Document gebn4xqDzRaGRyGXNqkk9o0L
444
i CHAPTER 18
-.
1953 Guide
y. Table 7. Steam Consumption of Buildings with Vabious Ttpes of Occupancy*
Type or Building
No. Bldgs.
Average
Volume Heated
Space 1000 Cu Ft
Steam for Heating
Lb per DD per 1000
. Cu Ft .
Average Hours op
Occupanct
Office........................................ Office and Bank.................... Offioe and Printing............... Office and Theater............ Office and Stores or Shops..
Bank............................ Department Store.'.. Stores.......................... Loft........................... Warehouse..................
Hotel and Club.. Apartment or Residence.. Thheateerr................................ Garage............... Manufacturing.
Church..'......... ;.......... i: i. Hospital........................... ____________ School... ...................................... Municipal or Federal.____ Lodge, Gym, Hall or Auditorium... Miscellaneous................ .......................
334
2160
0.685
12.1.
49
3000
0.577
13.1
8
1895
1.230
17.7
7
4950
0.412
.12.9
28 1615 0.617 13.2
16 806 0.786 11.7
63
3400
0.385
11.1
73
. 310
0.624 .
10.4
.63 865 0.588 10.0
24
2230
0.459
9.4
73
1795
0.990
22.3
61
1425
0.962
'21.8-
22 1240 0.482 12.9
1013 1640 0.202 21.4
1350
0.808
` 9.5'
9
656
0.532 ~ '
7.9
4
3306 . 1.194
: 22.0;
8 1115 0.592 11.5
15
3215
0.587
15.6
12 880 0.390 12.4
7
1387
0.479 -
21.4
1 Principles of Economical Heating, National Association of Building Owners and Managers.
than approximately 70 F is to be used, the number of degree-days should be obtained for the new base.
- Example 7: An eight-story building in Pittsburgh is operated with a daytime temperature of 70 F. The calculated heat loss is 10,500 Btu per (hr) (degree temper ature difference). What is the estimated average yearly steam consumption for building heating?
Solution: Since the average inside temperature is approximately 70 F, the degreedays from Table 2, based on 70 F may be used. Therefore, from Table 2, Pittsburgh has 5430 degree-days per normal season. Inserting in Equation 5:
F_ = 1--0,-5-0--0--X----2-4;---X---5--4-3-0 = 1,368,000 lb o,f s;team.
Consideration .has been given to the difference in steam utilization of different types of buildings, and Table 7 shows actual average units for these various types. These figures were obtained from operating results in 896 buildings located in all sections of. the United States. Being aver ages, and for small groups in each type, the figures may heed considerable modification, to allow for local variations. It should be especially noted that the steam used for heating water for service is not included in the values given in Table 7.
Example 8: A store in Philadelphia with a heating system designed to maintain 70 F inside in 0 F weather has 250,000 cu ft of heated space. What would be the estimated average yearly steam consumption of purchased steam for heating?
Solution: According to Table 7, a store would use 0.624 lb of steam per degree-day per 1000 cu ft heated space. From Table 2, Philadelphia has 4739 degree-days per normal year. Inserting in Equation 4:
F = 0.624 X 250 X 4739 = 739,000 lb of steam.
Degree-Day as an Operating Unit
The degree-day is also widely used as a means of comparing the efficiency of the fuel consumption of one period with another for the same building.
^Estimating Fuel Consumption for Space.Heating
445'
Since the fuel consumption is proportional to the weather- (degree-days), and since the periods to be compared may not have the same weather con ditions, the comparison can be-made only after the fuel Consumptions have been computed on a comparable weather basis, that is, upon the actual number of degree-days occurring for a given month and year in the city under consideration. Since fuel consumption.is proportional to the number of degree-days, plant operators frequently compute each month the fuel burned per degree-day by the heating plant. The resulting unit value, by eliminating the outside temperature variable, indicates whether the operating efficiency of the plant is above or below the previous month or
year.
The figures in Table 8 illustrate a typical example of a method of using the degree-day for making heating comparisons for one building for two
Table 8. Heat Consumption Recobd fob Compabison
Col. 1
Col. 2
Col. 3
Col. 4
Col. 5 Col, 6
Col. 7
Total
Consumption
Consumption For Heating
Avg Temp.
Deg Days Lb/Dbg
65 F Base
Dat
Lb/Dbg M Cu W
/
Sept...........
337,500
3 Oct............
834,200
Nov........... 1,446,600
o 2,176,400 s Jan............ .2,332,200 H Feb............ 2,131,100
2,021,900
Apr............ 1,241,500
May..........
672,500
< 258,600
W .Tulv
180;i00
170,500
667,200 1.279,600 2,009,400 2,165,200 1,964,100 1,854,900
1,074,600 505,500 91,600
.
65 53 . 44
25 22 .
28 31
43 55
146 339 641
1,233 1,297 1,106 1,032
647 303
50
.
1.170 1,966
1,990 1,630 1,670
1,775 1,799
1,660 1,670
1,830
0.575 0.970 0.982 0.804
0.822 0.888 0.885 0.818 0.822
0.905
13,821,000
330,200
Oct............
887,100
X Nov........... 1,625,200 2,045,500
1,933,400
-- Feb............ 1,990,200
Mar............ 1,984,100
146,200 703,100 1,341,200 . 1,861,500
1,749,400 1,806,200
1,800,100
61 167 875 0.431
52 410 1,718 0.845
39 812 1,653 0.815
28
1,120
1,660
0.817
30 - 1,044 1,670 0.825
30
1,111
1,624.
0.800
31
1,021
1,760
0.868
If, for example, the heat consumption in March, 1943,'is compared with that in March, 1944, it will be found that in the latter the steam consumption is 1799 -- 1760 *= 39 lb less which is a decrease of 2.2 percent.
consecutive heating seasons. The heat quantity figures inserted are pounds of steam, but a similar comparison could be made using pounds of coal,
gallons of oil, or cubic feet of gas.
For such a comparison, a two-year record, as shown in Table 8, is often used. The year under consideration may then be compared, month by month, with the previous year. Column 3, Consumption for Heating, would be used if the same fuel is used for heating and process steam. Some reason able figure must be assumed for the process requirement and should be deducted from the amount shown in column 2. This would leave in column 3 only the fuel chargeable to heating.' The degree-day values in column 5 are obtainable from the local Weather Bureau. Values in column 6 are obtained by dividing corresponding values in column 3 by the degree-days in column 5. The heating index in column 6 is, then, a figure of heat con sumption, corrected for outdoor temperature, and should be relatively con stant month by month. Column 7 in Table -8 may be used if the heat consumption is to be compared on a building volume basis with average values shown in Table 7.