
XX. Ftefiplna Aikerel for Reuse,
A. Filtering' Through Ory Blotter Paper to Remove Moisture and
Extraneous Particles: ,
Mqst operators prefer portable r*fi/ilng apparatus, such as a plan-
press fitted with a dolly, available front Sparkler, Mundelein,
Illinois or (general Electric Company, Pittsfield, Massachusetts, or
the earthen cartridge filter type available from Industrial Filter
'.' Corporation, 4.6t>nori( Indiana. Filter paper liners for the plate
\ press are available.from Carl Schleicher and School! Company,
Kearic, Now Hampshire and manufacturers ol filter presses listed
"' above..
` .a .
' . The filter paper must be dried immediately before use. For best results/spread the ftoper for maximum surface exposure In a hot
.. . air circulating dven and heot it for 4 to 6 hours at HO C.
Circulate The eskjrel hot (but not over 40C) through the filter /' fitted with the dry paper liners. ,
After filtration.the dielectric breakdown voltage of the askarel should be 35 KV minimum, ` ( .
PRECAUTIONS:
'
1, ; Filtering sh.ould not be done when'the relative humidity
. exceeds 76%. -f,
,
2. Any flexible ho$*$ and gaskets on the refining equipment
should be lined With or made Of materials that will not be ;softened by contact with askarel fluid. (Materials lined wUh Siijconc, Vi ton or Teflon* or flexible metal
materials are suitable.I .,
i
I i >
I
t: :[ i v 1
i
trademark ot , t. Dumont DNer>>ou>s & Conv',r,V. Ire. MCNS 078675
TOWOLDMONOQ35751
TABLE VIII
Quid* to Rita of Dissolved Water Removal By Filtering Askarel Through Paper Press
Passes Through Paper Press
Water In Askarel __ PPM
0 115 1 35 2 22 3 18 4 12
6 10 6 10
B. Disposal of Solid Wastes:
The ANSI guide C107.M974, Section 4.1.6 gives detailed
recommendations.
>
ill
I1'!:
i1
i
C. Solid Insulation Requiring Drying:
. If the solid Insulation of the transformer requires drying, consult the transformer manufacturer pt an apparatus service shop, as In
such cess oven drying Is preferred.
P. , Earth Treetment for Maximum Improvement of Power Factor and
,i - V Volume Resistivity:
.
yj. We question whether pOmping and filtering the fluid solely to
; . achieve a change In po'^r factor o\ volume resistivity alone Is
r.'vjMftWW In today's ecolopteal.cllmite regarding PCBs We redom- -
' ' mend that Iri these Situations the original transformer menUTac-
turar6econtacted.
\ .
. ' -
..............1. Procedural
, .. '
'
The askarel liquid should tp relatively dry prior to the
' ` fallowing earth filtration, r. ^
\`
. ,. As a coding 00 the fclltaf Pipe/ surface use finely divided
Atteputgui* clay or .FuHara earth dr|#d and Activated by
heating tot \ 2 hoursJt 3o0-3lrF immediately prior to use.
The amount of earth Mwdebdyid.be 0,1 to 0.2 percent by
Weight po"the vvel^t of^ iskajet.tp be treated. Askarel
weighs about 12.6 pb^ndj wjllpnv] ' J
.
..
To deposit the rihvehfy^r'^'-third of tfo earth with a
small portion of askarel in tflbleap contalner.fump the
mixture through the filter *rjd f9,l{tw .With two more one third portions. .Then circulate .Bskarei taken from near
the top of the trensTormer, pesif Itwarm (not over 55*C)
through the earth-coated filter .and feed beck through the
bottom transformer outlet. Continue Circulation until the
fluid Is clear and test shows that the electrical properties are
fully restored.
; , ' V;'/V.';
2. Effect of Earth on Rfftioval of $ceVangeri , .
.
Only slight end insignificant loss by selective absorption pf
tin tatraphenyi and epoxies occurs When askarel is refined
1 by treatment with 0.1 to 6.2 percent by weight of earth. To
remove significant amounts of the scavengers requires repe
titious treatment with mltcb larger amounts of earth.
.'Trademark Qt Engelhard Minardi and Chemical* CorD.
MONS C 756 76
TOWOLDMONOQ35752
Table IX Approximate Relationship Showing the Insignificant
Effect of Power Factor and Volume Resistivity on Dictccb Ic Breakdown Voltage of Trensformcr Askarel
Power Factor
(60 eye.)
100*0
26C
Volume Resistivity X 10* ohm-cm (at 100 C. 600 Volts . DC, 0.1" gap)
Breakdown Voltage
2b"C, 0.1'' gap
2% 65% 15% 20-26% 40-50%
0.05% 0.1% 0.7%
2.0% -
1600 600 100 6070
26
30 KV 35 36 36 36
XXI. Cleaning Arced Trensfoimcrs If a unit has arced so that the askarel is no longer fit for use, a thorough Cleaning of the unit it necessary before refilling with new askarel insulation and returning It to service*. Follow this procedure Insuring care is taken to prevent any toss of liquid askarel to affluent streams.
A. Drain out ail dark, carbon-contaminated askatel. Arrange to have the scrap fluid Incinerated under proper conditions. (Sec ANSI Committee C107 report.)
B. Carefully brush carbon deposits from internal parts and insulation, using a soft bristle brush making sure that Insulation is not
damaged.
,
C. Flush thoroughly using new askeiet - not an oil, nor a cleaning solvent.
D. Flush a second time with fresh askarel; drain; then fill to the proper level with new askarel.
E. Energln* transformer to warn* the fluid for 24 to 48 hours, then circulate the askarel through a filter, returning it to the unit filtered and ready for use.
XXII. Sampling Askarel
1 ake a sample as close to the top of the liquid surface as possible. Many largo askarel transformers have a built-in sampling tube near the surface for convenient sampling. Then, to make sure that your sample truly represents your askarel insulation, take another sample from ttre bottom, ff additional sampling tube connections are contrived on the .valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; end silicone, or Vifon or Teflon tubing fqr flexible typos'. .
Use NEW containers fpr the askarel sample. A new and thoroughly pre dried, small-moufh quart glass bottle fitted with a Bakelite"* screw cap with aluminum or tin cap liner is recommended for quick, on site ' testing. (If complete analysis Is to be made, a 6-pint sire sample Is
required.)
Be sure that the new' bolile does not stand open to collect dust or
moisture. Rinse tho temple bottle and cap lining two or three times
with askarel horn the transformer, then fill it. If the sample will be
tested promptly, a clear glass bottle can be used. If sample is to be
stored indefinitely. Use an amber glass bottle or wrap clear glass with
aluminum foil.
.
A. Select a dry day. Do nol sample insulation on a warm, moist day when humidity exceeds 76%, end ...
`This tsi'/vict that tire Cause o< arcing has teen established and coimc'roni made. When severe arcing occurs, major repidrs are usually neceu^y and ihc unit rebuilt. This procedure can be applied lo< flushing out tho repaired units
`Trademark of Union Carbide Corporation
MGNS 078677
TOWOLDMONOQ35753
B. Make lure that the eskarel is, at least as warm as the surrounding alt. ICokt liquid* can condense moisture horn humid air.)
C. When templing eskarel from transformers, it Is best to take the
sample when the unit is warm end operating t average or
maximum toad, especially for a check on moisture as reflected by a dielectric breakdown voltage test. Sampling the warm eskerel
mom truly rtpi?$fnts its condition during operation. .
Experience shows that watei will tfliQiate from a transformer's solid insulation to the eskeiei liquid and vice versa, depending on temperature. Therefore, when tfic transformer U hot, the moUtyre It most likely to be found in the liquid. This accounts largely for periodic variations In dielectric breakdown voltage. For example, a relatively high dielectric breakdown vottegc may be found during w|nlet months and a relatively low dielectric breakdown voltage
during the summer months on samples taken front the tame unit.
'When testing has becn completed, tire remainder of the fluid
sample should be destroyed by high temperature incineration
described In Section VIII,
'
MONS 078678
TOWOLDMONOQ35754
Askarel
tilled Switches ami Icnhinal Oiambcrs
I. Introduction
.
High voltage leads are usually connected to askarel or mineral oil-filled
network transformers and power canters through terminal chambers
and switches, In sonic cases terminal chanibers are not used, and the
high voltage leads are connected directly to the switch terminals. They
may be filled with either askarel or mineral oil. Switches re usually
rotary or drum type fitted with a revolving block and porcelain unit as
the principal element arranged for three phase service.
Asker'el tfanvtpfirifcrs'with gtladhcd (witches have been In use for about 30 years. When they were first Introduced, the availability of insulating and gasketing materials was rather limited and even the best materials at the time had no service history. As result, inadequate gasketing materials such as Cork, nitrile rubber, and nitrile rubher-and-eork
particles were ysed. While satisfactory for a limited period of time, these materials cannot be depended upon for the exprtted long life of the equipment,
The terminal chamber )s usually above or below the switch compar tment ar>d separated by *'steel wall through which the bushings
a/e Inserted. When bushjngs a>c properly selected end correctly
Installed, there is no leakage front one.comp*'tmcnl to the other. With
poor bushing seals, and the terminal chamber above the twitch, potting
compounds Or cable oil can seep into the askarel. When the terminal
(jhanibcr Is below the switch, askarel can drain Into tire terminal
chamber.1
, ^ '1
II. Sources of Contir)iination
There ale Three possible . aourct* of contamination for askarel in
twitches end terminal chambers; they rank In this ordc-i of frequency:
|1) water entering through poOr gasket*; (?) decomposition products from arcing When switch,is used to break magnetizing current, (3) entrance of pothcad or cable compound* through leaky boshing seals.
-Unlike an esjtarel transformer where the amount of contaminant is likely to be very piall (probably only tract amounts) in relation to she volume of askarel fluid - in' switches or terminal chambers with faulty teals, the amount of contamination can be relatively largo.
Experience has shown drat, b*scd on tire number of installed askaral-swftcli units, the percentage Of failures Is exlremOly small When Investigated, it has been found that rfiost failures originate in the switch chamber. Water It ttte child source of contamination. However, heavy contamination of askarel with petrolatum and asphalt material, due to leakage, have caused a few failures. , .
Petrolatum it used frequently for filling terminal chambers. When either cable Oil Or petrolatum Seeps info askarel, no great harm results. The fire resistance will be somewhat decica'-od and power factor of the askarel will Increase with an actomperiyiny d*op in resistivity, While highly Undesirable, it is doubtful that fa,Hurt of the unit results. Where asphaltic compound*.*'*)'used in place of petrolatum, the danger is increased soprewhat because asphaltic .contamination may cause
'excessively high dielectric losses in the p*k*'tl.
When the terminal chamber is below the switch chamber, the potting compound can be contaminated by askart) if the bushir>y seals are feoky. This it undesirable because the askarel will increase the power factor arxf conductivity of the potting compound or cable oil and develop heal from dielectric loss. If this mix tut a is drawn into the tabic
MCNS 078679
TOWOLDMONOQ35755
Insulation, a cable failure Is likely. This again emphasizes the Importance of tight bushing assemblies,
III. Scaling Swltclios and Terminal Chamber*
Proper bushing construction, use of Silastic seals and welding wherever possible is highly desirable {as covered In Section A). Whore an elastomeric scat is to be used In contact With both eskarel and petroleum oil, DuPont's Viton Is suggested.
For new equipment the user should specify these modern sealing Hangrmentt to kaop out contaminants and minimize maintenance.
IV. Askar el Used Under Mild Arcing Conditions
The IEEE Guide for Transformer Ask at cl calls attention to the
following:
,
"Askarcl Is used, to some extent, in apparatus where it It subjected
to light Intermittent arcing, such as in self-contained Induction
regulators, where operating switches are continually producing
slight arcs, In transformer deenergizing switches, ate., Under
normal conditions, deterioration of the. Sskerel 1$ very slight.
However, improperly adjusted or defective switches In this type of
apparatus can product excessive and prolonged arcing and
accelerated deterioration of the askarcl, It is recommended that
when askarbl Is used under these Conditions, checks of the liquid,
especially for moisture and dielectric breakdown voltage made
more frequently the!) when it is used only as a cooling and
insulating fluid. Deterioration of this type is Indicated by a
blackening of the liquid, it. can usually be reconditioned as
previously described.. Special attention should be given to
maintaining the scavenger at the appropriate'concentration."
V. Maintenance foi Askarcl FJHcd Switches
`
A. Switches uiedfor grounding frfur power , source has been .
de energized will not undergo arcing.
'.
B, Bwltcho* Interrupting magnetizing current will be subject, to
arcing; the amount of decomposition will depend on power
Interrupted, time and frequency of operation. At a general rule,
tire liquid sl>ould be checked after 6 to 10 operations.
t. On newly Installed switches, check the iskarel at 3, 6 and 12 ... month intervals; H found satisfactory, chock onefe annually _
thereafter, With proper. attention to the gasketing'of covers *
. and bushings experience will probably Indicate that less 1
frequent, irjsjrccOon IS wrirrinted- *
.
' ;`
2. Check askarol for;
;
a. Dielectric .braakdriwn vOllaoc (ASTM D87'/|: It should . . be 2G KV minimum. If dieTcctiic breakdown voltage is:
' low, confirm presence of water by Karl Fischer methpd
. . AS1M D-\633. Flltei to temovc moisture. Dielectric
strength should th'wft be 30 KV minimum.
A
b. Piescnce of carbon .from arcing; fluid should, be ..
' ' relatively free of carbon. If badly arced and very black,
. replace fluid, tf only minute amounts pf carbon are
\ , present, filtration Vrecommended. Check power ,factor
Of liquid (should not bC Oyer 5% at 26*C and 60 cycles).
Flush put switch chamber with several gallons of fresh
askarel befoie refilling.
.
3. if there Is discoloration, high power factor, detectable change
In specific gravity Or refrecUve index, or if fluid flashes below -
, 2hDF, there |s a possibility of seepage of potting compound
Into the switch compartment. In this ease, correct any loaky
bushing sea's with proper replacements and fill With new
askarcl. ' ' , . '
.
.s
4. If terminal chamber Is below switch, chtck potting
compound for presence of aSkaiel (can usually be detQded
by odor or by ah Increase in specific giavlty). If askarel Is . .present, correct any leaky bushing seals with proper
replacements, and r enew compounds.
$. Examine cover gaskejs visually. Deterioration can be detected
I.
, . ( ! .. '
' `1
' J
*
..
; '
by (welling and cracking of the exposed edge. In cases of
acvere deterioration, liquid seepage Is usually present, 5. Check for leakage at packing gland of twitching thafl. If
leaking, repack with a Silastic ring type gasket.
' VI. Askmet Under Excessive Temperature or Fault
, Conditions
, The IEEE Guide also points out that,
. "Chlorobenzenes used In transformer askarels begin to boil at
'
:.
temperatures of about 20b*C, under atmospheric conditions. If the
.. . material is heated to such high temperature In a scaled aystem.
- pressure develops. Pressure will also develop In the system if the
. askarel is arced sufficiently to generaie copious hYdroQr ri chloride
.
, gas.
`
...
"Therefore, it is recommended that wherever possible, scaled
: askarel-fillcd equipment bo provided with piessure relief devices.
. .'
These devices must be large enougi. to provide In.mediate relief at
. '. a definite pressure, and to prevent further build up of pressure if
decomposition continues. It must be remembered that the
presence of devices 0! this sort does not necessarily preclude the
. rupUrring of containing vcs<els, since piessure build up can be
' '
extremely rapid under violent arcing conditions."
Safe
16xiic*(y&.? llaiicllinr.
I. Inhalation
.,
At Ordinary teniperatdres the chlorinated biphenyls In Askarel have not presented industrial toxicological problems The h*?a>d of potential
toxic exposure varies with their volatility: the lower-chlorinated, more
Volatile ones Present more of a potential problem from the stendi>olnt
of both inhalation and skin contact. When Askarel fluids are used at
elevated temperatures, engineering controls must be applied, either by
' tire use of closed systems of by effective local exhaust ventilation togMhc/with general workroom exhaust.
}. '
..,.v vl. t, ,;i . ` :v
, .'
Vapors of Ask**** at room tepipcrauire ahould not be breathed In e
: ' confined ipace, and.no vapor of any fluid evolved at elevated
temperatures, sliould be allowed to tx disput'd Inti, the geneial
. workroom.
, '
,
ft Inhalation tests pn animals Indicate that the maximum safe concentre tion of vapor is In the rang*1 of from 0.5 to 1.0 milligram per cubic meter of air. The threshold limit value (maximum allowable concern
traiion of ah 0-hour working day) set by the American Conference of Government Hygienist^ Be t.O milligram of the lower chlorinated biphenyl compounds pci Cubic meter of elr and 0.5 milligram of the more highly-chlorinated compounds, per cubic meter of air.
1
( :
*. f
It. Skin Contact
.
Prolonged or repeated skin con tact with the Askarel fluids must be
avoided by tire .use otglovfes and protective garments, because of the
possible pccUrrahce of a Condition called chlorecne. Altiiougf 1 reports
of tliis condition caused by Askarel are fare, it can be produced by
excessive (kin contact. If the fluid Is (pilled on the skin the skin should
bo washed In the usual'monitor with a soap solution.
A burn caused by Contact with a hoi Askarc! should br treated like any
ordinary burn.
'^
Fqi disposal Instiuctions of Asketel fluids sec Section A VIII, page 6.
*0NS 0 78681
j I
I \
I TOWOLDMONOQ35757
'S@tlnco)i8ilO) - A| alylical Scrvices
.
t oii lianrforiiici AskfticI
Available liom Monsanto
[ Transformer users nol wishing to mqke thalr own fluid analyses oah obtain the service from Monsanto. Simply contact Monsanto
and |>ecUy what analyses are wanted.,Yog will be sent, the Proper-Sized, clean sample container, fitted with a proper lakl.Wlnn
| you receive this, carefully taka your wnyiple following the procedure for sampling In this guide). Send the container to
Monsanto'i laboratory. Charges listed Include sample container and laboratory costs, tire charges are those In effect Aupusl 6,
1676, and are subject to chongr.
.
>
'
J| Types of Analysts Avglloblc ,
j :) Analysis 1)
'
g,;i ROUHNt MAINUNANCt CHtCK .
.
,, Total Charge: fcft.OOPer Sample
Todcteimlnc the general condition of the fluid and find whether further analysis Is necessary, (one quart sample required)
Properties Tasted
' , , . , Dielectric Breakdown Voltage
Color and Condition ' : .
Moisture . . . . .
You will be notified of the result* of this test. If fur the; testing 1$ Indicated, and you want a complete analysis, you will be sent
five pint sampler container ,1 n\s sample will pc used for tire following scries of tests:
Analysis ?)
.:
COMPLfU ANALYSIS :
-.
.' .:
,
Total Charge: $166,00 Per Semple .
*.
(1) To deter mine tire extent of fluid contamination, (?) earth reflnemept to determine what degree of restoration of electrical and ImuloliuQ propertiesU possible, (3) ctack test to Sec how the fluid responded to eaUh treatment. .
a) Ocuviplciv Analysis', to determine the extant of contamination ; '
Properties Tested
.\
` free Chlorides'
1`
. , Color and Condition , Specific Gravity , `
. Acidity :
-' ' . .
v ' Oielceuic^rcakdown Voltage
,Rglr active Index
J
Power fafclor, Diel^tric Constant, and Resistivity
:^
;v-:
. .v
'.
d. ' ,b) t tli,hctincn'>cnt Response:. . ' . '/; . : ,. ' v ^
'
`
.'
Consists of treatment for 2-6 hours el 6060^C. with p.1 0.2 percent by weight of proper ly conditioned AU<tj'ulgu$ clay
j;, and then filtration ihipugh dry filter papfi. ':
. ' '
* . c) Analysis After Laboratory Earth heUucmeui:
. . .
`
,
(. Properties Tested . '
' ;* Apf.dily : ; ; <*
` ,-
, Rehocllve Index ;
^ Dielectric, BreaKdown'VpItag''
1
|
Water .
V
*, . Power .factor. Dielectric Constant, and Resistivity -
J: Pfoc Chlorides ' 1
' -.C- ' V
,
d'. . ` Yog will be notified of the results of this test series on your sample. Then after refining your entire tiensformei fluid fill you
if . cap check on the result^ by reqirstidg the loMowIng analysis:,* ;
,
ifIk ' ' Analysis 3)
,'
ANALYSIS Arn ft 6AfttH Rtf JNCMf NT
, /; '
- . :
. *. "' . v; Total Charge: $70.00 Per Sample
Hhis ciialgc will hot apply wlirn
, -
\ - . V *: analyses l and 2 have aheady been nadc.)
.
' '
v To determine whether the entire lot of the esltue! fill raspondedto tlie Same extent a^ the .laboratory sumplc. (five pint sample
required) ' Piopcitius Tested
V' ' .; :
` ...
' * .free Cftlorldes , .
,
Color and Condition
";
: Acidity
, '*
'
Reh^ciivi' In^x
. , ; Dielectric Breakdown Voltagt' :
'
Wstv.t
. 1 . ' v)' Power Factor, Dicleciiic Conslaht, artd Resistivity r
To arrange fur the tests described above; wi itu b the following iddra^:
Pvld W.wod .. .
.
\
Moushoio Irsdustrlel Chcrqlcals Cof|>rH*ny
':
BOO North JLIndl-irgf. Blyd.
/. v
.. .
. Rt. Louis, Missouri 6316G
- <:
,! . ' .
, ,. .
.; *
'' ,
'' .
' '
.
Semples to be tested siroul.d b'Vciem.ly narked for Identification and sent directly lo'.
i *' Mmdimto Compfriy
!' . W. G. Kiummriglt talK>iatory ' .
| W,St*ug'1. Illinois 6?201 , . . ; , Atieutipn J. A. Qtocckoe* .
,-
:-
. '
. , ,:;v
'
W
;
.
HONS 078682
TOWOLDMONOQ35758
^xstjttailK AiH*cn(kcs
APPENWXA
" `
.
Askara! Stability and Composition of Arc F orn.cd Gas:. Askarel insulation Is one pf the most Inert, chemlcatlysublc heat
resistant, non-con wWe liquids known. It will not break down, oxidize or sludge when exposed to air and high temperatures,
1S0"C. or even somewhat higher. Arcing, however, will break down the compound to liberate some hydrogen chloride and
amall amounts of carbon.
'
.
. ..
-,
AP/`ROXIMA1fc COMPOSITION
A^-FORMED GAS FROM TKANSFORMt R ASKARU BkFND$
- ' ASTM TYPES P ANDO
- . (INEHTt EN 70-30 ANDPYRANOL A13B3R;3,RESPECTIVELY)
' .
" Gas '
'' ' , . ; .
' ' .. ;
' Amount
.
, . carbon monoxide
..
carbon dioxide
i `
oxygen
,.
; v
' Inertgases
,. '
. > ' , hydipgrn Chloride '
, "'
|note the absence of phosgene)
`
,
' :.
.
- .
0.3% 0,3% 0,6% 1.6% 97.3%
(Tnls arc-formed gas f(om A$T M Type D and Type F transformer askarols is non-flammable and non-combustible.
For all practical purposes, the amount of gas liberated front askafel under a given set pf arcing conditions is about 100 cubic
centimeters pci kilow.att-setorid. ' ,
. ' : -
. ,. . ;
ANENDIX6 ; ':.V .. ; ;*' t
:. '
' i < SOLUblinVOf OASIN1RANSFOr(MtRAS^ARt'l.S
.
1 ' : '
A$TMTYPES DANI'G '
. ' '
1. ,
. '
.
' y . ; \
{'
,, Rarcent of Ga< By Volume Corrected u>:
' ;'
76Ci.n,ni
^ BC.fM.rm
,
... . . '
tyc
me : ;, -c
jooc
Carbpndioxide
/; Air
. ,
. Ni.tr^gen .>,* '
Hydrogen chloride*.
, 71% ..' .6.7 ' , " 6.0
- - ; 37.8
. . ,47%
, 4.9 ' ,,
. . 4.8 ...
60.9
.
,6.8 6.6 ,
-6.0
4.4
-
: . ^In'ahscnce of.wftvcrigcr ^
-'`V ' J
.
' apKnwxc
.. ;
;.
.
.
T Ep tCf or ItMrEHATUftf ON PlklSCTRIC BBEAKriOVyKl VOIIAOE Ot ASICARtt
,; ,
' ,
. , '
: ` .
Tarnperature 'C
-60 :-40'
- 2t ` 0
: ' >0 ' V 40 ,
eo .80
Dielectric Breakdown Voltage
AS1MD87?
' 67 KV .
63 67 6b 60 W , 60 48, 46
HCNS 078663
TOWOLDMONOQ35759
APPENDIX D
COMPARISON OF THE APPROXIMATE yiSCOSIl Y IN SAYBOIT UNIVERSAL SECONDS OF TRANSFORME R ASKARELS AND MINERAL OIL
Tamp. *C
~ -20
0 20 . 40 60 60 100
Pyranol . A13B36-3
~i,ooo
' 100 70
46 39 34 30
10 C Mineral ^ Oil
~ 1,000
160 66
49 40 34 30
tnerlecn 7030
2,800
166 86 60 40 36 33
APPENDIX E
mp. *C
0 20 40 60 80
tHC DENSITY OF INERTEEN 70 30 AND TRANSFORME R PYRANOL A13R3P 3
Approx. Density gm/ec.
' ; Inertecn 7030
1.674
1.662
; 1.629
1.607
c
1.486
Pyranol A13B363
~ 1.67/
1.666 1.632 1.610 1.488
APPENDIX F
The thermal conductivity values of transformer Pyranol A1383B3 at 27*C and MFC ara 26.? and 26.8 x 10 * calorie* iantimetets 1, degrees centigrade*. ifcispnd * , respectively. Or, approxlnitly O.06 81U pot (hr.) (sq. ft.) fF.) pet foot.
7hli*meapproximiWn4f>plle$tolnertcn?03O.
'
.
appcnpixg
; vc
Hast Capacity
\
^ /'
/ V. ... ; .
*bvot the temperature range of 2* to12b*C the specific heat of transformer *k,erel it close to 0.30 calories per grant par
dcgtac. ' , `
' '*
; appendix h :
/''/V'-.
' ' ` ' .! . '
'
Coefficient of Expansion ,
t \
.. . ' 0 ,
1.
^ho average coefficient of txpantion of transfornieriskarel pver thctemptratvirc range 20 to100*C is Q.0007 cc/ccAC. One
gallon wduld increasrl to I.ObC gallons op heating from 20 to 100*0. ,
i
.. .
V
APPENDIX I
!;
fire Resistance
'' * - V. :
.. '
Askarel* of various compositional types ire usld. Undet .arcing condition* the .gases produced, while consisting of
predominantly non-combustible hydrogr n chloride can yield varying arribohl* of combustible gases depending upon the
askareltype.
' ''
v
'
Insulation systems tncoi poiating Wiese askarel* and cellutoilc dr other organic materials may, when arced, produce gaseous mixtures which ate modelalely flammable. As a precaution, such gases shout'd be removed from the askarel by bubbling dry nitrogen through the eskeiel eM. flushing the flat space with dry nitrogen before any woik is performed on the apparatus.
HONS 076684
TOWOLDMONOQ35760
APPENDIX J
Suit, Properties end Procurement Dow Corning Corporation, Midland, Michigan with Districts at Atlanta, 8oston, Chicago, Cleveland, Dallas, Los Angelas, New York City, Washington, D.C. and Toronto has available Bulletin 09-019, August 1962 entitled "Silastic Design Data". This lists the gasket fabricators throughout the country from whom the "Silastic 50" gasketing can be purchased in sheet, extrusions or molded shapes.
Generally, Silastic 50 sheet goods are stocked by local die cutters, hence, could be generally purchased locally. Usually small quantities of gaskets are die cut. if larger quantities are needed, tools are made of the same type used to cut other elastomers.
Where the gasket is extruded for fitting into a machined groove or between gasket stops, Dow Corning advises use of a starved Joint. This joint is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) materials, which air cure.
Dow Corning points out that the local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll milt in preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 60 for 24 hours at 480*F.
SPECIFICATIONS*
ASTM D676
ASTM D412 ASTM D412 ASTM D395
Color Specific Gravity at 77*F Hardness, Shore A. Scale
Tensile Strength, psi, min Elongation, percent, min Compression Sat after 22 hrs
at 30O*F, percent, max
White 1.20+ 0.02 45 to 60 800 250
30
4All physical properties measured on 0.076 inch thick samples molded 5 minutes at 240*F, and oven cured 24 hours at 460*F.
APPENDIX K _________________ __
Caution Label Th< following or equivalent caution ttatements should be fixed on all container! of transformer askwels and ilia trans former! themselves:
fhle product contains Polychlorinated Blphenyle (PCBs). Cara should be taken to prevent entry Into the environment throu* spills, leakage, use, vaporisation, or dlaposal of liquid or containers. Avoid prolonged breathing of vapors or mists. Avoid contact with eyes or prolonged contact with skin. If skin contact occurs, remove by washing with soap and water. Following eye contact, flush with water. In case of spillage onto clothing, the clothing should be removed as soon as practical end the skin washed. Dispose of any contaminated materials as suggested In the American National Standards Institute document C107.1, "Guidelines for Handling and Disposal of Capacitor and Transformer Grade Askarels, Containing Polychlorinated Biphenyls".
Monsanto
MONSANTO INDUSTRIAL CHEMICALS COMPANY
FUNCTIONAL PRODUCTS GROUP 800 N. LINDBERGH BLVD. IT. LOUIS. MISSOURI 63166 Th Information herain regarding obtaining optimum results from askarel fluids in your transformer hes been eccumoleted by Monsanto for over 40 years from the experience of makers and users of askarel transformers and it is believed will be helpful.
Nothing herein shell be construed at applying to other than askarel Insulation. Data and maintenance suggestions herein do not apply to the other components of the transformer. All operating and maintenance suggestions recommended by the manufac turer of the transformer should also be carefully followed.
Because these maintenance directions apply only to the askarel insulation, Monsanto disclaims any liability for damage to properly or Injury to persons arising from transformer operation.
HONS 078685
TOWOLDMONOQ35761
US CUSTOMER SERVICE CENTERS
tBORtfOae 0evelcpment Park TW. (9181 $$94tlt
ATLANTA GEORGIA 90339 $80 Interstate North Perk wty Suite $00 Tei. 14041 434 4949
HOUSTON, TCXAS 7/059 1300 Port Oak Tot**r 90S1 VNtthtlmor Rood ft/. (713) $21-9680
LOSANGELES, CALIFORNIA 14010o** Btraat Suite $60
Naurport Beech, California 93880 TW. (714) 833-9180
NEW YORK, N8W YORK 18898 1114Avenue of tha Americas TW. (313) 7844000
GT.Louts, MISSOURI 9'66 BOON. Lindbergh Bird. 71. (314)884 1000
INTERNATIONAL OFFICES
AR08NTINA Bhutan* Argentina SA./.C.
. 4Mb Madaro 1800 Floors 17th S 19th Buenos Aires, Argentina
AUSTRALIA Bhiubnte Australia Limited
8m Them, Prince* Gate Bldg ttifpMhnBiHtl tarr........
ntgAmdlia Limited
\. . .....
, ;E:..ittwaiMMlkiM tuftmrlliwfu.ilJr
toHnllt Umbr
'{*#,
'
K Belgium
i*44ir'- ' hdugMsMehsento Ltda.
'
` ;L{ftSy5foJU . ,\'"h |l
<Mdli Ltd.
* ' ' Monsanto Canada Ltd. . . ' 100hHt Royals, Butts 701 Mbat Vancouver. B.C.. Canada
cHite
Monsanto Chile Comerciei t Industrial Lim/ttde EdHMo Etpene Ofkina 803 CoDa Estado 337 Santiago da Chile
COLOMBIA Monunto Oolombltm Inc.
Carrara 14, No 77 89 Bogota, Colombia
DENMARK
Monsanto A/S 0 Rysanttaantgade OK 1564 Copanhtgen Danmark
EL SALVADOR
Monsanto Centroamarka (Et Salvador) SA. tdificlo Plata 67 Ayan/da Sur y Cello a Santa Tecta San Salvador, El Salvador
FEDERAL REPUBLIC OF GERMANY Monsanto (Deutschland) GmbH Itnmarmannstrasaa 3 0-4000 Dumldorl,
Federal Reoub/k of Germany
FINLAND Monsanto (Scandinavia) AB Arkadhnkatu 9 0 30
00100 Helsinki 10, Finland
FRANCE Sodeta Monsanto SA 9 nta d'Argeneen 76 Paris (Bl Franca
GUATEMALA Monsanto Guatemala Inc.
ElfMo Casa Te AvanIda 7-11 Zone 9 Ouasamala City, Guatemala
HONGKONG Monaento Par East L td. Mansgsmant House. 2nd Floor 380cn1RoadWct HangKostg
INO/A . BUndle Chemicals Lid. RMtafUd House
11 Egrott Rd., Ballard Etsete Bombay B0t>001, India
MM* Chamkls Ltd. 19 Rafendronath Bhkhariaa Rd. ' CWewti* 780 001, tndla
Mindk Chamko/i Lrd Bt041 ILtnghi Chatty Street
Madras OOO 001. India
MRtOk Qwmketi ltd. . 9/B AMAH Road ; NlMDalhl 118001, India
HtoONE&A P. T. Monaahto Pan Electronics 1810). Or Seherdjo
Jakarta, Indonesia
ITALY
Monsintb Itailana Sp.A. Via MaMthrra Obit 0 Mffeno 30134, Italy
Bfonaanso Japan Ltd. Raom 317, Whin Kokusa! Bldg. 4-t. Bteruhouchi 3-choma Chtyodaku, Tokyo, Japan
Monsanto fa/ East Ltd.
(MelerUe Branch)
- ItO.MenBsmeogat
.
; PataHng Jaya, Selangor, Malaysia
MEXICO
Monsanto CotnercUSA. daCV. Thiers No. 948 Mexko 8. O.F., Mexico
NETHERLANDS Monsanto 8. V. Jan van Naasauttraat 53-56 Dan Haag Holland. Tha Nethertend*
NEW ZEALAND Monsanto Naw laaiand t td. 19 Oraat South Road Ramuara Auckland 8. Naw Zaaland
NICARAGUA Monsanto (Nicaragua) S A P. 0. Bom 3BB Managua, Nicaragua
NORWAY Monsanto Norge AS. Fred Qtmnsgeta 11 Oslo 1. Norway
PHILIPPINES Monsanto Philippines Inc Suita tIOt Security Bank 6 Trust 8788 Ayala Ava. Makati Risai 0 708. Philippines
PUERTO RICO Monsanto Puerto Rko Company Munot Rivera Ava. Bomlquen St. Rio Ptadras, Puerto Rko
Monmnto Singapore Company IPte.J L id Suita 708 Cathay Bldg.. 7d> Floor Mount Sophia, Singapore 9
SOUTH AFRICA Monsanto South Atrko (Pty.lLsd. 11th Floor, Sandton City Bldg. Sendton, Transvaal. South Afrka
SPAIN Monsanto tbarka SA. LapantaBSOS
SWEDEN Monsanto (Scandinavia) AB Xxhammarsaatan 27 Boras. Sweden
SWITZERLAND Motmnto (Suisse) SA Postfach
CH 9600. Lanaburg, BwlUarland
Monwtto Far East Ltd - (Tehran Branch) SO Ghana An Seat Road, dth Floor Section 1. nil
THAILAND Monaento Thailand Ltd. 6th Floor, Katamki) Bkfg. 120 Worn Road
, Ban&oh, Thailand
UNITED KINGDOM Monsanto Ltd. 1010 Victoria Street Monsanto House London SWW ONQ England
VENEZUELA Monsanto (Vanatualal CA Torre Phelps Pison 34 Plata Venezuela Caracas 101, Vanaauata
MOMS 078686