Document gb1vmpjGLRrLdddnorrGrbv0J
940
CHAPTER 43 -
1953 Guide
of brines. Ammonia precipitates calcium and magnesium salts,. thus cloggingthesystem at restricted-points. -
The addition of caustic soda and. sodium dichromate to brine solutions to inhibit corrosion of iron, is a more or less general practice. . Sodium sili-' cate and sodium phosphate are also used at' times, but tests indicate they are not as effective as is sodium dichromate. It has been suggested20 that 125 lb of sodium bichromate per 1000 cubic feet of calcium chloride brine, and 200 lb per 1000 cubic feet of sodium chloride brine, be added to inhibit brines; that when salt or calcium chloride is added to "strengthen" brine, sodium dichromate also be added in the amounts shown in Table 7.
Refrigerants. The common refrigerants, except those of the hydro carbon type, will attack the common metals and alloys if moisture is ;present. Even a very small amount of water may cause severe, corrosion
. Table 7. Quantities op Sodium Dichbomate to. be Added to Maintain Initial Concentration
Specific Gravity op . Brine to be Strengthened
1.16 1.18 t 1.20 1.22 1.24
1.12 1.14 1.16 1.175
Lb Sodium Dichromate per 100 lb CaC It Added
0.695 0.621 0.556 0.502 0.455
Lb of Sodium Dichromate per 100 lb NaCl Added
1.79 1.47 1.32 1.18-
with certain refrigerants. The amount required need only be sufficient to produce a water film on the metal surface.
' With the halogenated hydrocarbons, complete elimination of water is much to be desired. Where ammonia is used, copper and its alloys, aluminum and zinc, are attacked especially at elevated temperatures. When sulphur dioxide is used, more than 50 ppm (0.005 percent) of water will cause appreciable corrosion of virtually all the common materials.
Minimizing Condensate Corrosiveness
There are four expedients that may be utilized to minimize corrosion
in steam condensate systems: (1) treatment of the boiler feedwater so
as to eliminate deleterious gases entrained with the steam, (2) design of
the condensing equipment to minimize. dissolution in the condensate, of
the deleterious gases entrained with the steam, (3) chemical treatment
of the condensate, (4) use of resistant metals.
i
Boiler Feedwater Treatment. Elimination of oxygen from boiler feedwater and, therefore, from the steam developed, can be accomplished either mechanically or chemically. In some steam generating stations, both expedients are employed.
Tests21 have indicated that in small low-pressure heating boilers, where the boiler input contains less than about 50 ppm of carbonate hardness,
Coirosion and Water Formed Deposits, Causes and Prevention
.941
rthe-CQ^in the steam :can be controlled by adding calcium hydroxide:to the boiler/ In Fig. 5 are shown the equilibria conditions proposed for boilers operating at pressures up to about 5 psi gage. This expedient may 'not be used in higher pressure boilers, because of the possibilities of scale and sludge formations. In the latter, the only method used to date, for ,,treating the feedwater consists of removing the alkaline earth salts, i.e., rsoftening, and subsequent acidulation followed by deaeration at tempera tures near, the atmospheric boiling point of water.22
.Design of Condensing Equipment. In the design of water heaters and comparable types of condensing equipment,23 it is possible to shift-the accumulation of non-condensible gases to a location away from the con densate level and, subsequently, vent these gases to the atmosphere.
Fig. 5. Relation of Hydbate/Cakbonate Content in Hard Boileb Wateb and COj in Steam at About 5 Psi Opebating Pbessube
'{All analytical values are ppm by weight)
Venting an amount of steam equal to about one-half percent of the total steam entering the condenser is the .optimum vent rate.
Venting is of little practical value when the CO content of the in coming steam is below about 5 ppm. When the steam contains more, than 5 ppm, venting provides a means of producing a condensate containing a minimum of about 3 ppm. However, even as little as 3 ppm of dissolved CO* can produce active corrosion if large amounts of condensate are flowing.
Chemical Treatment of Condensate. Condensates containing compara tively large amounts of oil, are practically non-corrosive, due to the pro tective film provided by the oil. When oil is intentionally added to con densate,24 inadequate quantities may accelerate rather than decelerate corrosion on those surfaces not covered by the oil. Sodium silicate added to COj-bearing condensate has been shown to decrease, but not entirely prevent, corrosive action. It is not definite whether the protection afforded by silicate, solutions is due to the establishment of a protective