THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-04 14-JUN-1996
PAGE 1 OF 2
MCC's
ELECTRICAL SAFETY AND RELIABILITY AUDIT CHECK LIST FOR
MOTOR CONTROL CENTERS (MCC'S)
MCC LOCATION I.D. #: MCC EQUIPMENT I.D. #:
'7
Yes No N/A
1. Is the MCC equipped with a main disconnect?
2. Is the MCC equipped with molded case circuit breakers?
___________
j/
3. Is the working space clear in front of all MCC's?
4. Are all MCC's properly grounded?
ts
5. Are all holes in doors or panels in MCC's covered with approved coverings that would withstand fault*pressures and temperatures?
/
6. Are all required bolts or fasteners on cubicle doors?
7. Is the MCC free of corrosion?
8. Is the eqipment designed to prever exposure
_j/ _to energized bus when doors are
or closed?
9. Are tall indicating lamps funcctcnai?
V_
10 . Is the manufacturer nameplate in place and
legible?
.11 Does the MCC have provisions to lock-out the
equipment?
12 . Is the MCC on a PPM Program?
j/ _
13. Are the fuse sizes and relay settings according to standards?
14. Does the working clearance in front of all MCC's meet local code requirements?