Document jBNG2yR0Rnbx5LQQGpw2Qpzj2
HEATING VENTILATINC AIR CONDITIONING CUIDE 1942
In an investigation recently conducted at the University of Pittsburgh, in a cooperative research program with the Society, comparative studies were made on the bacterial content of conditioned and non-conditioned operating rooms. From these studies4 it was concluded that the bacterial content of conditioned operating rooms was considerably less than that of non-conditioned rooms. Although this difference may not be great it is sufficient to demonstrate that properly conditioned spaces with adequate filtration can definitely reduce the bacterial and other foreign substance content in an enclosure.
The increasing incidence of allergies or of their recognition is becoming a factor in the operating room. Operations may be postponed on allergic patients during asthmatic manifestations through fear of complications. The removal of the allergens, therefore, is in some cases an important function of the air conditioning system.
Central system air conditioning plants and unit air conditioners prove satisfactory in operating rooms when producing between 8 and 15 air changes per hour of filtered and properly conditioned air without recircu lation during the course of anesthesia. A separate exhaust fan system is as a rule necessary to confine and remove the gases and odors. Double windows are desirable and often necessary to prevent condensation and frosting on the glass in cold weather and to minimize drafts. The high air flow of 8 to 15 air changes in operating rooms is desirable for three reasons: (1) to reduce the concentration of the anesthetic to well below the physiologic threshold in the vicinity of the operating personnel, (2) to remove the great amounts of heat and sometimes moisture, from sterilizing equipment if inside the operating room, from the powerful surgical lights, from solar heat, and from the bodies of the operatives, and (3) to provide extra capacity for quickly preparing the room for emergency operations. Much can be gained by careful insulation of sterilizing equipment and by thorough exhaust ventilation of sterilizing rooms adjoining the operating rooms.
A very common complication presumably traceable to operations is pneumonia. The difference' in conditions between the operating room and the final hospital destination of the patient, including corridors and elevators, is conducive to post-operative pneumonia. A suggested remedy is a recovery ward where conditions closely approximate those of the operating room and in which the patients remain from one to four days. Satisfactory conditions in the recovery ward not only hasten convalescence, but dispel the fear frequently found'in patients who must undergo operations during the hot seasons5.
Sterilization of Air in Operating Room
Of considerable significance to operating rooms and contagious wards is the use of ultra-violet radiation for sterilizing the air6. Results reported7
4Report on Air Conditioning in Surgery, by W. Leigh Cook, Jr. (Department of Industrial Hygiene. School of Medicine, University of Pittsburgh, 1940).
`Report of the Committee on Air Conditioning (The American Hospital Association, 1937, p. 2).
Air-Borne Infection and Sanitary Air Control, by W. F. Wells (Journal Industrial Hygiene, 17:253, 1925).
'Sterilization of the Air in the Operating Room by Special Bactericidal Radiant Energy, by Deryl Hart {Journal Thoracic Surgery, 0:45, 1936).
700
CHAPTER 37. AIR CONDITIONING IN THE TREATMENT OF DISEASE
would indicate that the post-operative temperature rise of patients
during the first few days is in most instances caused more by bacterial
contamination of the operative wound than by the absorption of blood
and traumatized tissues. Operating room infections, which were quite
frequent before the installation of special ultra-violet lamps, are ap
parently being reduced.
.
Direct ultra-violet radiation is distinctly advantageous in sterilizing
not only the site of operation but also wounds to prevent the spread of
infection. In infants' wards, contagious disease wards, and even in
school rooms, the sterilizing effects are definitely known. Whether an
air conditioning system with, ultra-violet installations in the ducts is a
feasible procedure is controversial; but it would appear that this indirect
method is not as satisfactory as the direct in the. light of present reported
knowledge. .
.
Table 3. Net Mortality of Premature Infants According to Humidity* Infants Hospital, Boston, Mass,
Unconditioned Nurseries (1923*1925)
Conditioned Nurseries (1926-1929)
Cause or Death
Natural Humiditt
Acute and chronic infections......... Congenital deformities.................... Unclassified........... ...........................
All causes...;.... -...............................
Per Cent Mortality
26.5 1.2 1.2
28.9
Relative Humiditt
25-49
Per Cent
50-75
Per Cent
Per Cent Mortality
9.7 0.0 4.8
Per Cent Mortality
0.0 0.7 0.0
14.5 0.7
Excluding cases with multiple congenital anomalies incompatible with life, and also deaths occurring -within 48 hours after admission to the hospital.
NURSERIES FOR PREMATURE INFANTS
One of the most important requirements in the , care of premature infants is the, stabilization of body temperature. This is because their heat regulating systems are not fully developed; the metabolism is low and the infants generally exhibit marked inability to maintain normal body temperatures. The resistance to infection is low and mortality rate high.'
Air Conditioning Requirements The optimum air conditions for the growth and development of these
infants were determined by extensive research8 at the Infants Hospital, Boston, Mass., using four valid criteria, namely, stability of body temperature, gain in weight, incidence of digestive syndromes, and mor tality. Individual temperature requirements varied widely (from 72 to
The Premature Infant: A Study of the Effects of Atmospheric Conditions on Growth and on Develop ment, by K. D. Blackfan, C. P. Yaglou and K. McKenzie (American Journal Diseases of Children, 46: 1175, 1933).
701