Document jBm39DjMMmrZjymg6G9Dav419
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02 14-JUN-1996
PAGE I OF 5
ELECTRICAL SAFETY AND RELIABILITY AUDIT CHECK LIST ELECTRICAL ROOMS
RBUILDING NUMBER/LOCATION I.D. #:
/_<~/ 3--
Doors/Exits
Yes No N/A
1. Are there two means of egress from the room?
2. Are the doors equipped with good working panic bars? [LPP]
3. Do all doors open to the outside?
4. Are the doors seif closing?
5. Are there warning signs posted on the doors? (i.e. DANGER: HIGH VOLTAGE)
6. Are the Exit Doors identified with Exit Lights or Sign?
Doors/Exits Index Score
Lighting
Yes No N/A
1. Is lighting in good condition and lighting level adequate?
2. .Are all lamps burning?
3. Is there a good working emergency lighting system? [LPP-356]
4. Is the Exit Sign Lighting working?
Lighting Index Score
Environment
Yes No N/A
1. Is the air conditioning system in good working condition? (Temperature, Humidity)
2. Is the air conditioning system isolated for switch room service only?
DO A 045014 CONFIDENTIAL
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02
14-JUN-1996 PAGE 2 OF 5
3. Is the noise level acceptable?
4 . Are measures taken to keep water/ice out of the room or cable cellar effective?
5 . Are openings in the walls, ceilings, floor, or cable cellar properly sealed?
Environment Index Score:
1
Housekeeping
Yes No N/A
1. Is the room clean and uncluttered?
2. Is the floor vacuumed instead of swept with broom? (Broom stirs dust)
Housekeeping Index Score
Access
Yes No N/A
1. Is there adequate access and clearances for the electrical equipment?
2 . Is the cable cellar easily accessible?
Access Index Score:
3
Drawings
Yes No N/A
1 . Is SEOLD posted properly in the room? 2 . Are drawing accurate and up to date?
Drawings Index Score:
------
y
DO A 045015 CONFIDFNTTAl
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02
14-JDN-1996 PAGE 3 OF 5
Labeling
Yes No N/A
1. Is the room identified with a formalized building number?
X____
2. Is the equipment in the room adequately labeled?
Labeling Index Score:
Fire Protection
Yes No N/A
1. Is the room separated from control room with a
2 hour fire barrier wall? [LPP]
J____
.2 Is there a smoke and/or fire detection system
in the room? [LPP-356]
3. Is the Smoke and/or Fire Detection System annunciated?
X
4 . Are all wall-penetrations closed with Fire Stop materials? [LPP]
5 . Is the room free of stored combustible materials?
6. Are the proper fire extinguishers
the room?
ated in
7 . Does room have fire retardant walls and doors to oil-filled transformers or process area?
Fire Protection Index Score:
DO A 045016 CONFIDFNTIAl..
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02
14-J0N-1996 PAGE 4 OF 5
BATTERY/UPS SYSTEMS
Yes No N/A
1. Is there a preventive maintenance schedule for UPS systems. Battery Banks, and Battery Chargers?
2. Is the battery rack grounded?
3. Are the battery posts and terminals free of corrosion?
4 . Is the battery charger in good working condition?
5. Is the battery room or location designed according to the appropriate standards?
____ ____
o. Do batteries have the proper water level?
Battery/UPS Systems Index Score:
Other
Yes No N/A
1. Is there Flash protection clothing/equipment in the room?
2 . Has all process piping been routed itside the switch room?
3. Is there a written set of Elecftta Emergency plans for various situations like loss of power, fire, or smoke in the room? [LPP]
4 . Is there room to grow?
5 . Is there a preventive maintenance schedule for the room?
6. Are the cable raceways in the room/cable cellar in good shape?
X
7 . Are the cable raceways in the room/cable cellar overloaded?
8. Are all the cable raceways in the room/cable cellar properly leaded?
_
DO A 045017 CONFIDENTIAL
THE DOW CHEMICAL COMPANY
ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-02 14-JUN-1996
PAGE 5 OF 5
9. Are there appropriate clearing procedures and operating procedures for electrical equipment in the room?
N/A
10. Is communication equipment available in the room?
11. Is the steel structure of the room properly grounded?
12. IS ttlBJTG a rrrrinnH har atrai 1 ahla -fn ^ H a room/cabl
DO A 04501,8 CONFIDENTIAL