PAMPA RFA 331-571 PLANT BREATHING AIR SYSTEM
-MOB-
Capital Expense
Total
$321,000 30,000
$351,000
Pampa Plant requests $351,000 to assure that all users of breathing air are supplied with breathing quality air that meets OSHA requirements.
Presently, the breathing air system consists of tie-ins to the instrument/ service air system with backpacks being provided for emergency use. The instrument/service air system is also used as a source for various.process uses. On several occasions, process chemicals have been identified in the system.
The breathing air system having instrument/service air as its supply is not safe, in our opinion, and is in direct violation of OSHA standards due to process interconnections, lack of proper supply filtering and no continuous contaminant monitoring.
The proposed facilities will provide a separate breathing air system to include purification of compressed air, plant wide distribution network and in-unit distribution. Total carbon and carbon monoxide monitors will be part of the new system as well as marked lines and strict conformance to the plant connection standard. Alarms will be provided to warn of any con dition causing loss of air quality or quantity.
The new facilities will ensure that all breathing air is safe and will meet OSHA requirements.
Funds for this project are included in the 1981 Capital Plan ($731M) and Expense Budget.
This project will not have any impact on Plant Energy Consumption and will not require additional headcount.
Facilities will be operational 10 months after approval and will be closed 13 months after approval.
MAJ :mb
010519
"YlUcST FCH APPRCr'IUAribfr
V, `*ii**'*eiT.
^ni~i*&
IV. Timing
This project will be operational 10 months after funds approval and closed 13 months after approval.
V. Engineering & Construction
Engineering and construction will be done by the Pampa Engineering/Maintenance Department, utilizing contract draftsmen and labor as required.
VI. Patents No patent infringement or patentable items are involved.
VII. Headcount
No change in headcount will result from this project.
456* < >2 6T
* ESTIMATE SHEET
A
TITLE
Plant Breathing Air System
ESTIMATE NO
331-571
WO
LOCATION
ITEM
1 Equipment
DESCRIPTION
DATE DEPT.
2-23-81
Engr./Maint.
CAPITAL
MATERIAL
LABOR
Monitors and Purifiers
35,000 -
6,000
SHEET
1 OF
1
expense
MATERIAL
LABOf
2 Piping Headers, Manifolds and Supports
55,600 96,100
3 Instrumentation Alarms and controllers
7,500 7,200
4 Electrical Equipment and Building
5,000 7,000
5 Painting and Marking 6 Building
4,000 10,000 7,000 7,000
Direct Material & Labor Engineering Construction Overhead Escalation Contingency
114,100 133,300 22,000 30,000 13,200 11,400 14,000 13,000
Total Material and Labor Total Capital and Expense Total Project
APPROVED
163,300 157,700 30,000
321,000
30,000
351,000
- U1
DATE
~
OCN 2Ji
COMPARISON OF ALTERNATIVES
FINANCIAL COMPARISON OP ALTERNATIVES
TOTAL INVESTMENT
LONG TERM OPERATING INCOME
DCF RATE
EXTRA INVESTMENT ABOVE NEXT LOWER ALTERNATIVE INCREASEADECREASEIIN LONG TERM AVERAGE OPERATING INCOME AFTER TAX OVER NEXT LOWER ALTERNATIVE DCF RATE ON EXTRA INVESTMENT
PROPOSED
* 351,000 s
s s
*
ss
si
X
DESCRIPTION OF ALTERNATIVES
ALT. n
ALT. I
* 711,000
i
X
t t X
Alternate it 1
The funds noted ($711,000) would provide a totally separate system to include air compressors and purifiers as well as a high pressure back-up and bottle filling compressor. The proposed alternate will fulfill all existing OSHA requirements and plant considerations.
Notes:
1) - All Chemical Co. plants were canvassed and information obtained as to known OSHA
violations, design requirements, and current practices. Because of their limited
usage compared to ours. Bay City and Clear Lake can and do use bottled air. Bishop
is currently reviewing their system.
*
2) Bottled air alternate was considered for use at Pampa and was found to be far in excess of the $711 M considered in Alternate I. This is due to a combination of usage rates and availability to Pampa.
3) Portable compressors for localized use were also considered and discounted due to
reliability, $'s required for turnaround sizing, maintenance requirements and service contaminants monitoring.
-010523
VtRONMENTAL CONTROL DATA
flP A NO,
331-571
PLANT
Pampa
Ol VISION
Chemical
AMOUNT OF ENVIRONMENTAL CONTROL EXPENDITURE IN PROJECT
CAPITAL EXPENDITURE
|
PROJECT EXPENSE
|
TOTAL COST
AMOUNT
loocru
total capital
AMOUNT 1000's!
% TOTAL EXPENSE
AMOUNT (COO* l)
K total Capital A NO gXPSMSc
(
None
UST ANO SUB TOTAL BY MATERIAL controlled
None
MAJOR ITEMS OF ENVIRONMENTAL CONTROL EQUIPMENT
ITEM
CAPITAL IOOO'iI
EXPENSE IQOO'jl
None
total, cost (OOO-Jl
v. TOTAL, CAPI tav_ A,'
r XPENSc
TOTAL EXPENDITURE
BRIEF DESCRIPTION OF THE PROBLEM. TYPE OF TREATMENT TO BE USSO ANO THE ANTICIPATED QUANTITATIVE RESULTS
010524
A
>a < o Xm 2 o >r
vt
r>
rr
nm 2m 9O <
oz 3o n& o
2 X3
ft (CDD 3
rr
no CO2 T3C3
rr
HO* 3
zo >
> s
5*
mm 1 -t*O< *oo
i/%
I1MKK IVIM I t n l H L O M IM U C lU C m j I
SOURCE SUMMARY
INSTRUCTIONS ON RACK
HFA N O ' ~ ~ ~
c o m p a n y _____Chemical 2-23-81
DATE ___________________
010525