Document jBaaepeaQOm0JrVnrng75GMnk
212
CHAPTER 13
1960 Guide
the room load,
^ . Use the equation
hi -- h, Wi -- Wt here
(Space sensible load + space latent load)
Space latent load/1076
(18)
h, = enthalpy of moist air supplied to the space, Btu per pound of dry air.
hi = enthalpy of moist air at room design conditions, Btu per pound of dry air.
W, humidity ratio of moist air supplied to the space, pounds of vapor per pound of dry air.
Wi humidity ratio of moist air at room design conditions, pounds of vapor per pount of dry air.
Note that the ratio (space latent load/1076) is the equivalent
of the required rate of water vapor removal in pounds per hour. If the rate of water removed is known, it may be used directly in Equation 18.
3. Draw a line through the reference point on the ASHAE Pstchbometric Chart and the value of (hi -- h,)/(Wi -- W,) determined above. Draw a second line through the state point,
of the room air (design wet-bulb and dry-bulb temperatures)
parallel to this line. This is the condition line for the process.
4. Read the temperature where the condition line from step 3 intersects the saturation line. This is called the apparatus dew point.
See Fig- 6. Note that instead of using this graphical method the left band side of Equation IS may be solved by trial and error by substituting values of h, mid W, corresponding to assumed apparatus aew-point temperatures.
6. Compute the required air quantity from the relation
& I - (,, -
/ (l.OS "\
Apparatus'^
load / ( |_\dry-bulb/ \dew-point /J
X (l - bypass')} (16)
\ factor / J
The magnitude of is substantially the quantity, cfm, of cooled ana dehumidified air for which the distribution system must be designed.
The numerical factor 1.08 is derived from the product 1
cfm X 60min X 0.244 X 0.075(l - ^23) - 1.08, assuming
an average supply air dew point of 55 F. Since standard air density (0.075) includes the weight of the water vapor, it is desirable to reduce it to the basis of dry air by the last factor where 0.00923 -- humidity ratio of air at 55 F dew point, and 0.62 = ratio of density of water vapor to dry air at same tem perature and pressure. Refer to Chapter 23 for coil selection.
Note that the product {(space dry-bulb) -- (apparatus dew point)] X (1 -- coil bypass factor) is equal to tne diy-bulb range through which toe conditioned air is cooled. Hence, in rare instances when the condition line of the process may not intersect the saturation line, any other convenient reference temperature on the condition line may be used instead, pro vided that the coil bypass factor is specified accordingly on the proper basis.
MINIMUM ENTERING AIR TEMPERATURE
Due consideration must be given to the temperature of the air entering the conditioned space in order to prevent ob jectionable drafts. With ceiling-type diffusers or wall grilles with a high aspect ratio (see Chapter 20), many engineers consider 20 deg as the maTTimim difference for good dnqigp under average conditions. This difference can only be exceeded with extremely high ceiling outlets or wall grilles. Thus, if 80 F dry-bulb is to be maintained in a space with average ceiling height, the minimum delivered air temperature would be limited to about 60 F dry-bulb temperature. If the latent
heat load is relatively high, it is often necessary to circulate more air with a higher delivered dry-bulb temperature in
order to produce a thermodynamic balance. If the dry-bulb temperature of the air supplied to the space is known, the required air quantity can be calculated from the formula.
<? Qr 1.08 (U - tt)
(20)
or the supply temperature i, can be determined as follows,
(21)
EXAMPLE--COOLING-LOAD CALCULATION
Example It: A one-story office building Fig. 6 is located in an eastern state near 40 deg latitude. The adjoining buildings on the north and west are not conditioned, and the air tem
perature within them is known to be substantially equal to the outdoor sir temperature at any time of the day.
South wall construction: `8-in. concrete block, 4-in. brick veneer. (Table 7, Chapter 9, U - 0.41.)
East wall and outside north wall construction: 8-in. con crete block, no plaster on walls. (Table 6, Chapter 9, U = 0.52.)
West wall and adjoining north party wall construction: 13-in. solid brick, no plaster:
+f+
OI- v-oxa. Uf7-058.
Roof construction: 2^-io. flat roof deck of 2-io. gypsum slab on >-in. asbestos cement board suriaced with built-up roofing. (Table 13B, U -- 0.34 Jot summer.)
Floor construction: 4-in. coocrete on ground.
Window: 3 ft x 5 ft, nonopening type, with medium colored Venetian blinds for windows on south wall. Approximately 4-in. reveal on all windows.
Front doors: Two 2 ft-6 in. x 7 ft (glass panels).
Side doors: Two 2 ft-6 in. x 7 ft 04 glass panels).
Rear doors: Two 2 ft-6 in. x 7 ft (wood panels).
Outdoor design conditions: Maximum dry-bulb 95 F, wetbulb 78 Fj W, = 0.0168 lbs vapor per lb dry air; h, -- 41.38 Btu per lb dry air.
Indoor design conditions: Dry-bulb 80 F, wet-bulb 65 F; Wi =* 0.0098 lb vapor per lb dry air; A< 29.95 Btu per lb dry air.
Occupancy: 85 office workers.
Lights: 12,000 watts, fluorescent; 4000 watts, tungsten.
Fan motor: 1)4 hp.
Cooling Load
cooling coil has a bypass factor of 0.15, i.e., that 15 percent of the air passes through the coil without con tacting the coil surface.
Conditioning equipment to be located in adjoining1 structure to north.
Find: Total, sensible, and latent maximum cooling loads and required air quantity through conditioning equipment.
Solution: From Table 3, the recommended ventilation rate is 15 cfm per person. Total necessary - 85 X 15 - 1275 cfm or 76,500 cu ft per hr.
As the room volume is 40,000 cu ft, the air changes per hour will be 76,500/40,000 " 1.91 which is more than one air change.
Estimated Time of Afoxtmum Cooling Load:
For this job, judgment indicates that the roof will make the
greatest single contribution to the cooling load. Hence, the
time of
cooling load probably will be the time of
maximum heat g*in through the roof. From Table 9 the maxi
mum temperature differential for a 2-in. gypsum roof of me
dium weight construction is 54 deg at 4:00 p.m., and 63 deg
at 3:00 p.m. Examination of Table 12 (40 deg N Latitude)
shows that solar heat gain through glass on the south wall is
18 Btu per (hr) (sq ft) at 4:00 p.m., and 42 Btu at 3:00 p.m.
This indicates that the maximum cooling load occurs at ap
proximately 3:00 p.m. Therefore make load calculations at
3:00 p.m. sun time. (This may be slightly different from 3:00.
p.m. local time.) In some cases, there would be no clear-cut
evidence of this nature, and consequently, it would be neces
sary to estimate the load for several successive times, and then
to select the maximum.
Heat Gain Through Outer Wall and Roof Areas:
From Table 10 the temperature differential for the south wall (8-in. concrete block with 4-in. brick veneer) may be about the same as a 12-in. brick which is 6 deg at 3:00 p.m. for a dark colored wall. From the same table, the temperature differential for the east wall (8-in. concrete block with plaster) will be 11 deg at 3:00 p.m. for a light colored tool! (interpolating be tween 2:00 and 4:00 p.m.). Likewise, the temperature differ ential for the north exposed wall (8-in. concrete block plus
8laster) will be 3 deg at 3:00 pm. (by interpolation) for a ght wall.
The party wall of 13-in. brick on the west Bide and.part of the north side may be treated as if it were an outside wall in the shade which has a temperature differential (from Table 10)
of 2 deg..
For the door in north wall, estimate U = 0.59 from Chapter 0. The outdoor temperature at 3:00 p.m. is 95 F. Neglect time lag and any decrement factor. The temperature differential is (t, -- I*) -- 95 -- 80 15 deg. The tabulation of the preced ing values at 3:00 p.m. is given in the following table:
Sscno*
Mn Sc Ft
TntrtxAnu
Dam-
zvtial
F Dbg -
Hut
Tununcion Cosm-
asm V
Hut
Flow
TORati
Hotm Bto
Roof South wall East wall North exposed wall West & north party wall Door in north wall
4000 405*
765* 170*
1065*
35
53 6 11 3 2 15
0.34 0.41 0.52 0.52 0.26
0.59
72,000 995
4,380 265
550 310
78,500
" Cskutsted from grow mil Arcs, lea windows and door*.
Heat Gain Through Glass Areas:
In computing the load for 3:00 p.m., only the south windows and doors will be exposed to direct sunlight. Tables 12 and 13 will give the total heat gain from the glass areas. The window reveals will shade the south windows; the fraction of the
213
wiodcrw area receiving direct radiation is obtained from Equa tion 5 by substituting values as follows:
r, = s/I - 4/60; r* - 4/36; 0 - 45.5 deg, tan 0 =* 1.02
y =* 74 deg, tan y * 3.487, cos y -- 0.276
4 / 1.02 \ 4 60 \0.276/ 36 R1S7)
/ 4 \ / 4 \ M2M3487) _
` \60/ \36/ 0.276
The south doors will be considered entirely sunlit. The out door air temperature is 95 F at 3:00 p.m. From Table 25 the inside Venetian blind factor is 0.65. The instantaneous heat gains due to transmitted direct and (tiffuse solar radiation, and from convection and radiation gain, are found in Tables 12 and 13 as listed below for the south-facing doors and windows, the north-facing windows and the ^ glass doors in the east wall. The gain through the solid portion of the east doom may be approximated by use of Fig. 3, since the wood panels have little neat capacity. From Table 4 the diffuse radiation value is taken as 18 Btu per (hr) (sq ft) from which t, + aJi/fo, is found to be 98-2 for a =* 0.7 and fa% TM 4.0. From Fig. 3, q -- 22.0 Btu per (hr) (sq ft). These heat gains are itemised in the following table.
Location
Abu Sq Ft
Thais
Cow Total
Frac Solas AMO RaO Gain Total
tion
Gain
Gain Bto/ Gain
Smut Btu/(hb) Btu/(kb) (hs) Btc/bs
(sq ft) (SQ Ft) (Q ft)
South windows* South doors
Wood North windows
60 0.462
35 1.00
_18 _18
30 --
13 42
_14
15
Total................
19 32 1920 19 61 2135
17 31 560 22 22 395 17 32 960
5970
* Shade tutor - 0.63.
In some jobs it would be desirable to increase (or decrease) the instantaneous radiation heat gain by a load-lag factor. The reason for not doing so in this case is that the solar gain is of a low magnitude, and reference to the table indicates that 0.8 of the previous hour would not affect the results materially.
Heat Gain from Ventilation and Infiltration:
Since the desired outdoor air rate 1275 cfm is greater than one air change per hour, it will be satisfactory for determining the ventilation component of the heat gain.
Window infiltration can be taken as negligible since the windows do not open.
Door infiltration requires some judgment. Assume that for each person passing through the double doors, the infiltration will be 100 cu ft of outdoor air, see Chapter 10, Table 3. Assume that the outside doors will be used at the rate of 10 persons
er hour and the inside doors at the rate of 30 persons per our. Total infiltration will then be 40 X 100 = 4000 cfb or 67 cfm. The design rate of entry of outdoor air is then:
Q - 1275 + 67 - 1342 cfm.
The sensible, latent, and total loads are determined from Equations 7, 8, and 9, respectively, at 3:00 p.m. (J# -- 95, (, 80, * 0.0168, Wt = 0.0093). All the air entering the room os infiltration becomes a part of the space load. Infiltration (see Equations 7, 8, and 9):
q. = 67 X 1.08 (95 - 80) - 1085 Btuh, sensible,
j, - 67 X 4840 (0.0168 - 0.0098) = 2270 Btuh, latent.
?*-?. + . - 1085 + 2300 = 3385 Btuh, total.