Document jg3b2o7gMojjrzY5dMOZ01O92
Operating Manual Old Unit PVC Reactors Page 1
III. OPERATING PROCEDURES (CONTINUED) D. Recovery General Information f The recovery system is designed to remove unreaqhed vinyl chloride monomer from a reactor batch that has reached a stage of polymeri zation where product quality is satisfactory. The objective is to remove as much of the remaining VCM as is possible from the reactor within as short a time as the recovery system can remove the VCM. Government regulations require that less than 400 ppm VCM can be left in the resin (averaged over all batches dumped in 24 hours) and a sample must be taken when the batch is dumped to verify com pliance with the regulation. The lead operator must start the re covery and monitor its progress from the control room. He must follow the given procedure closely to make sure that each batch is recovered to below the regulation limits. The reactor "A" operator will assist from the field and solve problems as they arise during recovery to keep the recovery system operating smoothly. It is essential that the "A" operator have a very thorough knowledge ofthe recovery equipment and how it works. This was described in de tail in the General Process Description beginning on page XX of this manual. Refer to Figure 5 in the Appendix for a sketch of the recovery system as needed.
DTH 000110207
Operating Manual Old Unit PVC Reactors Page 2
III. OPERATING PROCEDURES (CONTINUED) D. Recovery General Information (Continued) The steam stripping parameters to be reached and followed are posted on the control panel. Generally, for each product a differ ent temperature and hold time is specified. The reactor must reach the specified temperature and have a vacuum (below 0 psig) on it before the hold time can begin. Full cooling is put on the con denser at the specified temperature to keep from discoloring the resin. For 5385 in the old unit, 220F and a vacuum must be reached. Then full cooling is put on the condenser and the reactor is held for 25 more minutes on recovery with steam continuing to be put into the reactor. These parametes vary with weather, recovery system operation, and production requirements.
Procedure
The normal recovery procedure will be given below^ assuming that
all systems work as they are supposed to. Abnormalities in re
covery operations and troubleshooting will be given in the
&J .
-
"Troubleshooting" section following-the normal procedures.
1. The reactor is ready to be recovered when the "A" operator has finished killing the reactor and radios the lead operator that the reactor is killed. The following conditions must be met prior to starting recovery on a reactor:
DTH 000110208
Operating Manual Old Unit PVC Reactors Page 3
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued)
a. The reactor to be recovered must be killed.
NOTE: Recovery must not be started until the reactor is killed. This will prevent getting excessive amounts of initiated monomer into the recovery system which will cause polymer buildup in vessels and equipment.
b. The recovery system must not be in use on another reac
tor. If one reactor is recovering, the recovery on other __. -pmiVir.ed
reactors will have to wait until the recovery is #luhed
on the reactor that was recovering first.
c. There must be adequate room in the RVCM receiver that is set up to collect the monomer .removed from the reactor.
--^ If the level in the RVCM receiver is high, contact the Shift Supervisor who may give word to charge some 50% RVCM charges to lower the levels in the receivers, or to returnAthe RVCM receiver not: being used._
d. The recovery system must not be in use recovering a batch
water stripper. The emission recovery system normally is
used on the batch water strippers but if. it is not work
ing properly, the large reactor recovery system must be
used.
.DTH 000110209
Operating Manual Old Unit PVC Reactors Page 4
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued) Reactors must not be recovered while a batch water strip per is being recovered with the large system.
e. The steam stripping and recovery system must be opera tional with no maintenance work going on that will pro hibit using the systems.
f. A water stripper must be available to collect recovery system water drains. If both strippers are almost full, one must be stripped and emptied prior to recovering a reactor.
g. The pressure on the water stripper collecting the liquid drains should be 10 psig or less.
h. The recovery system should be ready to start up from the field. The following items should be given particular attention: - " s
(1^ The level in the knockout tanks should be at about
the midpoint of the sight glass. - If the. level is
abnormally low or high, the recovery system cannot
operate properly and the procedures given onpage -5HC for troubleshooting must.be followed to correct
the level.'
.
..
~ " DTH 000110210
Operating Manual Old Unit PVC Reactors Page 5
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued)
(2^ The manual valves on the knockout tanks should be set up to have^the recovery vapors enter the north knockout tank first, h then the south knockout tank. For efficient recovery system operation, both knockout tanks must be in service and must be used.
V^The n
t* ;nockout tank water flow should be routed through the re-
i circulation cooler and cooling water flow should be set up on the cooler as needed. In winter operation, the recirculation cooler flow may need to be throttled down to prevent condensa tion of VCM in the knockout tanks.
' 4) Seal flush flows on the vacuum pump and compressor seals should be shewing about of the flow meter and the pressures should be about 100 psig.
( 5) The level in the seal water separators should be high.. (The automatic drains are not operational at the present time). Low levels in the separators must be corrected prior.to com pressor" startup. At least one separator and pump must be operational, ami ,both\aa profarrod and must be used for most efficient operation of the system. One.pump will hot supply enough water for both compressors to run at the same time.
DTH 000110211
Operating Manual Old Unit PVC Reactors Page 6
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued) t
f s
161 All recovery vacuum pumps and compressors must be operational for best results in recovering. If any of the machines are not operable, the lead operator should be notified and a tag put on the switch on the panel so that it will not be started up.
NOTE: i Any vacuum pump or compressor that is not operating must be repaired and returned to on-stream operation as soon as possible, on a call-in or emergency work order maintenance basis. Both vacuum pumps and compressors are required or ex tensive downtime will be suffered waiting on recovery and/or
I residual VCM results will generally be higher than normal.
NOTE: If either vacuum pump, A or B, is inoperable, the
iMV S t~ corresponding compressor will-have-feo "be shut off
when the pressure switch diverts flow from the com
pressors to the vacuum pumps and the vacuum pumps
\%
--
start. The compressor can.be used only until the
point where vacuum pump is supposes to"come on,
then it must be shut down because it will lose
suction and seal water flow when the valves are
switched.
- .*
DTH 000110212
Operating Manual Old Unit PVC Reactors Page 7
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) /procedure (Continued)
t?f /f [/) At least one collect tank pump must be operating and set up
<'to one of the RVCM receivers.
C* The hydroquione system should be operational. This is
checked once per shift by the chief operator.
(9^ The knockout tank level pot flush should be operating.
[2. The lead operator will record the time on the batch sheet and start the recovery system by turning on the equipment as follows:
a. Turn on both recirculation knockout pumps.
NOTE: These may be left running all the time in cold weather conditions to prevent freezeup. The recovery compressors or vacuum pumps do not have to be running to keep the recirculation pumps running. V/V*
b. Turn on both seal water pumps and then push the run button on the switches for the'compressors to be started. The compressor $un^buttbn opens the compressor discharge and seal water valves
and will open tire vacuum pump bypass valve on the suction of the compressor, allowing vapors to be pulled directly from the knockout tanks into the compressor suction. The *AUTO* button. on the recovery compressor switch does not work..
DTH 000110213
Operating Manual Old Unit PVC Reactors Page 8
III. OPERATING PROCEDURE (CONTINUED)
D. Recovery (Continued)
Procedure (Continued)
The seal water must be flowing for the compressor to work.
NOTE; Do not run the seal water pumps without running
at least one compressor. The seal water pumps are tfah
dead-headed when the compressors are/lrunning.
3. The lead operator will notify the "A" operator that he is starting recovery on the reactor. The "A" operator will pro ceed to the second deck of the recovery system to wiithc\for foaming from the reactor when recovery on the reactor is started.
4. The lead operator will put the recovery automatic pressure con trol valve in manual and will close the valve. The setpoint should be at 30 psig.
NOTE: If the recovery system was already funning on another^reactor or the batch water strippers, this will be the first step to recovering a reactor following completion of the prior recovery or batch water stripping,
i
The automatic pressure control valve must be closed prior to
opening the reactor recovery and-condenser valves to prevent
foaming and to keep from-"slugging" the recovery system with
high pressure.
DTH 000110214
Operating Manual Old Unit PVC Reactors Page 9
III. OPERATING PROCEDURES (CONTINUED)
D. Recovery (Continued)
Procedure (Continued)
5. The "A" operator will notify the lead operator via radio when he is positioned to watch recovery startup. The reactor re covery valves are not to be opened until the "A" operator noti fies the lead to start the recovery, i.e. "You Can Start Re covery on D-300".
6. The lead operator will perform the following when the "A" oper ator notifies him that recovery can be studied on the reactor: a. Push the mode advance button on the reactor panel to put the reactor in the ^RECOVERY* mode.
b. Set the setpoint on the reactor temperature controller at 200F.
c. Lock out the cooling water automatic flow controller. This prevents cooling water leaking through and cooling off the the reactor during stripping.
d. Open the reactor condenser valve.
e. Open the reactor recovery valve.
7. The lead operator will put, the recovery automatic pressure con- .
trol valve in automatic and watch the pressure indicator as it
rises.
'.
DTH 000110215
Operating Manual Old Unit PVC Reactors Page 10
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued)
The valve should slowly open until the setpoint is reached, and the controller should not let the pressure overshoot the setpoint. If the controller does not work properly, it should be repaired as soon as possible (contact the Shift Supervisor).
8. The "A" operator will listen for foaming at the knockout tanks and will watch the bullseye. If any foaming occurs, he will immediately notify the lead operator and steps must be taken until the foaming is stopped (see "Troubleshooting", page XX). The "A" operator will observe the recovery for a few minutes and then notify the lead operator via radio that the recovery is OK, for example "Recovery Looks Good on D-300".
NOTE: The "A" operator should take the opportunity to check the water levels, flows and flushes of the equipment while on the second recovery deck and make sure that all* systems are operating properly. .A rl-t Troubleshooting and easily detection of problems by the "A" operator are crucial to smooth recovery system operation and good reactor recoveries.
DTH 000110216
Operating Manual Old Unit PVC Reactors Page 11
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued)
9. When the pressure starts decreasing on the reactor to the point where steam can be put on the reactor without rapidly increas ing the pressure, the lead operator will open the reactor steam stripping valve. This should occur about 10 minutes after recovery has started, if the system is pulling efficiently. If steam is turned on and the pressure is caused to increase rapidly on the reactor, it will take longer to recover the batch. The steam should be turned on by the time the reactor pressure has dropped to 60 psig. The steam flow controller will control the rate of steam put into the reactor. It is normally set at 5 roots of flow which is 14,000 lbs/hr. Settings higher than this will cause excessive reactor vibra tion during recovery.
10. The lead operator will check the steam flow after opening thereactor steam stripping valve to make sure it holds at.the setpoint.
11. At 170F, the cooling water flow indicator-should come up to 1-2 roots of flow and a small flow will- stay on the condenser for the rest of the recovery.
- DTH 000110217
Operating Manual Old Unit PVC Reactors Page 12
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued)
12. As the reactor temperature approaches 200F, the pressure
should be low enough that the vacuum pumps will come on. The
vacuum pumps for each compressor running will come on at
8 psig and the vacuum pump inlet, discharge, and seal water
valve opens. The vacuum pump bypass valve on the compressor
UJ tft''' suction and the compressor seal water valve closes (seal dts^
'Hs. T'A'-'-Hf 4 ft*
cj*5 charge).
'
The lead operator will watch and make sure the steam does not heat the reactor above 200F before the vacuum pumps come on. If the reactor temperature gets to 200F before the vacuum pumps come on, the steam stripping valve may have to be closed. On the other hand, if the vacuum pump should come on prior to the reactor reaching 200F, the recovery valve may need to be closed to allow the reactor to heat up.
13. When the reactor has reached 200F and the vacuum pumps have come on, the lead will move the temperature controller setpoint to 230F. Do not move' the temperature controller until both conditions are met.
DTH 000110218
Operating Manual Old Unit PVC Reactors Page 13
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued)
14. The reactor will continue to heat up and the pressure will drop. The specified temperature and a vacuum must be reached. If the reactor will not heat up to the specified temperature,
ha
the lead operator may rihve) to shut the reactor recovery valve. More often, the temperature will rise but the vacuum pumps will not pull the pressure off of the reactor. In this case the lead will shut the steam stripping valve until the pres sure drops below 0 psig.
NOTE: The lead operator must be careful not to leave the reactor at a high temperature for a very long period of time (more than 10-15 minutes). This will degrade product quality by discoloring the resin. If the vacuum pumps are not operating correctly, follow the procedures given in the Recovery Troubleshooting section of this manual.
15. When the specified temperature is reached and the pressure is
below 0 psig, the lead operator will put full cooling on the
reactot condenser by opening the emergency cooling water
valve. He will then record the time arid the temperature
reached in the appropriate space on the batch sheet. The re
actor is to be held for-the specified hold time after the
time is recorded.
DTH 000110219
Operating Manual Old Unit PVC Reactors Page 14
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued) 16. The lead will monitor the reactor temperature and pressure throughout the hold time. If the reactor temperatue does not begin to fall when full cooling is put on the reactor, the steam must be shut off until the temperature starts to drop. This must be watched closely becuase often the temperature will continue rising even after full cooling is put on the condenser. When the temperature starts dropping, resume the steam flow. If the reactor should come back above 0 psig, a problem with the recovery system is usually indicated, ^fhe The problem must be solved as soon as possible and the reac tor should be held at least 10 minutes beyond the normal hold reaamtdi, time after a good vacuum is reaebsd..
17. If another reactor must be vented during the vacuum hold time of the recovery, the following procedure must be followed: a. Close the recovery, condenser, steaim stripping, and emergency cooling water valves on the reactor being re covered.
b. Clbse the automatic recovery pressure control valve and vent the reactor that, needs venting per the procedure starting on page XX in this-manual.
DTH 000110220
Operating Manual Old Unit PVC Reactors Page 15
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued)
c. When the reactor has vented, pull the recovery system header back to the pressure of the reactor being re recovered.
d. Reopen the valves closed in (a) above.
e. Do not count the time another reactor was vented as part of the hold time on a recovering reactor.
18. Five minutes bofrg^the hold time has expired, the lead oper ator will open the main dump valve to recovery any VCM out of the reactor manifold (except on D-700JP, where VCM does not tie into the manifold^. If a spike of pressure is noticed when the
manifold was opened, leaky VCM valves may be indicated. The reactor should be pulled back to the vacuum and held for 10 minutes extra after the normal hold time has expired.
I) 19. Steam stripping is complete after holding the reactor for the
specified time below a vacuum or after pulling to a -gwoUr vacuum and holding for extra time , if problems occurre.d. The reactor recovery should be stopped as follows:
a. Advance the reactor mode switch to_*DUMP*. This should
close the reactor valves, and the lead will verify that
all valves close.
------
DTH 000110221
Operating Manual Old Unit PVC Reactors Page 16
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Procedure (Continued) b. Shut down the recovery compressors (if the system is not needed to recover something else) by pushing the OFF* button that is next to the *RUN* button on the compressor switches.
c. Shut down the seal water and recirculation pumps by push ing the motor stop switches.
The reactor is not ready to be dumped to the slurry blend tanks.
Troubleshooting Troubleshooting is very important concerning the recovery system. The "A" operator should keep a regular check on the equipment and solve any problems as soon as possible before they become major. He should inform the lead operator, chief lead, and supervisor of any major problems that are beyond his ability to repair. Good communication and prompt action is very important, and information about potential problems should be passed on to the next shift at shift change times. The safety of plant personnel is of primary
pfhSonr, c j concern, and banning any psasonai hazards, the protection of the equipment is the next concern.
DTH 000110222
Operating Manual Old Unit PVC Reactors Page 17
III. OPERATING PROCEDURES (CONTINUED)
D. Recovery (Continued)
Troubleshooting (Continued)
The first indication of recovery system problems is usually that the
recovery system "won't pull" or will not reduce the reactor pres
sure. This can be caused by one or more of several problems with
the recovery system. The "A" operator should first check the valve
line-ups and flows for the system and check the items as given for
rec&p rccedcures . S~fcep I h*
____
startup conditions under -fah^""n<wr
i * t n|W"n^
He should respond to problems that he finds according to procedures
given in this section. In any cse-case where the "A" operator
cannot solve the problem after taking the recommended approaches,
he should contact the sfai-ft operator or Shift Supervisor for
assistance and/or further instructions.
NOTE: Pressure readings are very important to diagnosing recovery system problems. It is the "A" operator's responsibility to keep pressure gauges changed out and in good operating conditions *W/
1. General Upset Conditions - The recovery sequence can be halted at any time during reactor recovery by isolating reactor using any or hll of the following valves: a. Reactor condenser valve. b. Reactor recovery valve. c. Reactor steam stripping valve. . . DTH 000110223
Operating Manual Old Unit PVC Reactor Page 18
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) The recovery system may also be shutdown and no personnel or equipment hazards result and a fairly long-term stable condition is obtained (water flushes^ may eventually fill up equipment and cause a hazard). This is the best option to take under any upset condition if the result of any other action is questionable. 2. Actuated Valve Malfunctions - The recovery system equipment will not operate and recovery cannot be accomplished if the actuated valves do not open and close properly and in sequence. For instance, a recovery compressor or vacuum pump will not start if the discharge valve does not open. When problems arise during recovery such that the system is not pulling correctly, every piece of equipment should be checked
and from it verified by checking the valve set-ups. Then the valve can be over-ridden }-*ir opened^ or closed per the procedures given in Section Q of this manual.
s. j -
3. Foaming (Resin Carryover) - Resin carryover ^EtsfB) into the recovery system during recovery is very seripus and can shut the system down in. a hurry; It will also - re<tcfc-t foul the condenser.tubes and cause extensive/\maintenance downtime because the resin will "bake" onto the tubes during steam stripping. Some of the things that will cause foaming are listed below.. These should be closely
Hui
DTH 000110224
Operating Manual Old Unit PVC Reactors Page 19
III. OPERATING PROCEDURES (CONTINUED D. Recovery (Continued) Troubleshooting (Continued)
checked when a foaming problem is discovered, a. Recovering too fast -This is why it is important to go
to one recovery compressor operation and to close down on
the pressure control valve when foaming is discovered.
b. Lip seal flush flow too high.
c. Sprayhead flush flow too high. Ths
d. Lip seal flowmeter bypass open - these, should only be
opened uponn Supervisor's approval.
e. Reactor seal blown. - Th tJ COvY CcOuVl Ujccf*
ri?*o/Uv)
]i- -fa fllf
f. Reactor batch size too big.
pc P ic
fit.
g- Excessive venting during polymerization. h. Bumping during polymerization. i. Change meter malfunctions -This should be exhibited by
the reactor quality results. If the reactor was
mischarged, the quality will probably be bad. Reactor
C-hlor^i~i kM.j
u&l,
cal.auLatins or reeeiver VCMAcalibrations may be taken to
verify that the meters are correct,
j. Reactor not empty prior to charge.
The following steps should be taken when the "A" operator
notices that a batch is foaming:
a. The "A" operator will immediately notify the lead
operator that the batch is foaming.
dth 0110225
Operating Manual Old Unit PVC Reactors Page 20
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) b. The "A" operator will check the position of the automatic recovery pressure control valve and make sure it is not more than half open. If it is more than half open, he will notify the lead operator and shift supervisor and the valve will need to be manually operated until it is repaired (a maintenance work order must be written). c. Upon notification that the batch is foaming, the lead operator will shut down one compressor. d. If this does not stop the foaming (check by radio with the "A" operator), the lead operator will put the automatic recovery pressure controller in manual and close down on the valve until foaming is stopped.
p. e. The lead operator will notify the Shift Supervisor of the problem and will note on the batch sheet that the bath bcdck.
foamed and what steps were taken to prevent it. The Shift Supervisor will note in this logbook that the batch f' foamed and give recovery details, also. f. If closing down^from the control panel does not stop the fbaming, the lead operator will have the "A" operator partially close the manual valve going into the knockout tank, until foaming is stopped. g. The "A" operator will flush the recovery knockout tanks
DTH 000110226
Operating Manual Old Unit PVC Reactors Page 21
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) as needed to keep the pumps running and pumping and the tanks draining. The tank should be thoroughly flushed after foaming is detected and corrected. Add water to the tanks using the HPSW connection on the pump filter pack.
NOTE: When flushing water into the tank be careful not
to overfill the tank. Monitor the tank closely. When
foaming is a problem, the leadAshould leave the knockout
tank pumps running all the time Jv
res/*
h. If none of the above steps stop the foaming, the shift
supervisor will advise what steps to take. The reactor
may have to be equalized with another reactor. For the (jL
reactor equalization procedure see Section 3* of this
manual.
i. After the reactor is equalized, be sure to give the u
reactor condenser^short rinse prior to restarting
l recovery. This will flush resin off of the condenser I tubes and prevent condenser fouling. The rinse should be
only 15-30 seconds long to prevent re-filling the
TP
reactor. Reactor foaming must be corrected as soon as r` ^
ecW possible when deleted-. Steps must be taken by the A"
DTH 000110227
Operating Manual Old Unit PVC Reactors Page 22
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Contineud) Troubleshooting (Continued) -f operator to idei^.fy the source of the foaming. This may include: Jec^L a. Coming back to the second eieek- of the recovery Yo system frequently to check for foaming- and^listen for foaming. b. Watching and/or listening for foaming when the vacuum pumps come on. c. Watching and/or listening for foaming when a reactor is vented. 4. Recovering a Reactor Killed Early - Special recovery procedures should be followed when a batch is killed early. When a batch is killed prematurely there is a much greater possibility that foaming will occur during recovery. This may i~re u. & hvi* 'f't require equalization into another reactor. Follow the^steps given in Number 3 (above) for foaming problems. Since the reactor may have a higher than normal pressure when recovery
? is stated on an early kill batch, some special precautions must be taken when starting the recovery systems aSfollows:
DTH 000110228
Operating Manual Old Unit PVC Reactors Page 23
III. OPERATING PROCEDURES (CONTINUED)
D. Recovery (Continued)
Troubleshooting (Continued)
a. Only use one compressor when recovery is started on the
"early killed" batch.
Follow normal recovery system and recovery start up
procedures. Remind the "A" operator that the batch was
killed early and that foaming will likely be a problem.
c. Close the recovery pressure control valve before
recovery is started, per normal operating procedures.
After recovery is started and the recovery lines out
start the other compressor. Have the "A" operator check
for foaming when it is started.
,< /
e. Steam may need to be periodically added to the^batch if
it cools off. The lead operator must be careful when
adding steam adn should watch the reactor pressure
closely while adding the steam. Most of the recovery
:o' L /should proceed without steam on until the reactor vit'j <r~i p-t lv pressure drops to about 50 psig and stays/\fehere with
--7* steam on.
~Z> f. Recovery the batch per normal operating procedures just qs. rjr -like a full batch of resin was made. A residual sample
=r
on any PVC made must still be taken and the result will cestuit-v/
affect the daily^verage.
DTH 000110^29
H. /
Operating Manual Old Unit PVC Reactors Page 24
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) g. If the lead operator needs to "get off" of recovering the early killed batch to use the recovery sytem elsewhere, cu-d. the steps |4cf^ above must again be followed prior to returning to recovering the early killed batch. This includes if another reactor is vented, recovered, or if the batch water stripper pressure is lowered using the big recovery system. 5. Knockout Tank High Level - The recovery system will not operate as efficiently if it has to pull the vapors through a large head of liquid in the knockout tanks. A high level should be automatically drained by the pumps to the Batch Water Stripper. THe level should normally be halfway in the sight ^lass. Reasons for the tanks not draining and giving a
high level may include: a. Pump 4)lain lines plugged - Flush the lines with HPSW or^
if necessary, have maintenance pull and clean the line. b. High pressure on the Batch Water Stripper -"This will
especially affect knockout tank draining if the pressure oh the knockout tank is very low, during the vacuum part of recovery. It may become necessary to stop recovery of the reactor long enough to pull the Batch Water Stripper pressure down so theypumps will drain|the knockout tanks.
DTH 000110230
Operating Manual Old Unit PVC Reactors Page 25
III. OPERATING PROCEURES (CONTINUED
D. Recovery (Contined)
Troubleshooting (Continued)
,
-f c. Pump suction line o*b4he-pmnp--i-teoolf betng plugged - tr
to flush the line and/or pump and have maintenance pull
and clean these if necessary. This can be isolated as the problem if the pump will not pump either back to the
tank or to the low pressure Batch Water Stripper.
Flush the knockout pot level controls on the side of the
tank. These may be hung, keeping the drain valve from
opening./The tank may need to be drained manually by
opening the manual drain valve to the Batch Water
Strippers, but the knockout tank pressure must be greater Mr
than stripper pressure Xc the level to drop.
6. Knockout Tank Low Level - A low level in the knockout tank
will cause the pump to lose suction and there will be no
cooling in the tank. This will heat up the recovery vacuum
pumps and compressors to the point where they kick the
breakers. Once the*level is lost in the tank, it must be
manually isea^ixad because there will be no cooling to condense
anything into the tank. Water should be added to the tank to
keep the level showing in the sight glass
preferably
about halfway in the sight glass). Possible causes of low
level in the tanks include:
DTH 000110231
Operating Manual Old Unit PVC Reactors Page 26
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting a. Automatic drian valve not closing on low levelsFlush the level controls on the side of the tank. The level pot may be plugged or the floats may be hung. b. Manual drains leaking through to the sewer or to the batch water stripper^1* This should be evidenced by VCM
~r readings in the area or high pressure on the strippers. leech Have/(valve changed out or repaired as soon as possible,
c. Pump discharge or recirculation cooler pluggage^-- This will prevent water flow to the spray nozzles and condensation in the tank will cease. The level could be low due to evaporation of liquid from the tank due to high temperature. Have maintenance pull and clean the lines or bypass the recirculation cooler until it is . - <n clened and returned to service.
7. Knockout Tank High temperature - This will' cause problems as mentioned in item 6 (above). The causes, could include: a. Pump discharge or recirculation cooler pluggage - fbllow v steps given in 6c (abope). b. Not enough cooling water on the- recirculation cooler ~hese. valves are manually cut back at times to prevent VCM condensation in the tank. c Low level in the knockout tank--See item 6 {above).
- .DTH 000110232
Operating Manual Old Unit PVC Reactors Page 27
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) d. Excessive overheating of a reactor batch controllers and indicators may need checking. During the high temperature part of recovery in the old unit, a high knockout tank temperature is normal because there is not enough heat removal capacity at the present time. 8. Liquid VCM in the Knockout Tanks - VCM condensing in the knockout tanks will cause slow recoveries because the compressors have to do extra work to "re-vaporize" the VCM. This condition is evidenced by "frosting" or "sweating" on the knockout tanks. Heat must be added to the tanks to expedite vaporization of the VCM. This usually must be done by hooking up a steam hose to the tank. This should be performed very carefully and must be monitored the entire time the steam hose is removed, **Hhe cooling water to the recirculation cooler should be partially closed to the point where the tanks willnot get too hot but4VCM will not condense in the tanks. 9. Knockout Tank Pumps Will Not Pump - This is' a serious situation that will greatly hamper recovery system efficiency. The pump and/or suction and discharge lines should be given immediate attention to get the knockout tank pump back into proper operation. When the "A"-operator is aware-of this problem, he should contact the lead operator and the Shift
should be informed. The situation should also
DTH 000110233
Operating Manual Old Unit PVC Reactors Page 28
III. OPERATING PROCEDURES (CONTINUED)
D. Recovery (Continued)
Troubleshooting (Continued)
be noted in the Supervisor's logbook and should be corrected
on a high priority basis. The basic problem is usually
reactor foaming which should be watched closely to solve the
problem.
10. High Compressor Discharge Pressure - The machines are rated
for a 80 psig maximum discharge. At 80 psig on the discharge
the compressors will
recover^ vapors from the reactor very
aieeitt^ and may cause the vacuum pumps and/or compressors
to kick the breakers because of high amperage. Common causes
of hig compressor discharge pressure include: a. High receiver pressure -^inerts should be vented from the
receiver to keep the pressure at or below 80 psig on the
compressor discharge. b. Collect tank pumps not pumping - ,2t may be necessary to
switch pumps and/or discharge lines to get the VCM to
flow to the rehdivers. Pluggage would be indicated by
high pressure on the collect^ tank .or pumps and lower
pressure in the receivers. It may also become necessary
to switch receivers being pumped to. c. Not enough cooling water on the condensers - Check the
inlet, and outlet valves. They should normally stay wide
open.
-
'
DTH 000110234
Operating Manual Old Unit PVC Reactors Page 29
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) d. Lines plugged between condensers and collect tank Pressures on each side of the plug will indicate this condition. The affected section of line can be carefully flushed with HPSW to try to break the plug. D not exceed rupture disc pressures on the collectiank or recovered condensers. Maintenance may be required to clean the line e* a temporary connection made with a flexible stainless steel hose. e. Plugged condensers -T^his may be indicated by pressures -fi-i or by ^temperature of the VCM leaving the condensers (it should normally be cool). The condensers can be flushed carefully as indicated in d (above) but may have to be drilled out by maintenance. 11. High Amps on Vacuum Pumps/Con^essors - Vacuum pump and
compressor amperage cfan be monito^d from the control panel and
should normally run about 150 amps for the compressors
100-i?#- amps for the vacuum pumps. Extended time at levels
above these will cause the machines to kick th^breakers.
Causes may included:
-
a. High compressor discharge "pressure - (See item 10 above).
DTH 000110235
Operating Manual Old Unit PVC Reactors Page 30
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) b. High vacuum pump discharge process -JEndicates a problem with the compressors not pulling properly. Check pressures, temperatures, and seal water flows for the compressor-?, c. Seal Water flows not correct - seal wat(f flow should be 40 gpm. Move the setpoint to make sure the control vavle is working and check the seal water valves to make sure they are open or closed as they should be. 12. Compressors/Vacuum Pumps Kicking the Breaker - This may be caused by: a. The machines pulling high amps for an extended period (2-5 minutes or longer) of time - See item 11 (above). b. Malfunction of breakers or heaters. c. Mechanical problems with the equipment causing high amps. 4. The machine^ should be thoroughly flushed to make sure it is not plugged with foam or res-in before a mechanical work order is-made out. 13. Seal Water Flow Abonrmal - This will cause the-vacuum pumps and compressors to run inefficiently- and may cause them to run hot or kick the breaker. Seal'water flow should be 40 gpm. a. Low seal water separator levels^"* If these are low, the flow will be low. HPSW can be.added to make-up the level
. DTH 000110236
Operating Manual Old Unit PVC Reactors Page 31
III. OPERATING PROCEURES (CONTINEUD) D. Recovery (Continued) Troubleshooting (Continued) b. The flow control valve positions should also be checked to make sure the valves are open. The flow indicator will not always give the correct flow and may show 30 gpm when the valve is closed. The setpoint may have to be adjsuted to get the flow control valve open. c. Seal water pumps kicked out - i^eset the breaker and Jx oi watfrrh for problems auasing the pump to kick out. d. Seal water filter plugged -This would be indicated by pressure gauges around,the filter. Change out the filter element; if needed. e. Seal water subcoolers not working - if the seal water gets too hot, it may try to vaporize and will cause flow problems. If the seal water temperature gets too low, VCM will condense and cause problems in the compressor as it tries to act like seal water. The temperature out of the subcoolers should be 100-150F to keep the machines running efficiently. f. Actuated valves not properly lined up - when the compressors are on, flow should go to each compressor. When the Vacuum pumps come on, the valves to the compressors close and all the flow is fed through the vacuum pumps.
DTH 000110237
Operating Manual Old Unit PVC Reactors Page 32
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) 13. Seal Water Separator Low Level - This will cause the seal water flow to the recovery machines to be abnormal and the machines will not do their job. The tanks should be maintained at least half full. HPSW may be added to the tanks if the level is low. Causes for the low level may include: a. Automatic drain valve stuck open - flush the level controls to get valve to operate properly. Maintenance on the level controls may be required. These are disconnected in the old unit and the valves stay closed. b. Manual or automatic drains leaking through to the sewer or batch water stripperi(" This should be evidenced by VCM readings in the drain area or high pressure on the strippers. Have maintenance repairs made as soon as possible. c. Tubes leaking in subcoolers -"The process pressure is
typ-inasbiy greater than the cooling water pressure in the subcoolers. Water may be lost to the cooling water return header, causing a low separator level. d. Leaking seal on a machine and no seal flush water*"* This would most likely give high VCM- readings in the area and the/^loss would probably be~very slow. 7^ 14. Vacuum Pump or Compressor Seal Blows Out - This will be evidenced by large amounts of water leaking from the machine
DTH 000110238
Operating Manual Old Unit PVC Reactors Page 33
III. OPERATING PROCEDURES (CONTINUED)
D. Recovery (Continued)
Troubleshooting (Continued)
seal area and from VCM reading}^in the area. The "A" operator
will:
a. Have the lead operator immediately shut down the piece of
equipment and notify the .Shift Supervisor. `
b. Secure proper respiratory protectipn/and, an/HNU toy
monitor readings.
OMn tih '5
/ ',
c. Isolate the piece of equipment and properly depressurize it with hoses or piping to a vacuum source.
15. No Seal Flush Flow - The seal flush flow will be checked regularly by the "A" operator. If^seal flush water will not flow to or from th^e seal he should check the piping and try to "slug" it to break the plug loose. If this is not successful he must notify the Shift Supervisor and an
approximate work order must be written if the flow cannot be regained. Seal flush flow is essential to long seal life and
ij to keeping VCM readings in the area down.
16. No Steam Flow to Reactor -.If there is no steam flow to the reactor being recovered according to the flow Indicator, the following problems may be- involved:
DTH 000110239
Operating Manual Old Unit PVC Reactors Page 34
III. OPERATING PROCEDURES (CONTINUED) D. Recovery (Continued) Troubleshooting (Continued) a. The instrument may have malfunctioned and steam is getting into the reactor. However, there may not be any control over the flow so this should be monitored by the "A" operator until the instrument is repaired. It may be necessary to bypass the controller manually and regulate the flow with the bypass valve. b. The actuated steam valve on the reactor may not be open. Have the "A" operator override the valve and have it repaired if necessary. c. The line may be plugged - pressure is normally kept on
the line that is higher than reactor pressure so that if
a valve leaks, slurry will not get into the steam header.
Check the stem bleed that pressurizes the header after
having the line cleared.
DTH 000110240
17. Winter Operation - In severe cold weather (below 32F), it is i> -
best to keep the recovery system runtiing all the time. This
will keep the water in the system from freezing and will keep
the system warm. The system can be put on the batch water
strippers to recover them if not needed elsewhere, or can run
on the feedback RVCM. This may necessitate running only
compressor and vacuum pump, because the feedback RVCM volume
T1 ' is not large enough for-both recovery machines*-but-the seal,
water pumps and knockout tank pumps-can remain running.
. J! a/, 'kr'
Vw t*
diu. /VA^ 4 i/4Cud*#*. OL*id l\(tA dh /? epAtS^h o^c/i 'jda ydueo
A Uaktys/ 0*4 ad a. d>n^ , Frps4i<j ^ il# &*cfsk4 ^ ^
vJU. i*di**d*s~^ One/ j^d d&a>^d^eu*i ^ <f/a y'aJu? fi(/{/ii^r
Zc/$ l*t&
fjucvJt--k--*& i>Ji
fop'/i dy yd*
bjHit A*^JA
* tM*i/&U&1 UJrtd/e^ ^ fo
.
DTH 000110241